Unical KONm R 18 Installation And Servicing Manual Download Page 1

IT

ALIANO

ENGLISH

R 18 - C 18 - R 24 - C 24
R 28 - C 28 - R 35 - C 35

ISTRUZIONI PER L’INSTALLATORE E IL MANUTENTORE
INSTALLATION AND SERVICING MANUAL

KON

m

Summary of Contents for KONm R 18

Page 1: ...I TA L I A N O E N G L I S H R 18 C 18 R 24 C 24 R 28 C 28 R 35 C 35 ISTRUZIONI PER L INSTALLATORE E IL MANUTENTORE INSTALLATION AND SERVICING MANUAL KONm...

Page 2: ...2 http www unicalag it prodotti domestico 50 condensazione gas 774 kon...

Page 3: ...e manutenzione 29 4 2 Parametri modificabili da pannello comandi 31 4 3 Adattamento all utilizzo di altri gas 32 4 5 Schema elettrico 33 4 6 Codici di errore 34 3 ISTRUZIONI PER L INSTALLATORE 15 3 1...

Page 4: ...ll uso per il quale stato espressamente previsto Ogni altro uso da considerarsi improprio e quindi pericoloso 1 1 avvertenze generali Il libretto d istruzioni costituisce parte integrante ed essenzial...

Page 5: ...zioni nonch gli altri documenti relativi all apparecchio inseriti nella busta contenuta nell imballo L utente deve custodire tale documentazione in modo da poterla avere a disposizione per ogni ulteri...

Page 6: ...perativa dell apparecchio ATTENZIONE Per stringere o allentare i raccordi a vite utilizzare esclusivamente delle chiavi a forcella chiavi fisse adeguate L utilizzo non conforme e o gli attrezzi non ad...

Page 7: ...otenza utile in condensazione 11 Qn Portata termica massima 12 Adjusted Qn Regolata per portata termica nominale 13 PMS Pressione max esercizio riscaldamento 14 T max Temperatura max riscaldamento B C...

Page 8: ...tamento delle acque di alimen tazione consente di prevenire gli inconvenienti e mantenere funzio nalit ed efficienza del generatore nel tempo Il valore di pH ideale dell acqua negli impianti di riscal...

Page 9: ...HE TECNICHE E DIMENSIONI 2 1 CARATTERISTICHE TECNICHE 2 2 VISTA CON L INDICAZIONE DEI COMPONENTI PRINCIPALI E DIMENSIONI KON R 18 R 24 KON C 18 C 24 Vista dall alto Vista da sotto KON C 18 C 24 NOTA P...

Page 10: ...10 KON R 28 R 35 KON C 28 C 35 Vista dall alto KON C 28 C 35 Vista da sotto...

Page 11: ...ubinetto di scarico caldaia 15 Rubinetto di carico 16 Valvola deviatrice 17 Scambiatore a piastre 18 FL FH VM Ventilatore 19 AF AS PV Pressostato fumi 20 Valvola di sicurezza 21 By pass automatico 22...

Page 12: ...12 2 3 DIAGRAMMA PORTATA PRESSIONE DISPONIBILE PER L INSTALLAZIONE CIRCOLATORE MODULANTE DIAGRAMMA PORTATA PRESSIONE DISPONIBILE PER L INSTALLAZIONE KON C R28 35 7m KON C R24 6m...

Page 13: ...i rilevati con apperecchio funzionante a Metano G20 2 4 1 DATI SECONDO DIRETTIVA ErP Elemento Simbolo Unit KONm R18 C18 R24 C24 R28 C28 R35 C35 Potenza utile nominale Pnominale kW 17 23 27 32 Efficien...

Page 14: ...to sanitario bar 0 5 0 5 0 5 0 5 Pressione massima del circuito sanitario bar 6 6 6 6 Portata specifica acqua sanitaria t 30 C D l min 11 2 11 2 13 16 Limitatore di portata sanitaria l min 10 10 12 15...

Page 15: ...ldaia e camino canna fumaria Attenzione Se nel locale di installazione sono presenti polveri e o vapori aggressivi corrosivi l apparecchio deve essere adeguatamente protetto e deve poter funzionare in...

Page 16: ...declina ogni re sponsabilit nel caso di danni procurati a persone animali o cose subentranti in seguito a mancata osservanza di quanto sopra esposto H P L A B D C Nell imballo oltre all apparecchio s...

