OPTICAL SMOKE DETECTOR

WITH   ADDRESS  MODULE

OPTI^KO DIMNI 

JAVLJA^ PO@ARA

 

 

6130L

1. INTRODUCTION 

 
The Optical Smoke Detector is designed to provide 
early warning of a fire condition, by reacting upon a 
fixed smoke concentration level in the protected area.

 

1. UVOD 

Opti~ko dimni detektor je namenjen za otkrivanje 
po`ara u ranoj fazi, reaguju}i posle odre|enog praga 
koncentracije dima u za{ti}enoj zoni 
 

2. STRUKTURA I  PRINCIP RADA 

2. STRUCTURE AND FUNCTION 
 
The detector consists of two main parts: a base and a detector head. The 
latter comprises a circuit board and a chamber with great sensitive 
element. The contact plates are fixed to the base. 
The detector head is fixed on the base by the means of bayonet joints. 
When locating the detector head on the base, make sure the bench mark 
stands about 20 mm before the respective bench mark on the base; then 
rotate clockwise to fix. The bench marks should fully coincide when fixed. 
A flat point screw is provided on the detector head to prevent unauthorized 
removal. A 2 mm tip screwdriver is required for locking and unlocking. 
The principle of functioning is based upon smoke particles entering the 
detector head’s smoke chamber causing distraction of infrared rays within 
the chamber. The activation threshold of the detector is factory set at a 
specific smoke concentration level. Upon activation the two red LEDs, 
situated on the detector head illuminate (360

0

 visibility). They are 

extinguished by momentary interruption of the detector’s power supply. 
Detector’s type and sensitivity are marked. 
On fig.2 is shown DIP switch for the addresses and the address number 
label. The DIP switch is protected by a transparent cover. Address 
assignment is made through the DIP switch, according Fire Control Panel 
FS6000 Instruction Manual, Appendix 9. Fire detectors addressing is 
made via special communication protocol. 
 
3. PREPARING THE DETECTOR FOR OPERATION 
 
3.1 Connection diagram 
 
Connection diagram of a fire detector base to two-wire fire alarm line, 
using shielded wire, is shown on fig. 3. Shielded wire is strongly 
recommended for reducing electromagnetic interferences. 
 
3.2 Mounting 
 
Separate the base from the detector head by tuning the detector head in an 
anti-clockwise direction. 
Feed the connection cable through the cable entry in the center of the base. 
Fix the base on the ceiling using appropriate fixings. Completed the wiring 
as shown on fig.3. Fix the address label on its appropriate place. Pull the 
protection cover and assign the necessary address through the DIP switch. 
After completion replace the cover and press until a “click” sound is 
heard. 
Note: DIP switch should not be set to middle (null) position, because it 
would cause an incorrect reception of a fire detector address by the fire 
control panel. 
Replace the detector head on the base by offering the detector head to the 
base ensuring bench marks are no more than 20 mm apart. Rotate the 
detector head in a clockwise direction to completed location. 
Lock the detector head to the base by screwing the flat point screw, using 
a 2 mm tip screwdriver, ensure not to over tighten. 
 
3.3 Testing 
 
Test is made when the fire detector is connected to FS6000 control panel 
and according the provided test procedures. Place a permanent magnet on 
the detector heads surface at the point marked test periphery. The twin 
LEDs will illuminate. After removing the magnet the LEDs should remain 
lit until reset by momentary interruption of the power supply. In addition a 
simulation test of real fire conditions should be completed by a smoke 
probe. 
 
4. WARRANTY 
 
The manufacturer guarantees compliance with EN 54 Standard, Part 7. The 
warrant period is 36 months from the date of purchase, providing that 
requirements stated in the service schedule   have been observed. 

Detektor se sastoji iz dva osnovna dela: ku}i{ta i glave 
detektora. Glava detektora sadr`i {tampanu plo~u i dimnu 
detektorsku komoru. Kontaktni priklju~ci su fiksirani na 
ku}i{tu.  

