background image

SINGLE 

 

OUTPUT 

 

MONITORED 

 

MODULE

ADDRESSABLE

TYPE

 

FD 7

20

3OC

INSTRUCTION MANUAL 02-7

203OC

Manufactur

er: UniPOS Ltd. 114 Grenaderska Street, Pleven 5800, R. Bulgaria, http://www.unipos-bg.com

INSTALLATION

   

Install it according to 

fig.

1 in the following sequence:

1.Dismantle the single output monitored module by unscrewing 

screws

 pos.7 and pos.5.

2.Installation holes and connecting 

wire

s holes are drilled on the designated places on the b

ottom

.

3.Fix  the 

bottom

  on  the  desired  place  by  means  of  pins  and  screws. The  connecting 

wires

  are 

threaded in advance in the box.
4.Install the 

unit carrier

 to the 

bottom

 by 

using

 

screws

 pos.5.

5.The electrical connection is done according to 

fig.2

. Connect the 

wire

s of the signal loop 

to the

 

terminals 

pos.1, of the power loop 

-

 to pos.

3

 and the 

external devices

 

-

 to pos.2. Connect the negative 

leads to “

-

”, the positive 

-

 to “

+

”, and the shield

s

 - to “

Å

”. It is not necessary to take into consideration 

the conditional beginnings and ends of the loops. It is recommended cable shoes to be used.
6.Place the cover to the bo

ttom

 by using screws pos.7

.

TESTING

   

The single output monitored module is tested after installation as a part of the site's fire alarm 

system or 

with

 maintenance activities.

   

The  output  of  the  module  is  tested  by  the 

F

ire 

C

ontrol 

P

anel.  It  should  be  activated  and  the 

respective indication to be on. When the menu is quitted, the single output monitored module should 
be 

enter

 

D

uty mode.

SERVICE SCHEDULE

   It is done by authorized personnel and includes the following activities:

1.Inspection for visible physical damage

- monthly

2.

T

est

ing

 in real conditions

- monthly

WARRANTY

    

The warrant period is 36 months from the date of 

sale

.

   

The manufacturer guarantees the normal operation of the unit providing that the requirements set 

herein have been observed. 

   

The  manufacturer  does  not  bear  warranty  liabilities  for  damages  caused  through  accidental 

mechanical damage, misuse, adaptation or modification after production. The manufacturer bears 
warranty liabilities for damages in the unit caused through manufacturer's fault only.

GENERAL DESCRIPTION

  

The single output monitored module is designed to control external devices for the fire 

alarm system

 

IFS 7000 by means of potential output “Open collector” in case of detecting fire conditions.

   

The single output monitored module 

(fig.1)

 consists of 

printed circuit board (pos.2) and 

an 

unit 

carrier  (pos.4),  fixed  in  a  plastic  box  with  bottom  (pos.1)  and  a  cover  (pos.3).The 

terminal

s  for 

connecting the signal loop 

SL

 (pos.1), the power loop 

PL

 (pos.

3

), and the external devices 

OUT

 

(pos.2) are located on the printed circuit board

 (fig 2)

.

 

 The communication between the 

F

ire 

C

ontrol 

P

anel and the single output monitored module is 

completed via the signal loop by the specialized data exchange protocol UniTALK. The single output 
monitored module is power supplied by the power loop. Two built-in isolators are provided for short 
circuit protection – one on the signal loop and one on the power loop.

   

Both LED indicators (fig.1, pos.6) provide information for the current status:

- Duty mode 

-

 red and yellow LEDs flash briefly every 16s;

- Activated output 

-

 the red LED produces continuous light, the yellow 

LED

 is not lit;

- Fault condition (activated isolator on the signal loop) 

-

 the yellow LED flashes briefly every 1s, 

the red 

LED

 is not lit;

- Fault condition (activated isolator on the power loop) 

-

 the yellow LED flashes briefly every 2s, 

the red 

LED

 is not lit

.

TECHNICAL DATA

S

upply

 voltage

:

- signal loop

(15-30)V

 

DC

- power loop

(12-30)V

 

D

C

Current consumption in 

D

uty mode:

- signal loop

300 µÀ

- power loop

2 mA

C

urrent consumption in 

Activated output

:

- signal loop

3 mA

- power loop

up to 

200 m

A

Output:

1 pc.

- type

potential, “Open collector”

- voltage

(1

1

-30)V

 

DC

- maximum current

200 mÀ

C

ross section

 of c

onnecting wires

(0,8-2,5) mm

²

Type of the connecting 

cables

:

- of the signal loop

two-wire, shielded

- of the power loop

two-wire

- of the 

external devices

two-wire

Degree of protection

IP 50

Operational temperature range

minus

 10º

Ñ - plus

 55º

Ñ

Relative humidity resistance

(93±3)% at

 40º

Ñ

Dimensions

120

x

164

x

74

 mm

Weight

0,250 kg

1293

051-2