GENERAL DESCRIPTION

Button is compatible with Extinguishing

 

Fire Control Panel FS 5200E. It is designated for forced 

activation of the extinguishing process. The button is to be mounted close to the protected premise. 
Connect 

 

the

 

 button

 

 to

 

 the

 input

 

Manual Release

 of 

 

Control Panel 

FS

5200E. 

 

The connection 

line is monitored for short-circuit or interruption using end of line resistance

.

The button has a built-in switcher with one normally open contact and resistor of 1,5

 

k

? . 

When 

pressing the button, the contact is

 

closed and commutates circuit through resistor of 1,5 k

? . 

 When 

the button is 

 

situated 

 

at

 

 the end of the line

,

 it is necessary to connect

 

end of line resistance 

3

k

?  to

 

terminals

 ”+”

 and 

“-''(

fig. 2a, 2b, 2c).

FD3050Y  consists  of  :  surface  mounting  box  (pos.4

,

  fig.1),  a  carrier  unit  (po

s.

3

,

  fig.1), 

elastic 

element 

(pos.5

,

 fig.1), 

 

a test key(pos.6,

 

fig.1),

 

breakable seal(pos.7

,

 fig.1), cover(pos.2

,

 fig.1) and 

protective cover (pos.1

fig 1) :

To activate the Manual Release Button:

1

. Open the protective cover

fixed by means of the breakable seal.

2

Press  the  elastic  element

  by  mechanic  impact  on  the  marked  place  by  the  arrows

.

Forced 

extinguishing is activated.
To enable the button Manual Release
1.

 I

nsert the spiral end of the key into the hole (

f

ig.3) and press-to-end. The 

elastic element

 should 

fall. 

2. 

Place the flat end of the key into the hole (fig.3) and press-to-end. The 

elastic element 

 must 

return to its original position. 

3.

 Dismantle the cover (pos.2, fig.1) and replace the  torn breakable seal (pos.7, fig.1).

4

. Mount the cover by the reverse order and fix the protective cover by the breakable seal. 

5

. The button is ready for new activation.

TECHNICAL DATA

Switcher                                                  

 one normally open contact

 (NO)

Electrical installation            

by means of terminal for installation

2

wires with cross section

  (0,8-1,5) mm  

Degree of protection                   

IP 40

Operating temperature range      

from minus 10

°C  

to

  

plus 60

°C

Relative humidity resistance       

(93

±

3)% at 40

°

C

Dimensions                                 

90

 

õ 90

 

õ 44 mm

Material                                           

 ABS, yellow  

         

INSTALLATION

 

To install the button, please observe the following sequence:

1. 

Dismantle the basic components of the unit : the cover

,

 the carrier unit, and the back box shown 

on fig.1 by unscrewing the fixings.

2. 

Fix the back box on the wall by and dowels and self-tapping screws.

3. 

Join the wires of the input line to terminals (pos.8, fig 1a), located on the rare side of the carrier 

unit (pos.3, fig. 1).

4. 

If the button is the last one of several buttons FD3050Y (Fig 2b, 2c), additionally add end of line 

resistance

 

 of 

 

3k

?  

 to

 

 terminals

 ''+''

 and 

''-''

 for equalizing the line.

5. 

Consecutively mount to the back box of the button the following elements the carrier unit, the 

breakable seal, the 

 elastic 

 element

 

 with

 

 the 

 

sticker to the cover and the cover.

6. 

Fix the protective cover to the back box by means of the breakable seal.

7. 

Cut off the spare end of the breakable seal. Thus the breakable seal can be used twice for fixing 

the protective cover and indicates that the button has been used once

TESTING

The manual call point is tested after installation, as a part of the Extinguishing Fire Alarm System or 
after performing service schedule:

1. 

Testing

1.1. 

Turn on switcher Disable Extinguishing of the Control Panel.

1.2. 

An indicator 

''

Disable Extinguishing

''

 lights on in the Control Panel.

1.3. 

Insert the spiral end of the test key in the opening (fig.3) and press to end. The 

elastic 

 element 

should fall. The button is activated.

1.4. 

The Control Panel enters Fire Condition 2nd Stage. The relevant indicator lights on.

