background image

SHB_PNG07.fm

A31003-G2100-S100-2-7620, 03/2014
PNG Configuration for Gigaset M2 

plus 

and M2 Ex professional, Service Manual

39

   

  

  

PNG Configuration

Adjust Sensor

7.3

Adjust Sensor

This function is required to enable accelerometer sensors to identify when the handset is in an 
upright position.

Procedure:

1. Select 

Add. Features

 in the main menu.

2. Select 

PNG Configuration

.

3. Enter the requested PNG Service PIN and confirm with 

OK

; the default PIN is "00000". 

You are now in the PNG Configuration menu.

4. Select 

Adjust Sensor

 and confirm with 

OK

. The following text appears on the screen:

5. Hold the handset still and in a vertical position and confirm with 

OK

. The following text ap-

pears on the screen:

Once the adjustment is complete, the following message appears on the handset:

The vertical adjustment is tested again during the functional test.

Sensors must be readjusted after the handset has been initialised (reset to factory settings). 
They must also be readjusted if you replace the memory card.

Adjust Sensor

Please adjust  
handset  
in vertical position

Please wait 

 

for response

Sensor adjust  
passed!

Summary of Contents for Gigaset M2 Ex professional

Page 1: ...PNG Configuration for Gigaset M2 plus professional Gigaset M2 Ex professional Service Manual A31003 G2100 S100 2 7620 ...

Page 2: ...escriptions or characteristics of performance which in case of actual use do not always apply as described or which may change as a result of further development of the products An obligation to provide the respective characteristics shall only exist if expressly agreed in the terms of contract Availability and technical specifications are subject to change without notice Unify OpenScape OpenStage...

Page 3: ...Menu 11 Emergency Key 11 Preventing PNG Configuration Changes 12 Emergency Alarm Deactivation 12 PNG Configuration 13 Overview 13 Alarm Configuration 14 General Settings 15 Emergency Emergency key 26 Configuring Automatic Alarms 28 Alarm Signal 32 Control Ports 34 Adjust Sensor 39 PNG Service PIN 40 Factory Defaults 41 Sample Configurations 44 Operation in HiPath Cordless Enterprise with PNEZ 44 O...

Page 4: ...ons are identified The following types of alarms and signals are available Man Down Alarm Non Movement Escape Alarm The integrated motion sensor technology recognises motionlessness detects deviation from an upright position and sudden movement Pull Cord Alarm The system recognises when a magnetic contact which is plugged in on the underside of the handset and which can be attached to a person via...

Page 5: ...pplicable laws in other countries Employees of Unify are bound to safeguard trade secrets and personal data under the terms of the company s work rules A conscientious and responsible approach helps protect data and ensure privacy Use the password features of the system with no exceptions Never provide an unautho rized person with passwords either orally or in writing forinstance Prevent unauthori...

Page 6: ...aset M2 Ex professional A31003 G2100 U104 7619 Operating Manual HiPath 3000 HiPath 500 Gigaset M2 professional Gigaset M2 plus professional Gigaset M2 Ex professional to HiPath Cordless Office A31003 G2100 U102 7919 Operating Manual HiPath 4000 Gigaset M2 professional Gigaset M2 plus professional Gigaset M2 Ex professional to HiPath Cordless Enterprise A31003 G2100 U103 7619 Service Manual HiPath ...

Page 7: ...l describes how to configure the handset and indicates BGR 139 compliant set tings where applicable Activating the PNG functionality blocks certain handset settings for normal users forinstance PNG Configuration Reset Handset Select Base Register H Set etc You are requested to enter a PNG service PIN when you try to activate a blocked function The function will only activate if you enter the corre...

Page 8: ... that the alarm calls reach the alarm destination they are repeated until an alarm recall by the PNEZ has been identified or the set number of call repeats has been reached However there is no guarantee that all alarm calls will reach the programmed desti nation Consequently the PNEZ checks the communication channels to the PNG S and estab lishes contact with the PNG S on a cyclical basis If there...

