UniPOS
Interactive Fire ControlPanel IFS7002
Instruction Manual
Page
73
Revision 2.05
Of 107
−
If the number is higher than the number of outputs, activated by the addressable input the last
output will be selected.
Simultaneously the number in the
Go to
field is deleted; i.e. the field is deactivated.
When you press button
and the
Go to
field is empty, the list of outputs activated by the
addressable input will be deleted. When the last output from the list is deleted, a screen with the
message
No addressable outputs activated by this input
appears; the only option is to exit the menu.
13.6.3. Menu
Add addressable output
The menu allows the user to add separate addressable outputs to the list of outputs subject to
activation by the addressable input. Enter the menu to display:
−
If no free addressable outputs, not included in the list, are available – a screen with the
message
No unused outputs
appears; the only optio is to exit the menu;
−
If a free addressable output,
not included in the lis, is
available – a screen
displaying the first free
addressable output:
For each addressable output is
displayed:
−
The loop where the input
module is included in; the
module address in the loop
and the number of the output
in the module, if more than
one – in the top line;
−
Text message for the module
– in the line beneath.
The selected addressable output
is pointed by arrow – „
>>
”.
Buttons
and
in the right panel section are visualized if more than one free addressable
output is available, the
Go to
field and the digit buttons appear if free addressable outputs in more
than one module are available.
When you press a digit button, the
Go to
field is activated and you can enter a random 3-digit
number for the module. To edit the number, use button
and the last inserted digit will be deleted.
Devices obtain numbers according to the following sequence: from the first device in Loop 1 to
the last device in Loop 1; from the first device in Loop 2 to the last device in Loop 2.
When you press button
and a number is entered in the
Go to
field, the first free
addressable output in the first module whose number is equal to or higher than the number in the field
will be selected:
−
If the number is 0, the first free addressable output will be selected;
−
If the number is higher than the number of the module having the last free addressable output,
then the last output will be selected.
Simultaneously the number in the
Go to
field is deleted; i.e. the field is deactivated.
When you press button
and a number is entered in the
Go to
field, the field will be
deactivated.
When you press button
and the
Go to
field is empty, the output will be added to the list of
outputs, activated by the addressable input. When the last free addressable output is added, the
message
No unused outputs
appears; the only option is to exit the menu. When 12
th
addressable
Mode:DAY
17:53:49
Thu 24 Mar 2005
SetUp Input Lp1
А
ddr19.1
Go to:
Total:
11
>>
Lp1
А
ddr25.1
Point 1.025
0
1
2
3
4
5
6
7
8
9
С