RATE OF RISE HEAT DETECTOR

WITH   ADDRESS  MODULE

TERMODIFERENCIJABILNI 

JAVLJA^ PO@ARA

 

 

6120L

1. INTRODUCTION 

 
The Rate of rise heat detector is designed to provide 
early warning of a fire condition reacting upon a 
sensitive rate of rise in temperature and/or upon 
reaching a fixed temperature threshold. 

1. UVOD 

Termodiferencijabilni javlja~ po`ara je namenjen za otkrivanje 
po`ara u ranoj fazi raguju}i na brzinu porasta temperature ili pri 
prelasku maksimalne zadate temperature. 
 

2. STRUKTURA I PRINCIP RADA 

2. STRUCTURE AND FUNCTION 
 
The detector consists of two parts: a base and a detectors head. The 
latter comprises a circuit board and a chamber with head sensitive 
element. The contact plates are fixed to the base. 
The detector head is fixed on the base buy the means of bayonet 
joints. When locating the detector head on the base, make sure the 
bench mark stands about 20 mm before the respective bench mark on 
the base, then rotate clockwise to fix. The bench marks should fully 
coincide when fixed. A flat point screw is provided on the detector 
head to prevent unauthorized removal. A 2 mm tip screwdriver is 
required for locking and unlocking. 
The principle of function of the detector is based on the ohmic 
resistance alteration in the thermistor as a result of the ambient 
temperature change. It detects a rise in temperature by sensing a 
differential in circuit resistance caused by changes in the state of the 
thermistors. 
Upon activation the detector illuminates two red LEDs, situated on 
the detector head (360

0

 visibility). The LEDs can be reset and 

extinguished by momentarily removing the power source. 
Detector’s type and sensitivity are marked. 
On fig.2 is shown DIP switch for the addresses and the address 
number label. The DIP switch is protected by a transparent cover. 
Address assignment is made through the DIP switch, according Fire 
Control Panel FS6000 Instruction Manual, Appendix 9. Fire 
detectors addressing is made via special communication protocol. 
 
3. PREPARING THE DETECTOR FOR OPERATION 
 
3.1 Connection diagram 
 
Connection diagram of a fire detector base to two-wire fire alarm 
line, usig shielded wire, is shown on fig.3. Shielded wire is strongly 
recommended for reducing electromagnetic interferences. 
 
3.2 Mounting 
 
Separate the base from the detector head by turning the detector head 
in an anti-clockwise direction. 
Feed the connection cable through the cable entry in the center of the 
base. Fix the address label on its appropriate place. Pull the 
protection cover and assign the necessary address through the DIP 
switch. After completion replace the cover and press until a “click” 
sound is heard. 
Note: DIP switch should not be set to middle  (null) position, because 
it would cause an incorrect reception of a fire detector address by the 
fire control panel. 
Replace the detector head on the base by offering the detector head to 
the base ensuring bench marks are no more than 20 mm apart. Rotate 
the detector head in a clockwise direction to complete location. 
Lock the detector head to the base by screwing the flat point screw, 
using a 2 mm tip screwdriver, ensure not to over tighten. 
 
3.3 Testing 
 
Test is made when the fire detector is connected to FS6000 Fire 
control panel and according the provided test procedures. Place a 
permanent magnet on the detector heads surface at the point marked 
test periphery. The twin LEDs will illuminate. After removing the 
magnet the LEDs should remain lit until reset by momentary 
interruption of the power supply. In addition a simulation test of real 
fire conditions should be completed by a heat probe. 
 
4. WARRANTY 
 
The manufacturer guarantees compliance with EN 54 Standard, Part 5. 
The warrant period is 36 months from the date of purchase, 
providing that requirements stated in the service schedule   have 
been observed. 

Detektor se sastoji iz dva osnovna dela: ku}i{ta i glave 
detektora. Glava detektora se sastoji od {tampane plo~e i 
termo elementa. Kontaktni priklju~ci su fiksirani na ku}i{tu. 

