Touch Screen
28
Figure 27. Chronothermostat, "Legionella disinfection" page
The set timeline appears red-colored.
The pink line shows the eventual setting of the previous day that overruns in current day because the duration exceeds the
midnight.
It is necessary to enable the electric heaters in sanitary integration, by setting the parameter
R15 = 1
.
OPERATION:
•
When anti-legionella cycle is expected, the heat pump unit changes automatically into sanitary mode in order to reach the
setting values of the parameter
R27
(50°C.)
•
When the DHW temperature sensor meets the value of
R27
, the compressor will stop operation and the DHW electric heater
(DO = 26) will start after
R16
(1min).
•
The DHW electric heater turns off if one of the following conditions is fulfiled:
o
The DHW temperature sensor detects a temperature =
R25
(80°C), hysteresis 'cut-on' of 1°C.
o
The finishing of the programmed cycle.
4.7.5
AMBIENT THERMOSTAT
The “Touch Screen” control panel can operate as a typical ambient thermostat.
The ambient thermostat function, for each zone will be enabled/disabled, using the corresponding button at the bottom of the
screen of the zone status setting.
Figure 28. Status of Zone Staus settings
The thermostat activation key has two states depending on if the function is enabled or disabled.
Figure 29. Activation icon
When the icon shows the voice "
thermostat off
" (default) this means that the thermoregulation of the reference zone is performed
with the remote air temperature sensor of the fancoil unit.
To activate the ambient thermostat function in the zone:
1)
Press the activation icon, displaying "
Thermostat on
".
2)
Select the mode in which the thermoregulation shall be carried out of the refrence zone, by setting the parameters from
P46
to
P54
for the winter and from
P55
to
P63
for the summer. See Chapter 7.
The call of the ambient thermostat shall be active when the setpoint of the zone is not fulfilled, the heat pump is enabled for
operation.