ACCESS TO MAIN COMPONENTS
COMPRESSOR HOUSING
To access the compressor housing, remove the 8 fixing screws 1 and lift panel A using the two front
handles B . Removing panel A gives access to the compressor housing, the microprocessor control user
terminal and to the optional high and low pressure manometers..
A
C
1
3
4
B
2
5
IG
DANGER – HOT SURFACES! RISK OF BURNING.
When panel
A
has been removed the compressor and
refrigerant tubes are exposed – during normal unit operation these components are very hot and can cause
burns.
IMPORTANT:
Removing panel
A
does not stop the unit and the power supply to the compressors is not
interrupted. For service and maintenance, the main switch IG must be turned off (position ‘O’).
ELECTRICAL PANEL
To access the electrical panel move the main switch IG to position “O” and turn the two screws 4 1/4 turn.
This enables panel C , hinged at the base of the electrical panel to be opened.