Detekrorska glava je pri~vr{}ena na ku}i{te bajonetnom vezom. 
Pri postavljanju detektorske glave u ku}i{te reperi na ku}i{tu i glavi 
treba da su udaljeni oko 20 mm pre upadanja u `leb posle ~ega 
okrene}emo glavu detektora u smeru kazaljke na ~asovniku. do 
zabravljivanja. Reperi moraju biti poklopljeni. Pljosnati vijak 
zabravljiva~ je predvi|en za spre~avanje neovla{}ene demonta`e. 
Odvija~ od 2 mm je potreban za zaklju~avanje odn. otklju~avanje. 
Princip rada  detektora se zasniva na promeni omskog otpora 
termistora kao rezultat promene spolja{nje temperature. On detektuje 
porast temperature o~itavaju}i razliku u otpornom kolu uslovljenu 
promenama stanja termistora. 
Posle aktiviranja  LED indikatori svetle crveno, i sme{teni su u glavi 
detektora (vidljivo u krugu 360

0

). LED indikatori mogu biti resetovani 

samo momentalnim kratkim prekidom napajanja detektora. 
Na detektoru su ozna~eni tip i osetljivost detektora. 
Na slici 2 prikazan je DIP prekida~ za adresiranje i oznaka adrese 
javlja~a. DIP prekida~ je za{ti}en providnim poklopcem. Postavljanje 
adrese javlja~a vr{i se preko DIP prekida~a, prema Uputstvu adresne 
centrale FS6000, Poglavlje 9. Adresiranje javlja~a se omogu}ava 
specijalizovanim protokolom. 
 
3. PRIPREMA JAVLJA^A ZA RAD 
 
3.1 Shema veze 
Shema veze ku}i{ta javlja~a i dvo`ilnog voda sa {irmom je prikazana 
na slici 3. [irm se obavezno preporu~uje zbog otklanjanja 
elektromagnetnih interferenci. 
 
3.2 Monta`a 

Razdvojiti ku}i{te od glave detektora okre}u}i ga suprotono kretanju 
kazaljke na satu. 
Provu}i kabli kroz centralni otvor na ku}i{tu. Pri~vrstiti ku}i{te za zid 
ili plafon odgovaraju}om vij~anom vezom. Izvr{iti o`i~enje kao {to je 
prikazano na slici 3. Postaviti oznaku adrese na odgovaraju}e mesto. 
Ukloniti za{titni poklopac i dodeliti adresu pomo}u DIP prekida~a. 
Vratiti za{titni poklopac pritiskaju}i ga dok se ne ~uje zvuk “klik”.  
Napomena: DIP prekida~ ne setovati u srednji (nulti) polo`aj zato {to 
}e usloviti neta~nu detekciju po`ara protivpo`arne centrale. 
Vratiti glavu detektora u ku}i{te tako da reperi budu udaljeni oko 20 
mm. Okrenimo glavu detektora u smeru kazaljke na satu do 
zabravljenja. 
Osigurajmo glavu detektora za ku}i{te pomo}u zabravljiva~a, ne 
prete`u}i, pomo}u dvomilimetarskog odvija~a. 
 
3.3 Test 

Test se sprovodi kada je javlja~ vezan za protivpo`arnu centralu prema 
predvi|enoj test proceduri. Staviti permanentni magnet na povr{inu 
glave detektora na mestu TEST. Indikatori treba da svetle. Posle 
pomeranja magneta indikatori moraju i dalje da svetle sve do 
resetovanja indikatora. 
Test se mo`i izvr{iti i sondom za topli vazduh. 
 
4. GARANCIJA 
 
Proizvo|a~ garantuje da proizvod odgovara EN 54, Part 5. Garancijski 
rok je 36 meseci od dana kupovine, samo pod uslovima navedenim u 
servisnom planu. 
 

 