Installation
Improper installation of this equipment may result in equipment being damaged or personal injury
due to electric shock. This unit must be installed according to all applicable electrical codes and
standards. This includes but is not limited to proper bonding, seals for hazardous areas and proper
wiring methods and types.
The control circuit utilizes high energy capacitors. If the unit is shut off during the ignition cycle but
before the spark has been discharged, the charge is stored in the capacitor. A bleed circuit is
provided which bleeds the charge to render the unit safe. It is recommended to leave the unit in the
explosion proof enclosure (if fitted) for up to 4 minutes after power down to minimize risk of electric
shock.
Note: the eHenergizer contains no serviceable parts.
The correct voltage must be supplied to the exciter for it to function correctly. There are two models,
24 Vdc and 120Vac. Check to see you have the correct model for the voltage supplied to it. Do not put
the wrong voltage on the exciter otherwise the circuit will fail.
This is NOT a single wire ignition system. There must be a return wire or unimpeded ground connection
between the igniter tip and terminal G on the high voltage side of the unit. Follow all local codes for
proper bonding of the exciter.