RECEIVING AND STORING THE UNIT
Every unit leaves the factory in perfect condition. Therefore please check the unit very carefully on delivery
and notify the transport company immediately and in writing of any damage.
Check that the load capacity of the floor is sufficient to support the weight of the unit.
The unit must be located on a solid and flat surface. After positioning, with the help of a spirit level use the
optional adjustable feet (and spacers if necessary) to level the unit:
any gradient must be no more than
0.5°.
IMPORTANT: the unit must never be tilted or turned upside down.
The characteristics of the fans
do not allow the ducting of condensation
air.
Minimum distances around the unit
.
3000
mm
1000
mm
1500
mm
1500
mm
Accesso a:
- Motoventilatori;
- Serbatoio di accumulo (opzionale);
- Gruppo pompe opzionale (con
flussostato e vaso di espansione);
- Pompa di free cooling (opzionale).
- Aspirazione dell’aria;
- Estrazione filtri aria esterni (opzionali);
Accesso a:
- Ingresso / Uscita acqua refrigerata (acqua calda nel
funzionamento in pompa di calore);
- Ingresso / Uscita recupero di calore (opzionale);
- Ingresso cavo di alimentazione, collegamenti elettrici.
Accesso a:
- Terminale utente (opzionale);
- Manometri (opzionali);
- Quadro elettrico;
- Vano compressori (con filtro deidratore,
rubinetti e spia di liquido).
- Pressostati di alta e bassa pressione.
- Aspirazione dell’aria;
- Estrazione filtri aria esterni
(opzionali).
1500
mm
Access to:
•
Fans
•
Reservoir tank (optional)
•
Optional pump group (with flow
gauge and expansion tank)
•
Optional free cooling pump
- Air intake
-
External air extraction filters (optional);
Access to:
•
Chilled water intake/output (and hot water in heat
pumps)
•
Heat recovery intake/output (optional)
•
Power supply cable and electrical connections
Access to:
•
Air intake
•
Removing external air filters
(optional)
Access to
•
User Terminal (optional)
•
Manometers (optional)
•
Electrical panel
•
Compressor housing (with filter drier,
valves and sight glass)
•
HP and LP pressostats
•
Flow gauge
Summary of Contents for Aquaflair 00182