2. 

Enabling

2.1. 

Place the flat end of the key into the opening (fig.3) and press to end. The 

elastic

 element 

should move into its initial position.

2.2. 

The button is ready for use.

2.3. 

Restart

 

 the Control Panel.

2.4. 

Turn the mode selector key into its initial position. The indicator 

Disable Extinguishing

''

 lights 

off.

2.5. 

The Control Panel is in Duty Mode.

SERVICE SCHEDULE

1. 

Inspection for visible physical damage                                 - weekly

2. 

Satisfactory operation test in real conditions                        - monthly 

WARANTY

             

The warrant period is 36 months from the date of the purchase.
The manufacturer guarantees the normal operation of the fire detector providing that the service 
requirements of the instruction manual herein have been observed.
The  manufacturer  does  not  bear  warranty  liabilities  for  damages,  caused  through  accidental 
mechanical damages, misuse, adaptation or modification after the production of the product.
The manufacturer bears warranty liabilities for damages in the manual call point caused through 
manufacturer

'

s fault only.

BUTTON MANUAL RELEASE

TYPE

 FD3050

Y

INSTRUCTION MANUAL

 02-3050

Y

-04-11

Manufacturer: UniPOS Ltd., 4

7

 

San Stefano

 Street, Pleven 5800, Bulgaria,

 http://www.unipos-bg.com

GENERAL DESCRIPTION

Button is compatible with Extinguishing

 

Fire Control Panel FS 5200E. It is designated for forced 

activation of the extinguishing process. The button is to be mounted close to the protected premise. 
Connect 

 

the

 

 button

 

 to

 

 the

 input

 

Manual Release

 of 

 

Control Panel 

FS

5200E. 

 

The connection 

line is monitored for short-circuit or interruption using end of line resistance

.

The button has a built-in switcher with one normally open contact and resistor of 1,5

 

k

? . 

When 

pressing the button, the contact is

 

closed and commutates circuit through resistor of 1,5 k

? . 

 When 

the button is 

 

situated 

 

at

 

 the end of the line

,

 it is necessary to connect

 

end of line resistance 

3

k

?  to

 

terminals

 ”+”

 and 

“-''(

fig. 2a, 2b, 2c).

FD3050Y  consists  of  :  surface  mounting  box  (pos.4

,

  fig.1),  a  carrier  unit  (po

s.

3

,

  fig.1), 

elastic 

element 

(pos.5

,

 fig.1), 

 

a test key(pos.6,

 

fig.1),

 

breakable seal(pos.7

,

 fig.1), cover(pos.2

,

 fig.1) and 

protective cover (pos.1

fig 1) :

To activate the Manual Release Button:

1

. Open the protective cover

fixed by means of the breakable seal.

2

Press  the  elastic  element

  by  mechanic  impact  on  the  marked  place  by  the  arrows

.

Forced 

extinguishing is activated.
To enable the button Manual Release
1.

 I

nsert the spiral end of the key into the hole (

f

ig.3) and press-to-end. The 

elastic element

 should 

fall. 

2. 

Place the flat end of the key into the hole (fig.3) and press-to-end. The 

elastic element 

 must 

return to its original position. 

3.

 Dismantle the cover (pos.2, fig.1) and replace the  torn breakable seal (pos.7, fig.1).

4

. Mount the cover by the reverse order and fix the protective cover by the breakable seal. 

5

. The button is ready for new activation.

TECHNICAL DATA

Switcher                                                  

 one normally open contact

 (NO)

Electrical installation            

by means of terminal for installation

2

wires with cross section

  (0,8-1,5) mm  

Degree of protection                   

IP 40

Operating temperature range      

from minus 10

°C  

to

  

plus 60

°C

Relative humidity resistance       

(93

±

3)% at 40

°

C

Dimensions                                 

90

 

õ 90

 

õ 44 mm

Material                                           

 ABS, yellow  

         

INSTALLATION

 

To install the button, please observe the following sequence:

1. 

Dismantle the basic components of the unit : the cover

,

 the carrier unit, and the back box shown 

on fig.1 by unscrewing the fixings.

2. 

Fix the back box on the wall by and dowels and self-tapping screws.

3. 

Join the wires of the input line to terminals (pos.8, fig 1a), located on the rare side of the carrier 

unit (pos.3, fig. 1).

4. 

If the button is the last one of several buttons FD3050Y (Fig 2b, 2c), additionally add end of line 

resistance

 

 of 

 

3k

?  

 to

 

 terminals

 ''+''

 and 

''-''

 for equalizing the line.

5. 

Consecutively mount to the back box of the button the following elements the carrier unit, the 

breakable seal, the 

 elastic 

 element

 

 with

 

 the 

 

sticker to the cover and the cover.

6. 

Fix the protective cover to the back box by means of the breakable seal.

7. 

Cut off the spare end of the breakable seal. Thus the breakable seal can be used twice for fixing 

the protective cover and indicates that the button has been used once

TESTING

The manual call point is tested after installation, as a part of the Extinguishing Fire Alarm System or 
after performing service schedule:

1. 

Testing

1.1. 

Turn on switcher Disable Extinguishing of the Control Panel.

1.2. 

An indicator 

''

Disable Extinguishing

''

 lights on in the Control Panel.

1.3. 

Insert the spiral end of the test key in the opening (fig.3) and press to end. The 

elastic 

 element 

should fall. The button is activated.

1.4. 

The Control Panel enters Fire Condition 2nd Stage. The relevant indicator lights on.

2. 

Enabling

2.1. 

Place the flat end of the key into the opening (fig.3) and press to end. The 

elastic

 element 

should move into its initial position.

2.2. 

The button is ready for use.

2.3. 

Restart

 

 the Control Panel.

2.4. 

Turn the mode selector key into its initial position. The indicator 

Disable Extinguishing

''

 lights 

off.

2.5. 

The Control Panel is in Duty Mode.

SERVICE SCHEDULE

1. 

Inspection for visible physical damage                                 - weekly

2. 

Satisfactory operation test in real conditions                        - monthly 

WARANTY

             

The warrant period is 36 months from the date of the purchase.
The manufacturer guarantees the normal operation of the fire detector providing that the service 
requirements of the instruction manual herein have been observed.
The  manufacturer  does  not  bear  warranty  liabilities  for  damages,  caused  through  accidental 
mechanical damages, misuse, adaptation or modification after the production of the product.
The manufacturer bears warranty liabilities for damages in the manual call point caused through 
manufacturer

'

s fault only.

BUTTON MANUAL RELEASE

TYPE

 FD3050

Y

INSTRUCTION MANUAL

 02-3050

Y

-04-11

Manufacturer: UniPOS Ltd., 4

7

 

San Stefano

 Street, Pleven 5800, Bulgaria,

 http://www.unipos-bg.com

GENERAL DESCRIPTION

Button is compatible with Extinguishing

 

Fire Control Panel FS 5200E. It is designated for forced 

activation of the extinguishing process. The button is to be mounted close to the protected premise. 
Connect 

 

the

 

 button

 

 to

 

 the

 input

 

Manual Release

 of 

 

Control Panel 

FS

5200E. 

 

The connection 

line is monitored for short-circuit or interruption using end of line resistance

.

The button has a built-in switcher with one normally open contact and resistor of 1,5

 

k

? . 

When 

pressing the button, the contact is

 

closed and commutates circuit through resistor of 1,5 k

? . 

 When 

the button is 

 

situated 

 

at

 

 the end of the line

,

 it is necessary to connect

 

end of line resistance 

3

k

?  to

 

terminals

 ”+”

 and 

“-''(

fig. 2a, 2b, 2c).

FD3050Y  consists  of  :  surface  mounting  box  (pos.4

,

  fig.1),  a  carrier  unit  (po

s.

3

,

  fig.1), 

elastic 

element 

(pos.5

,

 fig.1), 

 

a test key(pos.6,

 

fig.1),

 

breakable seal(pos.7

,

 fig.1), cover(pos.2

,

 fig.1) and 

protective cover (pos.1

fig 1) :

To activate the Manual Release Button:

1

. Open the protective cover

fixed by means of the breakable seal.

