ENGLISH
TOUCH CONTROL
INSTALLATION AND SERVICING MANUAL
Ufly P
Page 1: ...E N G L I S H TOUCH CONTROL INSTALLATION AND SERVICING MANUAL Ufly P ...
Page 2: ...itivi elettrici automatici di comando per uso domestico e Applied Standards similare Parte 1 Norme generali Automatic electrical controls for household and similar use Part 1 General requirements 2014 C 207 2 punto 6 Comunicazione Commissione UE sulla classificazione dei dispositivi di controllo temperatura EU Commission communication on temperature controls classification In merito alle classi di...
Page 3: ...s 18 2 6 2 rogramming and possible adjusting at preset programs 20 2 7 Solar Menù 22 2 8 Devices Menù 23 2 9 Burner Menù 25 2 10 Error code 28 Info 31 Screen calibration 32 Wiring conenction 33 Analytical index Burner Generator 25 CH default 12 CH Heating hot keys 10 Comfort 7 10 11 Compensation 7 Correction 7 Day 1 2 3 13 DHW domestic hot water 18 Eco 7 10 11 External compensation chart 16 Gatewa...
Page 4: ...e present but not in operation at that time Buttons and symbol outline in ligh grey no filled area Service not installed Note The Menu page icons do not indicate the operating status 2 1 2 3 4 1 18 28 thur y 30 ma 2015 Real Request 76 C 84 C Burner 8 8 M tion odula 100 INFO MENU Status DHW 25 C 4 3 5 6 7 8 9 10 11 1 2 3 4 5 KEY 1 Terminal connection for Ufly P coming from boiler board 2 Display To...
Page 5: ...ption 6 Display Mode Stand by 7 Display Mode Home page 8 Display Mode Menù page 2 1 Display mode 2 2 Button One page back and Button Home 2 3 Display in Home page 9 One page back 10 Return always to Home page 11 INFO see at pag 30 12 Boiler Domestic 0 1 1 Professional 0 2 8 in operation for ex 2 boiler activate of 8 avaible see at pag 25 ...
Page 6: ...6 2 4 Set up Menù First start Setting Time and Date ...
Page 7: ...ditable see page 12 DEFAULT VALUE comfort 20 C eco 5 C DEFAULT VALUE comfort 50 C eco 25 C Setting temperature Eco and Comfort for continuous programs in DHW circuit H24 Legionella protection to be activated only in the pre sence of water accumulations boilers with kettle or external tanks pag 19 20 Correction Change the setting value if room sensor measures a different value than expected Compens...
Page 8: ... metric and imperial In Homepage the screen turn off after the set time Default 20 sec while the screen is on in other page if the switch is active No stand by in case of fault message screen also in Home page doesn t turn off Note Do not change the value configured for Modbus boiler Brightness and Stand by setting Language and Unit setting ...
Page 9: ... current password with Enter new password and confirm To restore default values set at the factory Password Software information and restore default UflyBox settings Note for security and protection default password is only avaible to the Authorized Service Center ...
Page 10: ...10 2 5 CH Heating Menù 2 5 1 Hot keys Change heating temperature Choose CH program Change confort eco temperature with keys as indicated ...
Page 11: ... 07 30 Temp XX Ignition from 17 00 to 20 30 at the temp YY Ignition from 20 30 to 22 30 at the temp XY select WEEK1 WEEK2 WEEK3 For a manual request and extend stop heating period for a few hours at certain temperature touch icon shown HAND Set end of heating and change temperature Default time set 1 hour forward from effective hour Switch OFF CH Heating SUMMER select STANDBY DEFAULT value are the...
Page 12: ...king day Weekday Holiday 2 5 2 Programming and possible adjusting at preset programs Creation modification of typical days Selezione Circuito Ch Is possible change Name of heating circuit in the system Delete Ch current circuit Rename Zone circuit and confirm ...
Page 13: ...Type 1 Eventually rename Week 1 Week 3 example Autumn Winter Jolly Insert day of the week separately mon tue wed thu fri sat sun the day type Day1 Day5 Set Week Type 2 Insert day of the week join the day mon fri sat sun the day type Day1 Day5 ...
Page 14: ...ection Comfort Eco Week1 Week2 Week3 Keys room Current temperatur request real Water temperatur of circulation in radiators request Flow temperature compensation modulation Modulation level of the boiler in the moment Showing temperature in CH Heating ...
Page 15: ...e details of the program in the 1 2 3 period Example Heating at times Period 1 From 06 00 at 07 30 at 21 temperature Period 2 From 16 30 at 20 30 at 19 temperature Period 3 From 20 30 at 22 30 at 21 temperature View detail CH heating program 1 ...
Page 16: ...r of generator even if you try to overcome it is prevented Adjust parameters heating program By touching Settings icon is possible to adjust the para meters For those highlighted in gray password is required For other parameters dotted no need password Outer temperature External Compensation Chart T max 70 C T outer da 5 C 20 C T min 30 C Flow temperature The three lines at 19 C 20 C 21 C represen...
Page 17: ...and HEATING parameter If the boiler is in Error Block Reset as shown For other faults that can not be reset with the Reset button contact the service center At Home page Enabling Function Manual Back to the set program Ch Heating Manual request View detail CH heating program 2 Reset ...
Page 18: ...vate DHW hot water production STANDBY No hot water production select stand by for Boiler R only Heating Choosing DHW hot water program Standby inactive Comfort Eco Week 1 For boilers with water tank inside or external stock of water Week 2 Week 2 Key real Temperature at the moment of DHW draw off hot water request Water temperature request modulation Modulation level boiler Temperature displaying ...
