![Uniks EVSE X7 Quick Start Manual Download Page 9](http://html1.mh-extra.com/html/uniks/evse-x7/evse-x7_quick-start-manual_3799602009.webp)
9
This allows to perform typical MFT
measurements:
Voltage,
frequency, phase indication,
phase sequence, various RCD
tests
and
measurements,
insulation resistance, low ohm
measure- ments, line and loop
impedances, ....
Typical connection between
EVSE X7 and NOVA or NOVA PRO
(Multifunction Installation Testers).
Test procedure:
•
connect the needed 4 mm test
plugs of the UNIKS EVSE X7to
your MFT,
•
select CP Mode
“A”
with the
slider switch,
•
connect UNIKS EVSE X7to the
Type-2 connector of the
charging point,
•
select CP Mode
“B”
with the
slider switch, the charging point
should show “ready to charge”,
•
select CP Mode
“C”
with the
slider switch, the charging point
•
should start charging,
•
perform all measurements in
active stage of the charging
point (voltage and similar),
•
after you completed all your
measurements select CP Mode
Summary of Contents for EVSE X7