Page 9: ...rm call count has been reached or until alarm repetition has been interrupted manually on the handset An alarm recall to confirm the alarm call ending the alarm repeats and possibly the silent mo nitoring of the person sending the alarm is only possible on HiPath 3000 versions which sup port CLIP transmission in the setup message Bear this in mind when configuring the number of alarm repetitions T...

Page 10: ...ure that the alarm calls reach the alarm destination they are repeated until the alarm call count has been reached or until alarm repetition has been interrupted manually on the handset It is not possible to call back the central office to end repetition of the alarms due to failure of CLIP transmission in the Setup message Bear this in mind when configuring the number of alarm repetitions Monitor...

Page 11: ...rd For information on how to proceed see the Operat ing Manual Operating Manual HiPath 3000 HiPath 4000 Gigaset S310 ISDN professional Personal Alarm Device Gigaset M2 plus professional Gigaset M2 Ex professional 6 1 PNG Menu Additional PNG menu items appear on the handset under the Add Features main menu when the PNG functionality is active 6 2 Emergency Key The emergency key operates as a progra...

Page 12: ...nitoring LED permanently lit Users can perform emergency alarm deactivation at the handset if they are unable to deacti vate an alarm during handset alerting because the handset was not properly configured forinstance Emergency alarm deactivation is reserved for PNG Service In other words emergency alarm deactivation is like other configuration changes protected by the PNG Service PIN Procedure 1 ...

Page 13: ...ugh out as PNA Service PNG configuration menus are protected from unauthorized unintentional changes by the PNG user by means of a five digit PIN code You are requested to enter the PNG service PIN when you try to activate a PNG menu The menu can only be accessed once the password has been entered correctly The PNG Service PIN is initially set to 00000 PNA Service must set this PIN to a confidenti...

Page 14: ...rm Configuration menu features the following submenus Menu item Description General Settings General alerting parameters Emergency For configuring the deliberate alarm alarm via the emergency key Non Movement For configuring automatic alarms referred to in the following as Autom alarms Man Down Alarm Time Alarm Escape Alarm Pull Cord Alarm Technical Warning For detecting and reporting device fault...

Page 15: ...and Section 7 2 1 3 PNEZ Basis Number Deleted Please note changing and saving Alarm Number Basis always affects all dependent config urations Dependent configurations are the following All alarm destinations of various alarm types PNEZ Basis and the control ports that are dependent on it Please note you must first define the Alarm Number Basis then make individual changes to the alarm destinations...

Page 16: ...ng the following formula PNEZ Basis Alarm Number Basis 10 Example enter the following as the Alarm Number Basis 52200 The PNEZ Basis is cal culated as 52210 and pre configured If you want to change the PNEZ Basis enter a new number maximum 32 digits The numbers of the PNEZ control port are derived from this PNEZ Basis as automatically pre configured numbers Please note changing and saving PNEZ Bas...

Page 17: ...automatically preset Recommendation for BGR 139 configuration Alarm destinations and control ports must be synchronised between PNEZ and the handset Use the handset s automatic configuration function whenever possible to reduce the time and effort required for configuration Alarm Number Basis 52200 input Emergency 52200 Non Movement 52200 Man Down Alarm 52200 Time Alarm 52200 Escape Alarm 52200 Pu...

Page 18: ...preset to Recommendation for BGR 139 configuration Alarm destinations and control ports must be synchronised between PNEZ and the handset Use the handset s automatic configuration function whenever possible to reduce the time and effort required for configuration Alarm Number Basis 52000 Emergency 52200 Non Movement 52200 Man Down Alarm 52200 Time Alarm 52200 Escape Alarm 52200 Pull Cord Alarm 522...

Page 19: ...rm calls PNG OFF is dis played on the right display key Monitoring is deactivated after resetting PNG activation in the Add Features PNG Activa tion menu The control ports are also deleted when you delete the PNEZ Basis Control calls for controlling the PNG S are only recognised if the CLIP information for the rele vant control port is transmitted in the Setup message The feature is supported in H...

