3.5 Online Panel Session Commands
The following online panel session commands are available via the NION-MXL panel session. For a more compre-
hensive list and descriptions, consult your MXL documentation.
On-Line Session Command Table
Acknowledge Commands
History Commands
Command
Function
Command
Function
AAL
Acknowledge Alarm
HAL
Alarm history from time/date
ASP
Acknowledge Supervisory
HSP
Supervisory history from time/date
ATR
Acknowledge Trouble
HTR
Trouble history from time/date
ASCAcknowledge Security
HSC Security history from time/date
SUA
Silence/Unsilence Audibles
HAE
All events from time/date
List Commands
Control Commands
Command
Function
Command
Function
LST
List Status
CRS
Reset MXL panel
LAL
List Alarms
LON
Log On
LSP
List Supervisory
LOG
Log Off
LTR
List Trouble
LMP
Lamp Test of MKB-1
LSC
List Security
LCD
Test LCD display on MKB-1
LSS m
List Sensitivity (m=module number)
PWR m
Power report (m - PSR-1 or MMB-1 module number)
LAV m
List Analog Voltage (m=module number)
MLT m
MOI-1 Lamp test
LTV m
List Threshold Voltage (m=module number)
DEV m-d x
Device LED Control
m = module number
d = sub-address device LED
x = E for energize LED,
D for de-energize LED
LMT m
List Module Type (m=module number
LDT m
List Device Type (m=device number)
LMS m
List Messages (m=module number)
LSW
List Software Version
Miscellaneous Commands
Command
Function
Command
Function
CTD hh:mm:ss
nn-dd-yyyy
Reset time/date.
hh = 2-digit number of hours (24-hr format)
mm = 2-digit number of minutes
ss = 2-digit number of seconds
nn = 2-digit month of year
dd = 2-digit day of month
yyyy = 4-digits of year
CSS m-d x
Change Sensitivity
m = module number
d = sub-address of smoke detector
x = desired sensitivity setting
0-low3; 1-low2; 2-low1; 3-Norm;
4-hi1; 5-hi2; 6-hi3
CIP m-d x
Change (Arm/Disarm) Input Point
m = module number
d = sub-address of smoke detector
x = A for Arm, D for Disarm
COP m-d x
Change (Arm/Disarm) Output Point
m = module number
d = sub-address of smoke detector
x = A for Arm, D for Disarm
Figure 3-5: Online Panel Session Commands