Page 19: ...ossible to set the hot water preparation stored in the tank in daily time slots and Weekly DHW water stored in the tank previously set From 06 00 to 08 30 at 43 temperature From 17 00 to 22 00 at 43 temperature In these boilers it is essential to activate Legionella protection function To settings DHW circuit of Days slot p 12 Periods page 13 Weeks p 13 Operation in Manual mode p 15 Refer to the s...
Page 20: ...ayed are relative to the DHW hot water circuit Note Then to adjust DHW parameters is not neces sary to drive on DEVICES menu Adjust parameter DHW mode By touching Settings icon is possible to adjust the para meters For those highlighted in gray password is required For other parameters dotted no need password View detail DHW hot water program 1 Adjust parameter DHW mode By touching Icon shown It s...
Page 21: ...21 In Home page View detail DHW hot water program 2 Reset Is possibile to view and modify program and DHW parameter If the boiler is in Error Block Reset as shown ...
Page 22: ...22 If this this service is active 2 7 Solar Menù Is possible to force manually with password the pump run Is possible to activate this service and where the conditions the pump will start ...
Page 23: ...Controller Multifunction module bmm Burner Modul Manager They are displayed on the next screen and is prompted to save the new configuration Icon scanning devices Icon save new configuration Detected Device Not installed device Device previously detected but not detected at the moment 2 8 Devices Menù WARNING Function reserved exclusively to authorized service centers ...
Page 24: ...24 BMM HCM Parameter List of parameter in par 4 2 instruction manual of the boiler To change the parameters is required password Hystorical Error Delete history with Button Clear password ...
Page 25: ...ry mod request from 10 to 100 2 Activation 3 Chose burner among those available eg usually 1 modulex from 1 to 8 2 9 Burner Menù Sweeper function Note once selected the burner 3 the display page changes Burner 1 8 Note the selected burner is running at maximum power modulation 100 Pressing button go back one page burner menu ...
Page 26: ...ry of modulation request to the minimum 10 and select the burner 8 Disable SWEEPER function Exit by pressing Home icon This displayed parameter are relevant to burner Note To change burner parameters is not neces sary to go in the DEVICES menu The psw remains active until you return to the MENU Change parameter ...
Page 27: ...r the counters Password is required Manual Activation of Boiler Touching inicated Icon you manually activate the boiler without possibility to set the time Manual Activation of Boiler Reset counter ignitions work hours ...
Page 28: ..._6 Overheating Check pump operation and if needed clean the heat exchanger ALARM_7 Aux temperature sensor ALARM_8 Low water pression ALARM_9 Outer temperature sensor ALARM_10 Internal failure ALARM_11 Unexpected flame ALARM_12 CH flow sensor Check the efficiency of the sensor see table Res Temp or its connections ALARM_13 DHW Temperature sensor ALARM_14 CH return sensor Check the wiring if needed ...
Page 29: ...tage is 190Vac the line voltage is really below the minimum limit otherwise there is a monitor line error replace BMM ALARM_33 Mix 1 frozen ALARM_34 Mixer 2 frozen ALARM_35 Mixer 3 frozen ALARM_37 Parameters memory Contact Customer Care ALARM_38 Factory parameters Contact Customer Care ALARM_39 User parameters Contact Customer Care ALARM_40 Low water flowrate ALARM_41 Mixed air water ALARM_42 Pump...
Page 30: ...1 sensor ALARM_81 Sun Panel 2 sensor ALARM_82 Sun Pan 1 overheat ALARM_83 Sun Pan 2 overheat ALARM_84 Sun Pan 1 frost ALARM_85 Sun Pan 2 frost ALARM_86 SunTank top sensor ALARM_87 SunTank bottom sensor ALARM_88 SunTank inlet sensor ALARM_89 SunTank overheating ALARM_90 CC internal communication ALARM_91 Exhaust temperature sensor ALARM_92 Low battery ALARM_93 Security block ALARM_94 Gas valve wiri...
Page 31: ...d in the HOME page eg changed from a value PRESSURE to RETURN temp Info Note FILL icon appears only if the boiler is equipped with automatic water loading see installation boiler instructions In this case if thesystem does not reach 1 2 bar pressure within 60 seconds turn icon FILL ...
Page 32: ...ve your finger and use a nib C Wait display activation D Operation Display log every time you see the X on the display touch with a pencil the center of the X 1 to 5 and press OK After these operations the display is calibrated B Screen Calibration To be made in event of difficulties in use of buttons ...
Page 33: ...rdinates the SHC requests and manage the heat request from a single burner or a cascade system the HCM device can also offers a function similar to the SHC Modbus remote interface Y2 Through the Modbus interface is possible the access to all the Ufly P functions Acquisition of operating information of all connected devices Setting parameters and the thermoregulation control programs of HSCP Diagno...
Page 34: ... ExtTemp is considered equal to 0 C The OTC algorithm does not directly use the read tem perature but its average value in the last 2 hours cal culated on the acquisition of a value every 15 minutes Temperature sensors Room Sensor the room tem perature can be acquired by Room Sensor and used for heating correction and for room thermostat function The OTC algorithm does not directly use the read te...
Page 35: ...35 ...
Page 36: ...ical eu AG S p A www unical eu 00338145EN 1 st ed 02 19 Unical declines every responsibility for the possible inaccuracies if owed to errors of transcript or press Also reserves the right to bring those changes that it will hold necessary to it own products or profits without jeopardizing its essential characteristics ...