Page 20: ...nises the alarm recall If an alarm recall is not recognised the PNG S repeats the alarm call a minimum of five times Then PNG OFF is dis played on the right display key You can initiate alarming signal deactivation by pressing PNG OFF With PNEZ Basis Number Requests for alarming signal deactivation in the PNEZ must be performed by the PNEZ With PNEZ Basis blank The alarming signal is deactivated i...

Page 21: ...ted alarm call and a pause The call and interval duration is s increased by one second after every alarm call Select a longer repeat alarm time for calls that break out into the public network The call du ration must be long enough to reach the alarm destination Make test calls if necessary You can communicate with the alarm destination throughout over the connection duration once the alarm signal...

Page 22: ...ime 90 s Alarm debounce time 1 s Prealarm time 15 s Transport Time 2 s Figure 7 2 Alarming signal time calculation The alarm debounce time is within the response time T0 Occurrence of monitored incident change in position forinstance T1 Occurrence of monitored incident T2 Start of prealarm T3 Alarm automatically triggered in the PNG TA Alarm signalling in the PNEZ Response time T1 Prealarm time Tr...

Page 23: ...tioning tone to be manually suppressed when the handset is in alarm mode The alarm positioning tone is suppressed for the du ration of the call once the key has been briefly pressed The alerting party can com municate with the alarm destination The alerting party can always communicate with the alarm destination if alerting is configured without an alarm tone Table 7 5 Parameter setting for Signal...

Page 24: ...r prohibits the suspension or reactivation of automatic alarms when the handset is in monitoring mode Autom alarms OFF No All activated automatic alarms non movement man down time and pull cord alarms forinstance remain active while the handset is in monitoring mode Autom alarms OFF Off in charger The activated automatic alarms are suspended when the handset is placed a charger Pre alarms and alar...

Page 25: ...ee Section 7 2 5 Control Ports This does not apply to the deliberate alarm or the technical fault warning The function requires the PNEZ control call The PNG LED displays the new monitoring mode Table 7 7 Parameter setting for Autom alarms OFF 7 This type of operation does not conform to BGR 139 Parameter Setting range Factory setting BGR 139 Autom alarms OFF No Off in charger By Control Call No N...

Page 26: ...ning signal is generated by pressing the handset s emergency key when an alarm is triggered The following parameters can be configured You can use the Alarm Signal Longpress setting to generate an alarm with or without an alarm signal depending on the situation Pressing the emergency key briefly generates an alarm with an alarm signal Pressing and holding down the emergency key generates a silent ...

Page 27: ... to configure the individual Alarm destination and Alarm destina tion lp alarm destinations up to 32 digits for the deliberate alarm Table 7 9 Alarm destination settings for deliberate alarms Parameter Setting range Factory setting BGR 139 Alarm destination 32 digit number Blank see Section 7 2 1 1 Alarm Num ber Basis Align with PNEZ Alarm destination lp 32 digit number Blank_LP see Sec tion 7 2 1...

Page 28: ...ch alarm type The alarm signal can be activated or deactivated for each alarm type You can select the sensitivity level of the escape alarm An individual alarm destination can be configured for each alarm type The parameters for each alarm type are as follows Activation Response time Prealarm time Alarm Signal Sensitivity level for escape alarm only Alarm destination Although the parameters are pr...

Page 29: ...s leaning at an incorrect angle for a defined and configurable pe riod of time in other words the handset is in a non upright position Table 7 11 Parameter setting for man down alarm Parameter Setting range Factory setting BGR 139 Activation On Off On At least one autom alarm Response time 10 s 900 s 90 s 90 s Prealarm time 0 s 30 s 15 s 5 s 15 s Alarm Signal On Off On On Alarm destination 32 digi...

Page 30: ...a defined and configurable period of time Table 7 13 Parameter setting for escape alarm Parameter Setting range Factory setting BGR 139 Activation On Off Off At least one autom alarm Response time 1 min 120 min 30 min 30 min Prealarm time 0 s 30 s 15 s 5 s 15 s Alarm Signal On Off On On Alarm destination 32 digit number Blank see Section 7 2 1 1 Alarm Num ber Basis Align with PNEZ Parameter Settin...

