ARE Series Chargers
RS-759, Rev. 11
6-2
6.5
ENVIRONMENTAL RATINGS
Ambient Temperature:
0 °C to 50 °C up to 3,000 feet
Storage Temperature Range:
-40 °C to +85 °C
Relative Humidity:
0 to 95 percent, without condensation
Altitude:
Up to 10,000 feet, derated for 50 °C
Heat Dissipation:
See Table in 6.7
Audible Noise:
The audible noise measured at a distance of five feet from any vertical surface does not exceed
65dBA.
6.6
OPTIONAL EQUIPMENT
No Charge Alarm:
Signals when the DC current falls below a preset value. Indicator light optional.
Load Sharing:
Furnished as part of the no charge alarm. Circuitry is provided which will proportionally divide
the load between two or more rectifiers within ± five percent of the current rating of the largest unit from 10
percent to 100 percent of that rating.
High and Low DC Voltage Alarm:
Signals when a preset high or low DC voltage condition occurs.
Indicator light optional.
High or Low DC Voltage Alarm with
adjustable time delay of 1 to 180 seconds. Indicator light optional.
Ground Detector Alarm Relay:
Signals when a ground occurs, providing means of remote indication. Indicator
lights optional.
Ground Lights:
Positive and negative ground indicator lights indicate ground.
Ground Lights with Test Switch:
Momentary test switch with center off permits checking of positive and
negative individually.
Ground Lights with Lamp Test Switch:
Momentary test switch with center off permits checking grounds on
both positive and negative simultaneously. Opposite side of switch permits testing for indicator light failure.
Voltmeter Ground Detector Switch:
Momentary center off switch permits testing for positive and negative
grounds through the DC voltmeter.
0 – 255 Hour Equalize Timer
Blocking Diode
Lightning Protective Device
One Percent Voltmeter and Ammeter
6.7
“ARE” SINGLE-PHASE GENERAL SPECIFICATIONS
MODEL
DC
VOLTS
DC
AMPS
NO.
CELLS
AC
VOLTS
AC
AMPS
FLOAT
RANGE
EQUALIZE
RANGE
RIPPLE MV (RMS)
ON BATT. OFF BATT.
HVSD
SETTING
BTU/HR
HEAT
DISSIPATION
ARE24AC6E
ARE24AC12E
ARE48AC6E
ARE48AC12E
ARE130AC6F
ARE130AC12F
ARE130CE12F
AFE130AC16F
ARE130AC25F
ARE130CE25F
ARE130AC35F
ARE130CE35F
ARE130CE50F
24
24
48
48
120
120
120
120
120
120
120
120
120
6
12
6
12
6
12
12
16
25
25
35
35
50
12
12
24
24
60
60
60
60
60
60
60
60
60
120/208/240
120/208/240
120/208/240
120/208/240
120/208/240
120/208/240
208/240/480
120/208/240
120/208/240
208/240/480
120/208/240
208/240/480
208/240/480
2/1.1/1
4/2.3/2
4/2.3/2
7/4/3.5
8.5/5/4
18/10/9
10/8.8/4.4
22/13/11
35/20/17
20/17/8.5
50/29/25
29/25/12.5
40/35/17.5
24-27
24-27
48-55
48-55
120-138
120-138
120-138
120-138
120-138
120-138
120-138
120-138
120-138
FL-30
FL-30
FL-60
FL-60
FL-150
FL-150
FL-150
FL-150
FL-150
FL-150
FL-150
FL-150
FL-150
-
-
-
-
30
30
30
30
30
30
30
30
30
30
30
30
30
100
100
100
100
100
100
100
100
100
30
30
60
60
150
150
150
150
150
150
150
150
150
65
130
130
260
325
650
650
870
1355
1355
1900
1900
2710