UniPOS
Interactive Fire ControlPanel IFS7002
Instruction Manual
Page
94
Revision 2.05
Of 107
Table 4
Trouble Indication Troubleshooting
Fatal system error
Indicators
and
illuminate in
steady yellow light; the local sounder
releases continuous signal
The trouble shall be fixed in
Technical Service and
Maintenance Department
Low backup batteries
due to interrupted
mains power supply
The local sounder releases
discontinuous signal (1s sound, 3s
break); the message
Battery Low
appears on the screen; the backlight of
the display is off
Restore the mains power supply
or replace the backup batteries
Short circuit or Open
loop
Indicator
flashes in yellow light;
the local sounder releases discontinuous
signal; information table with the number
of faults appears on the display
Eliminate the fault (short circuit
or open loop)
Activated isolator of
addressable device
Indicator
flashes in yellow light;
the local sounder releases discontinuous
signal; information table with the number
of faults appears on the display
Eliminate the fault (short circuit
in the loop)
Fault condition
Uninitialized loop
Indicator
flashes in yellow light;
the local sounder releases discontinuous
signal; information table with the number
of faults appears on the display
- Eliminate the fault (open loop);
- Restore the loop so it complies
with the configuration saved in
the controlpanel and start
initialization of the control panel;
- Start clean initialization of the
control panel
Fault Exceeding
number of devices in
the loop, Uninitialized
device, Exchanged
devices, Different ID
number of device,
Different device type,
Different device
temperature class
Indicator
flashes in yellow light;
the local sounder releases discontinuous
signal; information table with the number
of faults appears on the display
- Restore the loop so it complies
with the configuration saved in
the controlpanel and start
initialization of the control panel;
- Start clean initialization of the
control panel
Fault Removed device
Indicator
flashes in yellow light;
the local sounder releases discontinuous
signal; information table with the number
of faults appears on the display
Instal the device
Fault Communication
error with the device or
Fault in device
Indicator
flashes in yellow light;
the local sounder releases discontinuous
signal; information table with the number
of faults appears on the display
Repair or replace the device (if
you replace the device then run
clean initialization of the control
panel)
Fault Contaminated
sensor (only in
detectors with optical-
smoke part)
Indicator
flashes in yellow light;
the local sounder releases discontinuous
signal; information table with the number
of faults appears on the display
Remove the detector and clean
the optical part and place it
again.