Page 17: ...e non deve essere costituita da materiale infiammabile KON R C 18 R C 24 R C 28 R C 35 Poich la temperatura della parete su cui installata la caldaia e le temperatura del condotto di scarico coassiale...

Page 18: ...SIALE 60 100 SDOPPIATO 80 DA m FINO A m DA m FINO A m 1 7 0 5 0 5 40 20A 20S COASSIALE 80 125 SDOPPIATO 60 DA m FINO A m DA m FINO A m 1 9 1 1 20 10A 10S Terminali verticali di scarico e aspirazione d...

Page 19: ...er il prelievo dell a ria comburente e scarico fumi mediante camino individuale o collettivo C93x C93 Collegamento aria fumi mediante condotti coas siali nel locale caldaia e monoparete nella canna fu...

Page 20: ...llazione e nell uso e comunque per inosservanza delle istruzioni date dal costruttore stesso Adattatore per sistemi sdoppiati Attenzione Per tutte le configurazioni di scarico montare il distanziale c...

Page 21: ...FREDDA 1 2 Sc SCARICO CALDAIA S cond SCARICO CONDENSA Rc RUBINETTO DI CARICO Svs SCARICO VALVOLA SICUREZZA Prevedere un tubo di scolo con imbuto ed un sifone che conducano ad uno sca rico adeguato in...

Page 22: ...cuito Tale operazione deve essere effettuata con cautela rispettando le seguenti fasi aprire le valvole di sfogo dei radiatori ed accertarsi del funzionamento della valvola automatica in caldaia aprir...

Page 23: ...nte RT OT Si ricorda che necessario installare sulla linea di alimentazione elettrica della caldaia un interruttore bipolare con distanza tra i contatti maggiore di 3 mm di facile accesso in modo tale...

Page 24: ...o d acqua come indicato al capitolo 3 7 eventuali saracinesche di intercettazione impianto sono aperte il gas da utilizzare corrisponde a quello di taratura della caldaia in caso contrario provvedere...

Page 25: ...orizzati 3 11 1 ATTIVAZIONE DELLA funzione di taratura 3 11 2 Posizionamento delle sonde 1 ATTIVAZIONE Premendo il pulsante D per 3 secondi si attiva la funzione taratura Rilasciare quando compare sim...

Page 26: ...azione e scarico verificare che non vi siano perdite di gas 3 12 REGOLAZIONE DEL BRUCIATORE 2 Regolazione alla potenza minima Azionare la caldaia in modalit taratura alla MI NIMA POTENZA vedi 3 11 1 U...

Page 27: ...5 6 28 37 1500 5900 9 8 8 10 5 10 5 0 43 kg h 2 17 kg h 60 KONm R 18 KONm C 18 Tipo di Gas Potenza Utile kW Portata Termica kW risc Press Aliment mbar Velocit ventilatore rpm Diaframma collettore n f...

Page 28: ...centuale del bruciatore 3 12 1 ADATTAMENTO DELLA POTENZA ALL IMPIANTO DI RISCALDAMENTO Es KONm 24 per depotenziare la caldaia a 18 kW modificare il parametro HP circa 70 Agire sul parametro HP par 4 2...

Page 29: ...scaldamento nonch la valvola di entrata dell acqua fredda se chiuse in precedenza Sfiatare e se necessario procedere al ripristino della pressione dell impianto di riscaldamento fino a raggiungere una...

Page 30: ...ta chiudere i rubinetti di intercettazione del circuito di riscaldamento apri re il rubinetto di scarico per far scendere la pressione d acqua Prima di rimettere in pressione verificare la pressione d...

Page 31: ...TANDARD 0 TA 0 5 TA 5 30 TA 30 0 TA 0 POTENZA MASSIMA DI RISCALDAMENTO VALORI DA A STANDARD 0 Min 99 Max 99 PRERISCALDO VALORI DA A STANDARD 0 1 0 TEMPERATURA DELLA SONDA ESTERNA VALORI DA A STANDARD...

Page 32: ...to disaerato Per una disaerazione a regola d arte del serbatoio rivolgersi al fornitore dei gas liquido e comunque a personale abilitato ai sensi di legge Se il serbatoio non stato disaerato a regola...

Page 33: ...accensione rilevazione FLS Flussostato richiesta sanitario MVD Motore valvola deviatrice P Circolatore SR Sensore riscaldamento mandata SRR Sensore riscaldamento ritorno SS Sonda sanitario Pred per mo...