Page 31: ...onitoring timers are restarted You can configure the following parameters Activation technical fault monitoring can be activated or deactivated Locate req time checks whether the handset is receiving regular DPS requests The check is deactivated when Locate req time 0 Acoustic Out of range time checks whether the handset has contact with the base station The check is deactivated when Out of range ...

Page 32: ...acoustically signalled here The following signals start quietly and quickly rise in a crescendo to reach their configured max imum volume 7 2 4 1 Prealarm Configuration of acoustic prealarm signalling Table 7 16 Parameter setting for prealarm Acoustic On Off On On Out of range time 0 min 30 min 2 min 2 min Parameter Setting range Factory setting BGR 139 Acoustic On Off On On Alarm Signal All signa...

Page 33: ...rm and auto matic alarms Table 7 17 Parameter setting for the alarming signal 7 2 4 3 Technical Warning Configuration of acoustic warning signals for signalling local technical faults Table 7 18 Parameter setting for technical warning Parameter Setting range Factory setting BGR 139 Alarm Signal All signals 1 38 4 4 Alarm signal volume lev els 1 5 5 5 Parameter Setting range Factory setting BGR 139...

Page 34: ...nciple The PNG S calls specific PNEZ control ports in order to signal PNG states or PNG requests Conversely the PNEZ control ports call the PNG S in order to initiate certain PNG control func tions on the PNG S Figure 7 3 Communication between PNG S and PNEZ PNG S PNEZ control ports Request startup Start function test Function test OK Start monitoring Function test NOK Function test NOK callback R...

Page 35: ...quest The PNG S would like to be includ ed in the monitoring process This phone number is called when the user selects the following menu item for instance Add Fea tures PNG Activation Number_2 and Number_3 In accordance with BGR 139 the handset must perform a func tion test to check the alarm sensors prior to each startup proce dure This is initiated by the PNEZ see PNG control functions If this ...

Page 36: ...nd Number_6 Number_5 and number_6 can be used to request the PNEZ to suspend or reactivate the configured automatic alarms Number_7 to Number_9 Reserved for later use PNG control function Number Start function test Number_1 Start monitoring Number_2 Function test NOK Number_3 Reset Request Number_4 Autom alarms OFF Number_5 Autom alarms ON Number_6 Alarm Recall loud speakerphone mode on Number_7 A...

Page 37: ...e switched on The PNEZ can listen into the alarm situation and speak with the party signalling the alarm over the loudspeaker The call is disconnected from the PNEZ but can also be discon nected from the handset Number_8 PNG S accepts the alarm recall Microphone and receiver insert are switched on The PNEZ can listen into the alarm situation and speak with the party signalling the alarm over the r...

Page 38: ...he numbers can consist of up to 32 digits The numbers are automatically derived and con figured from the PNEZ Basis Number_n PNEZ Basis n If required to do so you can overwrite the control ports and assign other numbers to them The functions must be performed in pairs A shared number is configured in the handset for both functions Recommendation for BGR 139 configuration Automatic Configuration PN...

Page 39: ...0000 You are now in the PNG Configuration menu 4 Select Adjust Sensor and confirm with OK The following text appears on the screen 5 Hold the handset still and in a vertical position and confirm with OK The following text ap pears on the screen Once the adjustment is complete the following message appears on the handset The vertical adjustment is tested again during the functional test Sensors mus...

Page 40: ...main menu 2 Select PNG Configuration 3 Enter the requested PNG Service PIN and confirm with OK the default PIN is 00000 You are now in the PNG Configuration menu 4 Select PNG Service PIN and confirm with OK 5 Enter the new PNG Service PIN 6 Select Re enter PIN wiederholen down arrow key and repeat your entry 7 Confirm with OK 7 Memorise your new PIN If you forget the PIN it can only be reset by Un...

Page 41: ...wing table contains the factory defaults Parameter Active General Settings Alarm Number Basis Blank PNEZ Basis Blank Alarm Call Count 15 Repeat Alarm Time 4 s Autom alarms OFF No Signal Off manual On Signal Off autom On Transport Time 2 s Emergency Alarm Signal On Alarm destination Alarm Number Basis Alarm destination lp Alarm Number Basis Non Movement Activation On Response time 90 s Prealarm tim...

