4.2.1.
LED and sound indication
In this condition the indicator
(Fire) illuminates in red. The individual indicator
for Fire condition of a remote fire control panel is illuminated in red.
If the outputs for Fire condition phase are suppressed by button
(Outputs), the
LED indicator of the button illuminates in continuous red light.
The local sounder produces discontinuous signal. If the sound indication is
suppressed by button
(Alarm), the LED indicator of the button illuminates in
continuous red light.
4.2.2.
Text messages
For this condition the display is divided into two text panels, one in the first two lines
and the other in the last two lines. The panels provide information on the number of the
fire control panel and the respective line in fire condition. The second panel is displayed
if more than one line is in fire condition.
If more than 2 lines are in fire condition use the buttons
(Down)
(Up)
to review all lines in fire condition at the respective fire control panels.
4.3. Using the keypad
4.3.1.
Button
(Alarm)
Press it to:
−
switch the local sounder off if it was activated for Fire condition or Fault condition;
−
activate the local sounder if the fire control panel is in Fire condition or Fault
condition and the local sounder has been switched off by preceding pressing of
the same button.
The LED indicator of the button illuminates if the local sounder is switched off for
Fire Condition or Fault Condition.
Button’s operation does not effect and is not cancelled by the following events:
- a new fault condition will trigger the local sounder for Fault condition only.
4.3.2.
Button
(Outputs)
Button’s operation depends on the current access level and the operating mode of
the fire control panel.
Press it:
−
To suppress the outputs activated in Fire condition.
−
To activate the suppressed outputs, if any.
The LED indicator of the button illuminates if there are suppressed outputs for fire
condition.
4.3.3.
Button
(Reset line)
Press it to reset the line of the respective remote control panel shown in the top
panel of the display. After receiving a confirmation from the remote fire control panels
that their lines are reset and are not in fire condition, the Repeater enters Duty Mode.
4.3.4.
Button
(Menu)
Press the button to enter Information and Control Mode.
3