Page 34: ...erna 14 1 SONDA DI RITORNO Sensore SRR ausiliario in terrotto Verificare il cablaggio even tualmente sostituire il sensore ausiliario 22 30 2 PARAMETRI DI SERVIZIO Parametri di servizio alterati a cau...

Page 35: ...a acqua 16 10 CONGELAMENTO SCAMBIATORE 24 Viene rilevato il congelamento dello scambiatore Se il sen sore riscaldamento rileva una temperatura inferiore a 2 C viene inibita l accensione del bruciatore...

Page 36: ...da INCONVENIENTI RIMEDI KONm 18 24 28 35 Fiamma rumorosa in accensione a freddo Agire su parametro IG mediante ausilio di REGOLAFACILE sezione MENU TECNICO parametri TSP aumentando il valore del 5 10...

Page 37: ......

Page 38: ...2 http www unicalag it prodotti domestico 50 condensazione gas 774 kon...

Page 39: ...4 1 Inspection and maintenance instructions 29 4 2 Parameters that can be edited from the control panel 31 4 3 Adaptation to the use of other gas 32 4 5 Wiring diagram 33 4 6 Error codes 34 3 INSTALL...

Page 40: ...t was expressly designed Any other use is to be considered improper and therefore dangerous 1 1 general warnings The instruction booklet is an integral and essential part of the product and must be ke...

Page 41: ...the appliance inserted in the envelope inside the packaging The user must keep this documentation safe for future consultation Inform the user about the importance of the air vents and the flue gas ex...

Page 42: ...h affect the operating safety of the appliance Attention To tighten or loosen the screwed fittings use only appropriate fixed spanners Incompliant use and or inappropriate tools can cause damage e g w...

Page 43: ...ut 10 Pcond Effective output in condensation 11 Qn Maximum heat output 12 Adjusted Qn Adjusted for rated heat output 13 PMS Max heating operating pressure 14 T max Max heating temperature B Domestic h...

Page 44: ...F Sensor 11 par 2 2 1 7 WATER TREATMENT The treatment of the supply water allows to prevent inconveniences and maintain the functionality and efficiency of the generator over time The ideal water pH i...

Page 45: ...AND DIMENSIONS 2 1 TECHNICAL FEATURES 2 2 VIEW WITH THE INDICATION OF THE MAIN COMPONENTS AND DIMENSIONS KON R 18 R 24 KON C 18 C 24 View from above View from below KON C 18 C 24 NOTE For further deta...

Page 46: ...10 KON R 28 R 35 KON C 28 C 35 View from above KON C 28 C 35 View from below...

Page 47: ...iciency pressure switch 14 Boiler drain valve 15 Filling valve 16 Diverter valve 17 Plate heat exchanger 18 FL FH VM Fan 19 AF AS PV Flue gas pressure switch 20 Safety valve 21 Automatic by pass 22 rb...

Page 48: ...SURE AVAILABLE FOR INSTALLATION Flow rate l h Flow rate l h Avaible Head m c a metres of water Avaible Head m c a metres of water MODULATING PUMP DIAGRAM OF FLOW RATE PRESSURE AVAILABLE FOR INSTALLATI...

Page 49: ...in max Pa 2 70 2 70 2 70 2 70 Notes Room Temperature 20 C Data obtained with appliance operated with Nat Gas G20 2 4 1 DATA ACCORDING TO ErP DIRECTIVE Description Symbol Unit KONm R18 C18 R24 C24 R28...

Page 50: ...pressure bar 6 6 6 6 Domestic hot water specific flow rate t 30 C D l min 11 2 11 2 13 16 Domestic hot water flow rate limiter l min 10 10 12 15 Production of D H W in continuous operation with t 45 K...

Page 51: ...s dust and or if there are aggressive corrosive vapours present in the installation room the appliance must be protected suitably and must be able to operate independently from the air in the room Att...

Page 52: ...ble for damage to persons animals or ob jects due to failure to comply with the instruction above H P L A B D C As well as the appliance the packaging contains A DOCUMENTATION ENVELOPE System booklet...

Page 53: ...all must not be made of flammable material KON R C 18 R C 24 R C 28 R C 35 Since the temperature of the wall on which the boil er is installed and the temperature of the coaxial exhaust pipe do not ex...

Page 54: ...Horizontal exhaust and intake terminals directed outside via coaxial or double pipes C33x C33 TOTAL LENGTH LA intake L Exhaust COAXIAL 60 100 DOUBLE 80 FROM m TO m FROM m TO m 1 7 0 5 0 5 40 20A 20S C...