Detekrorska glava je pri~vr{}ena na ku}i{te bajonetnom vezom. 
Pri postavljanju detektorske glave u ku}i{te reperi na ku}i{tu i glavi treba 
da su udaljeni oko 20 mm pre upadanja u `leb posle ~ega okrene}emo 
glavu detektora u smeru kazaljke na ~asovniku. do zabravljivanja. Reperi 
moraju biti poklopljeni. Pljosnati vijak zabravljiva~ je predvi|en za 
spre~avanje neovla{}ene demonta`e. Odvija~ od 2 mm je potreban za 
zaklju~avanje odn. otklju~avanje. 
Princip rada je baziran na rasipanju infracrvene svetlosti usled ulaska dima 
u komoru protivpo`arnog dava~a. To dovodi do aktiviranja fotoprijemnika. 
Prag aktiviranja je fabri~ki pode{en prema specifi~noj koncentraciji dima. 
Po aktiviranju oba indikatora na detektorskoj glavi, oni svetle crveno 
(vidljivo u krugu od 360 

0

). Resetuju se trenutnim kratkotrajnim prekidom 

napajanja detektora. 
Na detektoru su zna~eni tip i osetljivost detektora. 
Na slici 2 prikazan je DIP prekida~ za adresiranje i oznaka adrese javlja~a. 
DIP prekida~ je za{ti}en providnim poklopcem. Postavljanje adrese javlja~a 
vr{i se preko DIP prekida~a, prema Uputstvu adresne centrale FS6000, 
Poglavlje 9. Adresiranje javlja~a se omogu}ava specijalizovanim 
protokolom. 
 
3. PRIPREMA JAVLJA^A ZA RAD 
 
3.1 Shema veze 
 
Shema veze ku}i{ta javlja~a i dvo`ilnog voda sa {irmom je prikazana na 
slici 3. [irm se obavezno preporu~uje zbog otklanjanja elektromagnetnih 
interferenci. 
 
3.2 Monta`a 
 
Razdvojiti ku}i{te od glave detektora okre}u}i ga suprotono kretanju 
kazaljke na satu. 
Provu}i kabli kroz centralni otvor na ku}i{tu. Pri~vrstiti ku}i{te za zid ili 
plafon odgovaraju}om vij~anom vezom. Izvr{iti o`i~enje kao {to je 
prikazano na slici 3. Postaviti oznaku adrese na odgovaraju}e mesto. 
Ukloniti za{titni poklopac i dodeliti adresu pomo}u DIP prekida~a. Vratiti 
za{titni poklopac pritiskaju}i ga dok se ne ~uje zvuk “klik”.  
Napomena: DIP prekida~ ne setovati u srednji (nulti) polo`aj zato {to }e 
usloviti neta~nu detekciju po`ara protivpo`arne centrale. 
Vratiti glavu detektora u ku}i{te tako da reperi budu udaljeni oko 20 mm. 
Okrenimo glavu detektora u smeru kazaljke na satu do zabravljenja. 
Osigurajmo glavu detektora za ku}i{te pomo}u zabravljiva~a, ne prete`u}i, 
pomo}u dvomilimetarskog odvija~a. 
 
3.3 Test 
 
Test se sprovodi kada je javlja~ vezan za protivpo`arnu centralu prema 
predvi|enoj test proceduri. Staviti permanentni magnet na povr{inu  glave 
detektora na mestu TEST. Indikatori treba da svetle. Posle pomeranja 
magneta indikatori moraju i dalje da svetle sve do resetovanja indikatora. 
Test se mo`i izvr{iti i dimnom probom. 
 
4. GARANCIJA 
 
Proizvo|a~ garantuje da proizvod odgovara EN 54, Part 7. Garancijski rok 
je 36 meseci od dana kupovine, samo pod uslovima navedenim u servisnom 
planu. 
 
 