Page 42: ... Alarm Number Basis Escape Alarm Activation Off Response time 30 s Prealarm time 15 s Alarm Signal On Sensitivity level Medium Alarm destination Alarm Number Basis Pull Cord Alarm Activation On Response time 30 s Prealarm time 15 s Alarm Signal On Alarm destination Alarm Number Basis Technical Warning Activation On Locate req time 0 min Acoustic On Out of range time 2 min Alarm Signal Prealarm Aco...

Page 43: ...Ex professional Service Manual 43 PNG Configuration Factory Defaults Alarming signal Alarm Signal 04 Alarm signal volume Level 5 Technical Warning Alarm Signal 06 Alarm signal volume Level 3 Control Ports Blank All control port numbers are deleted Parameter Active Table 7 22 Factory defaults ...

Page 44: ...ion Activate the time alarm enable activation Set the response time for the time alarm 15 min The following are configured automatically based on the Alarm Number Basis PNEZ Basis Alarm destination 10 95010 Control Ports 95011 95019 The following table provides a complete overview of the settings This configuration conforms to BGR 139 Parameter Active General Settings Alarm Number Basis Input 9500...

Page 45: ... Automatic 95000 Man Down Alarm Activation Input Off Response time 90 s Prealarm time 15 s Alarm Signal On Alarm destination Automatic 95000 Time Alarm Activation Input On Response time Input 15 Prealarm time 15 s Alarm Signal On Alarm destination Automatic 95000 Escape Alarm Activation Off Response time 30 s Prealarm time 15 s Alarm Signal On Sensitivity level medium Alarm destination Automatic 9...

Page 46: ...larm Acoustic On Alarm Signal 08 Alarm signal volume Level 3 Alarming signal Alarm Signal 04 Alarm signal volume Level 5 Technical Warning Alarm Signal 06 Alarm signal volume Level 3 Control Ports Start function test Automatic 95011 Start monitoring Automatic 95012 Function test NOK Automatic 95013 Reset Request Automatic 95014 Autom alarms OFF Automatic 95015 Autom alarms ON Automatic 95016 Alarm...

Page 47: ...iguration for Gigaset M2 plus and M2 Ex professional Service Manual 47 Sample Configurations Operation in HiPath Cordless Enterprise with PNEZ Sample change To change the alarm number for the pull cord alarm enter 95005 forinstance under Alarm des tination ...

Page 48: ...he Alarm Number Basis in the example 95000 Delete the PNEZ Basis delete automatically generated number Deactivate the man down alarm disable activation Activate the time alarm enable activation Set the response time for the time alarm 15 min The following is configured automatically Control port deletion The following table provides a complete overview of the settings This configuration does not c...

Page 49: ...n Automatic 95000 Man Down Alarm Activation Input Off Response time 90 s Prealarm time 15 s Alarm Signal On Alarm destination Automatic 95000 Time Alarm Activation Input On Response time Input 15 Prealarm time 15 s Alarm Signal On Alarm destination Automatic 95000 Escape Alarm Activation Off Response time 30 s Prealarm time 15 s Alarm Signal On Sensitivity level medium Alarm destination Automatic ...

Page 50: ...alarm Acoustic On Alarm Signal 08 Alarm signal volume Level 3 Alarming signal Alarm Signal 04 Alarm signal volume Level 5 Technical Warning Alarm Signal 06 Alarm signal volume Level 3 Control Ports Start function test Automatic Clear Start monitoring Automatic Blank Function test NOK Automatic Blank Reset Request Automatic Blank Autom alarms OFF Automatic Blank Autom alarms ON Automatic Blank Alar...

Page 51: ... Example Alarm callback without PNEZ To be able to execute e g an alarm callback with silent monitoring the HiPath 3000 version must support the CLIP protocol in the setup message Configure e g the control port Alarm recall sp on with the number of the subscriber who should make the alarm callback in the event of an alarm 7 Before using this feature get the permission of the person being monitored...