Page 55: ...UNICAL CAUTION LT total length is a reference value for the dimensioning of the ducts of A intake and S Exhaust Subtracting the values of LT reported at values of bends terminals extensions you get t...

Page 56: ...ation and use and in any case failure to comply with the instructions provided by the manufacturer Adapter for double systems Attention For all drain configurations mount the chimney spacer supplied w...

Page 57: ...ILER DRAIN S cond CONDENSATION DRAIN Rc FILLING VALVE Svs SAFETY VALVE DRAIN Provide a drain pipe with funnel and a trap that lead to a suitable drain in cor respondence of Svs This drainage must be c...

Page 58: ...filled This operation must be performed carefully respect ing the following phases open the radiator vent valves and make sure the automatic valve is working properly in the boiler open the filling t...

Page 59: ...terminals TA1 OT after having removed the jumper ON OFF room thermostat connection RT OT Remember that a bipolar switch must be installed on the boiler power line with over 3 mm between contacts easy...

Page 60: ...densation drain trap been filled with water as indicated in chapter 3 7 are any system shut off gate valves open does the gas to be used correspond to the boiler calibration gas otherwise perform the...

Page 61: ...ly 3 11 1 ACTIVATION OF THE calibration function 3 11 2 Positioning the probes 1 ACTIVATION By pressing the button D for 3 seconds the calibration function is activated Release it when the SERVICE sym...

Page 62: ...nal check that there are no gas leaks 3 12 ADJUSTING THE BURNER 2 Minimum output adjustment Operate the boiler in calibration mode at MINI MUM OUTPUT see 3 11 1 Once the burner is on check that the CO...

Page 63: ...27 2 5 6 28 37 1500 5900 9 8 8 10 5 10 5 0 43 kg h 2 17 kg h 60 KON R 18 KON C 18 Type of Gas Effective Output kW Heating Thermal kW Capacity Supply Press mbar Fan speed rpm Collector diaphragm n hole...

Page 64: ...urner output value 3 12 1 ADAPTATION OF THE POWER TO THE HEATING SYSTEM E g KON 24 to decrease the output of the boiler to 18 kW edit parameter HP about 70 Act on parameter HP par 4 2 parameters that...

Page 65: ...nlet valve if closed previously Vent and if necessary restore the heating pres sure until reaching a pressure of 0 8 1 0 bar Open the gas shut off valve Switch the boiler on Make sure the appliance is...

Page 66: ...he water pressure is below 0 4 bar Without request close the shut off valves of the heating circuit open the drain valve to make the water pressure decrease Before pressurising again check the pressur...

Page 67: ...LT 0 TA 0 5 TA 5 30 TA 30 0 TA 0 MAXIMUM HEATING OUTPUT VALUES FROM TO DEFAULT 0 Min 99 Max 99 PREHEATING VALUES FROM TO DEFAULT 0 1 0 EXTERNAL PROBE TEMPERATURE VALUES FROM TO DEFAULT 0 20 C 30 10 C...

Page 68: ...appli ance For state of the art deaeration of the tank contact the LPG supplier or a person qualified in compliance with law If the tank has not been professionally deaerated ignition problems could...

Page 69: ...gnition detection electrode FLS Domestic hot water request flow switch MVD Diverter valve motor P Pump SR Flow heating sensor SRR Return heating sensor SS Domestic hot water probe Pred for R models TL...

Page 70: ...lace the external probe 14 1 RETURN PROBE Auxiliary SRR sensor inter rupted Check the wiring if needed re place the auxiliary sensor 22 30 2 SERVICE PARAMETERS Service parameters altered due to possib...

Page 71: ...sure switch 16 10 EXCHANGER FREEZING 24 Exchanger freezing is detected If the heating sensor detects a temperature below 2 C burn er ignition is inhibited until the sensor detects a temperature above...

Page 72: ...18 24 28 35 Flame noisy in cold ignition Act on parameter IG using the REGOLAFACILE section TECHNICAL MENU TSP parameters increasing the value by 5 10 max KON 18 24 KON 28 35 Flame noisy in steady sta...

Page 73: ...37...

Page 74: ...38...

Page 75: ...39...

Page 76: ...ziali Unical declines every responsibility for the possible inaccuracies if owed to errors of transcript or press Also reserves the right to bring those changes that it will hold necessary to it own p...