2

Press  the  elastic  element

  by  mechanic  impact  on  the  marked  place  by  the  arrows

.

Forced 

extinguishing is activated.
To enable the button Manual Release
1.

 I

nsert the spiral end of the key into the hole (

f

ig.3) and press-to-end. The 

elastic element

 should 

fall. 

2. 

Place the flat end of the key into the hole (fig.3) and press-to-end. The 

elastic element 

 must 

return to its original position. 

3.

 Dismantle the cover (pos.2, fig.1) and replace the  torn breakable seal (pos.7, fig.1).

4

. Mount the cover by the reverse order and fix the protective cover by the breakable seal. 

5

. The button is ready for new activation.

TECHNICAL DATA

Switcher                                                  

 one normally open contact

 (NO)

Electrical installation            

by means of terminal for installation

2

wires with cross section

  (0,8-1,5) mm  

Degree of protection                   

IP 40

Operating temperature range      

from minus 10

°C  

to

  

plus 60

°C

Relative humidity resistance       

(93

±

3)% at 40

°

C

Dimensions                                 

90

 

õ 90

 

õ 44 mm

Material                                           

 ABS, yellow  

         

INSTALLATION

 

To install the button, please observe the following sequence:

1. 

Dismantle the basic components of the unit : the cover

,

 the carrier unit, and the back box shown 

on fig.1 by unscrewing the fixings.

2. 

Fix the back box on the wall by and dowels and self-tapping screws.

3. 

Join the wires of the input line to terminals (pos.8, fig 1a), located on the rare side of the carrier 

unit (pos.3, fig. 1).

4. 

If the button is the last one of several buttons FD3050Y (Fig 2b, 2c), additionally add end of line 

resistance

 

 of 

 

3k

?  

 to

 

 terminals

 ''+''

 and 

''-''

 for equalizing the line.

5. 

Consecutively mount to the back box of the button the following elements the carrier unit, the 

breakable seal, the 

 elastic 

 element

 

 with

 

 the 

 

sticker to the cover and the cover.

6. 

Fix the protective cover to the back box by means of the breakable seal.

7. 

Cut off the spare end of the breakable seal. Thus the breakable seal can be used twice for fixing 

the protective cover and indicates that the button has been used once

TESTING

The manual call point is tested after installation, as a part of the Extinguishing Fire Alarm System or 
after performing service schedule:

1. 

Testing

1.1. 

Turn on switcher Disable Extinguishing of the Control Panel.

1.2. 

An indicator 

''

Disable Extinguishing

''

 lights on in the Control Panel.

1.3. 

Insert the spiral end of the test key in the opening (fig.3) and press to end. The 

elastic 

 element 

should fall. The button is activated.

1.4. 

The Control Panel enters Fire Condition 2nd Stage. The relevant indicator lights on.

2. 

Enabling

2.1. 

Place the flat end of the key into the opening (fig.3) and press to end. The 

elastic

 element 

should move into its initial position.

2.2. 

The button is ready for use.

2.3. 

Restart

 

 the Control Panel.

2.4. 

Turn the mode selector key into its initial position. The indicator 

Disable Extinguishing

''

 lights 

off.

2.5. 

The Control Panel is in Duty Mode.

SERVICE SCHEDULE

1. 

Inspection for visible physical damage                                 - weekly

2. 

Satisfactory operation test in real conditions                        - monthly 

WARANTY

             

The warrant period is 36 months from the date of the purchase.
The manufacturer guarantees the normal operation of the fire detector providing that the service 
requirements of the instruction manual herein have been observed.
The  manufacturer  does  not  bear  warranty  liabilities  for  damages,  caused  through  accidental 
mechanical damages, misuse, adaptation or modification after the production of the product.
The manufacturer bears warranty liabilities for damages in the manual call point caused through 
manufacturer

'

s fault only.

BUTTON MANUAL RELEASE

TYPE

 FD3050

Y

INSTRUCTION MANUAL

 02-3050

Y

-04-11

Manufacturer: UniPOS Ltd., 4

7

 

San Stefano

 Street, Pleven 5800, Bulgaria,

 http://www.unipos-bg.com