UNI Geräte MG A.X Series Operating Instructions Manual Download Page 3

UNI-Geräte E. Mangelmann Elektrotechnische Fabrik GmbH 

Holtumsweg 13, D-47652 Weeze, Tel. +49 2837/9134-0, Fax. +49 2837/1444 

www.uni-geraete.de  [email protected] 

Seite  3/9 

TM 4021 

220.100.040-09 

 

 
 

 

Solenoid Drive 

 

Series MG…X, MG…-A.X 

 

With  - protection for intended use in ex- zone 1 
 in accordance with 2014/34/EU (ATEX 95) 

 

 

Operation 

100% ED are permitted even in case of the most unfavourable ambient conditions. 

 
 

DANGER! 
During continuous operation the solenoid drive may get hot. Don‘t touch, 
danger of injuries! 

 

During operation it must be guaranteed, that neither the maximum permitted ambient tempera- ture or  
of the fluid nor the load limit (excess voltage) will be exceeded. If necessary the solenoid drive has to 
be protected against overcharging. All solenoid drives are wired with a varistor. To avoid induced 
voltage, which may cause damage within the installation, the user must possibly provide additional 
protective measures, which go beyond the installed varistor. 

 
 

 

Dismounting of the solenoid drive 

 

 

ATTENTION! 

Disconnect  the  circuit  before  opening  or,  respectively,  removing  the 
soleno id drive and wait at least 120 minutes. 

 

 
 

DANGER! 

During continuous operation the solenoid drive may get hot. Don‘t touch, 
danger of injuries! 

 

Loosen cylinder head screw (910/3) and remove it including lock washers (905/3). Remove so- 
lenoid  housing  cover  (105)  from  Ex-chamber  cover  (127).  Disconnect  the  connection  cable 
from the clamps of the line duct (733). Loosen the cylinder head screws (910/2) and remove 
them with the lock washers (905/2). 

 

CAUTION! 

The  Ex-chamber  cover  (127)  must  not  be  disconnected  from  the 
solenoid housing (103) by means of a screw driver or any other pointed 
tool. 

 

 

Lift the Ex-chamber cover (127) from the solenoid housing (103). Loosen the conductor line of 
solenoid drive MG..x at the connection clamp, or respectively, in case of solenoid drive MG.. 
 
 
 
 
 
 
 
 
 

Summary of Contents for MG A.X Series

Page 1: ...om the type plate Solenoid actuators are electrotechnical components that are inoperative without the associated valve and also may not be operated for themselves alone For outdoor installations alway...

Page 2: ...nge clamping range of the cable gland must be noted and adhered to Where a flexible connecting line is used insulated wire end sleeves with plastic collars conforming to DIN 46228 part 4 are to be use...

Page 3: ...may cause damage within the installation the user must possibly provide additional protective measures which go beyond the installed varistor Dismounting of the solenoid drive ATTENTION Disconnect th...

Page 4: ...istor control TS and remove ex chamber cover 127 putting it onto a clear surface Loosen the cylinder head screw 910 1 and remove it with the lock washer 905 1 The magnet plate 500 may be removed from...

Page 5: ...5 Solenoid drive MG x MG A x List of parts Item Qty Description 103 1 Solenoid housing 105 1 Solenoid housing cover 106 1 Upper part of housing 127 1 Ex chamber cover 403 1 O ring 500 1 Solenoid plate...

Page 6: ...e housing 106 as well as Ex chamber cover 127 must be free of any defective parts or scratches The surfaces are to be greased with Kl berplex BE 31 502 grease On tightening of the cylinder head screw...

Page 7: ...21 220 100 040 09 Solenoid Drive Series MG X MG A X With protection for intended use in ex zone 1 in accordance with 2014 34 EU ATEX 95 MG x MG A x with internal control in solenoid drive Solenoid val...

Page 8: ...5 Max temperature of housing 95 C Ambient temperatur 20 C bis 60 C Fluid temperatur Solenoid core in fluid 20 C bis 60 C Solenoid core not in fluid no influence Duty cycle 100 Switching frequency Sole...

Page 9: ...Holtumsweg 13 D 47652 Weeze Tel 49 2837 9134 0 Fax 49 2837 1444 www uni geraete de info uni geraete de Seite 9 9 TM 4021 220 100 040 09 Solenoid Drive Series MG X MG A X With protection for intended u...