Page 52: ...r the Alarm Number Basis in the example 95000 Delete the PNEZ Basis delete automatically generated number Deactivate the man down alarm disable activation Activate the time alarm enable activation Set the response time for the time alarm 15 min The following is configured automatically Control port deletion The following table provides a complete overview of the settings This configuration does no...

Page 53: ...atic 95000 Man Down Alarm Activation Input Off Response time 90 s Prealarm time 15 s Alarm Signal On Alarm destination Automatic 95000 Time Alarm Activation Input On Response time Input 15 Prealarm time 15 s Alarm Signal On Alarm destination Automatic 95000 Escape Alarm Activation Off Response time 30 s Prealarm time 15 s Alarm Signal On Sensitivity level medium Alarm destination Automatic 95000 P...

Page 54: ...oustic On Out of range time 2 min Alarm Signal Prealarm Acoustic On Alarm Signal 08 Alarm signal volume Level 3 Alarming signal Alarm Signal 04 Alarm signal volume Level 5 Technical Warning Alarm Signal 06 Alarm signal volume Level 3 Control Ports Start function test Automatic Blank Start monitoring Automatic Blank Function test NOK Automatic Blank Reset Request Automatic Blank Autom alarms OFF Au...

Page 55: ...r to suspend automatic alarms du ring charging Configure alarm via the emergency key Check Transport Time 2 s Configure automatic alarms Note At least one alarm must be switched on to guarantee configurati on compliant with BGR 139 Non Movement on off Man Down Alarm on off Time Alarm on off Escape Alarm on off Pull Cord Alarm on off Configure alarm parameters for each active alarm Response time Pr...

Page 56: ... Alarm signal volume OK Check the alarming signal Alarm destination selected OK Repeat Alarm Time OK Number of repeat alarms OK Activate monitoring Check automatic alarms all activated alarms Check the prealarm Signal Melody Alarm signal volume OK silent alert OK Check the non movement alarm do not move PNG S Prealarm time OK Response time OK Signal on off OK Alarm destination OK Check the man dow...

Page 57: ...gnal on off OK Alarm destination OK Check the escape alarm move device erratically simulate running Prealarm time OK Response time OK Signal on off OK Sensitivity level OK Alarm destination OK Check the pull cord alarm remove contact Prealarm time OK Response time OK Signal on off OK Alarm destination OK Check the technical warning Locate req time OK Acoustic OK Out of range time OK Setting Done y...

Page 58: ... times listed in this table are compulsory Alarm type Response time PNA PNA S Deliberate personal alarm for voice traffic otherwise Prealarm Automatic personal alarm including prealarm Man Down Alarm Non Movement Time Alarm Automatic personal alarm Pull Cord Alarm Escape Alarm Note Prealarm is not mandatory Table 9 2 Response times according to VDE 0825 2 s 30 s 2 s 15 s 15 s 90 s 90 s 90 s 90 s 3...

Page 59: ...ng Line Identification Presentation CMI Cordless Multicell Integration DECT Digital Enhanced Cordless Telecommunications DPS DECT Positioning System HNA HiPath alarm signal system NOK Not OK PNA Personal alarm signal system PNA Service Service personnel responsible for the personal alarm signal system PNEZ Emergency call receiving centre PNG Personal alarm signal device PNG S Personal alarm signal...

Page 60: ...4 Conventions 5 D Data protection and data security 5 Debounce time 22 E Emergency 4 26 alarm destination 27 Alarm Signal 26 Escape Alarm 4 30 F Factory defaults 41 G General Settings 15 Repeat Alarm Time 21 Gigaset base 10 H HiPath alarm signal system 8 HiPath Cordless Office 9 HNA 8 M Man Down Alarm 4 29 N Non Movement 4 29 Number_n 34 P PNEZ 8 PNEZ Basis 16 19 PNEZ control functions 34 PNEZ con...

Page 61: ...lect Base 7 Sensor adjustment 39 Signal Off autom 24 Signal Off manual 23 Signal types 4 Symbols in the manual 5 T Technical warning 4 31 33 Time alarm 4 30 Time until prealarm 22 Transport Time 22 Typographical conventions in the manual 5 ...

Reviews: