background image

ADDRESSABLE SOUNDER

TYPE

 

FD 7

20

4S

INSTRUCTION MANUAL 01-7

204S

-

11

-05

Producer: UniPOS LTD, 114 Grenaderska Street, Pleven 5800, Bulgaria, http://www.unipos-bg.com

INSTALLATION

     

To install addressable sounder FD7204S please follow the sequence:

     

1. Remove the cover from the sounder base by releasing the clips(fig.1, pos.

5

).

         

2. Fix the base on the wall of the protected premises using appropriate fixings(fig.1, pos.

4

). If 

necessary, remove the printed circuit board before that.

     

3. Complete the wiring as shown on fig. 2

 and in accordance with the construction projects of the 

site.

     

4.  Replace the cover and press it to the base until it is locked by the base's clamps.

TESTING THE SOUNDER

     

Test addressable sounder FD7204S after installation, as a part of the site's fire alarm system.

To test the sounder please follow the sequence:

     

1. Apply power to the sounder from the fire alarm control panel IFS 7002 via the signal and the power 

supply loops.

     

2. Wait until the sounder is set to Duty Mode and send a test command for activation through the fire 

control panel. The sounder shall enter Fire condition and shall produce a discontinuous sound signal of 
sound  level  110dB  and  frequency  3  kHz

/

3

,2

  kHz;  the  LED  indicator  (fig.  1,  pos. 

6

)  shall  illuminate 

continuously.

     

3. Send a reset command from the fire control panel to the sounder under testing. The sounder shall 

restore 

Duty

 Mode.

SERVICE SCHEDULE

1. Inspection for visible physical damage

weekly

2. Satisfactory operation test in real conditions

monthly

WARRANTY

           

The warrant period is 36 months from the date of purchase. The manufacturer guarantees the 

normal  operation  of  the  sounder  providing  that  the  exploitation  requirements  set  herein  have  been 
observed. The manufacturer does not bear warranty liabilities for damages caused through accidental 
mechanical damage, misuse, adaptation or modification after production. 

     

The  manufacturer  bears  warranty  liabilities  for  damages  in  the  sounder  caused  through 

manufacturer's fault only.

GENERAL DESCRIPTION

    

Addressable sounder type FD7204S is intended to produce sound signalization upon fire condition 

detected by fire alarm system IFS7000. 

       

The addressable sounder consists of a base(fig.1, pos.

2

), piezoelectric transducer(fig.1, pos.

9

), 

printed circuit board with connection 

terminal

 for wiring

 the signal loop 

SL

(fig.1, pos.

7

) and connection 

terminal

 for wiring

 the power loop 

PL

(fig.1, pos.

8

), cover(fig.1, pos.

1

). The LED (fig.1, pos.

6

)  illuminates 

to indicate the sounder's mode of operation:

         

-

 – the LED flashes repeatedly every 16 seconds.

         

-Fire condition

 – the LEDs illuminates constantly.

         

-Activated isolator in the signal loop

  – the LED flashes repeatedly with 1Hz frequency .

         

-Activated isolator in the power supply loop

  – the LED flashes repeatedly with 2Hz frequency.

       

The sounder is able to exchange information with Fire Control Panel IFS7000 via the signal loop, 

using a specialized protocol – UniTALK, and is power supplied via the power supply loop. The built-in 
short circuit isolators provide protection to both signal and power supply loops of the control panel thus 
increasing the reliability of the fire alarm system.

Duty Mode

TECHNICAL DATA

Supply voltage of the signal loop

(15-30)

V DC

Supply voltage of the power supply loop

(12-34)

V DC

Current of the signal loop in Duty Mode

300 

µ

А at 24 V DC

Current of the signal loop in Fire Condition

(2

±

1) mA 

at

 (15

-

30)V DC

Current of the power supply loop in Fire Condition

<

 60 mA

Sound level at 1 m distance

110 dB

Rated frequency of the sound signal

3 kHz

/3,2kHz

Type of the sound signal

double tonal

with 

frequency 

of 

change 

2 Hz

Operational temperature range

minus 10

°

С plus 70

°

С

Relative humidity resistance

(92

±3

)% 

at

 40

°

С

Dimensions 

112 /163 /48 mm

Weight

0,450 kg 

2

Cross section of the wires

< 2,5 mm

Degree of protection

IP 40

1293

051-2

Reviews: