PAGE 1 OF 3
0621 IH-7260
H-7260
PLASTIC LED
EMERGENCY LIGHT
1-800-295-5510
uline.com
INSTALLATION
CAUTION! When using electrical equipment,
always follow basic safety precautions,
including:
• Rated for temperature range of 50-104ºF and
suitable for applications designated as a damp
location area as defined by NEC Article 100,
Location, Damp.
• Do not use outdoors.
• Mount in locations and at heights where it will not
readily be subjected to tampering by unauthorized
personnel.
• Do not mount near gas or electric heaters.
• Use of accessories not recommended by the
manufacturer may cause an unsafe condition.
• Do not use this equipment for anything other than
intended use.
• Disconnect AC power and unplug battery before
servicing.
• Servicing of this equipment should be performed
by qualified personnel.
• Battery in unit may not be fully charged. After AC
service is supplied to unit, let the battery charge for
at least 24 hours before performing any tests.
NOTE: Cap unused wires using enclosed wire
nuts.
J-BOX MOUNTING
1. Open base plate and lead out a wire through hole
in base plate.
2. Fix base plate on J-Box with screws.
3. Connect to AC power. (See Figure 1)
NOTE: If using 120VAC, connect black and white
leads to building utility.
NOTE: If using 277VAC, connect orange and
white leads to building utility.
4. Connect to battery with connectors. (See Figure 2)
5. Attach housing to base plate, turn on AC power and
press test button to check light. (See Figure 3)
CONDUIT
1. Secure base plate to wall.
2. Route wires through hole in conduit flange and
make conduit connection.
NOTE: Use flexible conduit only.
3. Connect battery before continuous AC power is
supplied to unit. (See Figure 2)
4. Align snaps and push housing directly onto base
plate. Apply continuous AC power and press "TEST"
button to check light. (See Figure 3)
NOTE: During a power failure, lamps on unit will
automatically turn on for 90 minutes.
NOTE: To test unit, let it charge with AC power
for a minimum of 24 hours after its first
installation. Press test switch to illuminate the
emergency lights. When switch is released, the
lamps will turn off.
SAFETY
Figure 1
Figure 2
Figure 3
Test Button
Para Español, vea página 2.
Pour le français, consulter la page 3.