USER GUIDE

Thermistor 1

u-line.com

SAFETY • INSTALLATION & INTEGRATION • OPERATING INSTRUCTIONS • MAINTENANCE • 

SERVICE

Thermistors

Thermistors are used for various temperature readings. 
Thermistors provide reliable temperature readings using a 
resistance which varies based on surrounding 
temperatures. If a faulty thermistor is suspected it may 
be tested using an accurate ohmmeter.

All thermistors in the unit are identical. If a thermistor is 
suspected of being defective the resistance can be 
verified. Place the thermistor in an ice water bath, the 
resistance should read 16.1k OHMs +/-5% on your meter.

Thermistor connections must be kept clean. A thermistor 
connection that has become corroded can cause 
resistance values from the thermistor to change as they 
pass through a dirty connection to the board. 

It is for that reason that we apply dielectric grease to all of 
our thermistor connections. Dielectric grease will help to 
keep thermistor connections clean and dry. 

If you change a thermistor in the unit please re-apply 
dielectric grease to the connection. If you encounter a 
dirty thermistor connection, you should replace the 
thermistor and the thermistor harness.

Thermistor error information can be found in the Control 
Operations - Service section.

This unit has 

three

 thermistors.

Thermistor one (Zone):

Located along the right hand side wall. It is used to 
maintain the operating temperature within that zone.

Thermistor two (Evaporator):

Located on the evaporator. It is used for defrost.

Thermistor three (Ambient):

Located in the base of the unit (secured to the 
condenser). It is used to monitor the ambient temperature 
within the base compartment. It is used for diagnostics.

THERMISTOR FAILURE

Zone Thermistors

If a zone thermistor(s) in the unit fails the unit will 
continue to cool in a backup mode (Self Preservation 
Mode) to preserve the integrity of the contents. The unit 
will otherwise operate normally.

2000 Series Self Preservation Mode:
The unit will cycle on for 10 minutes then off for 40 
minutes.

3000 Series Self Preservation Mode:
Cycle times determined by zone - see chart. The error will 
be displayed on the main display, “Self Test” and logged in 
“All Errors.”

Self Preservation Mode Data Table - 3000 Series

Evaporator Thermistors

If an evaporator thermistor fails the unit will rely on a 
preset defrost timer during defrost cycles. The unit will 
otherwise operate normally. Refer to defrost section.

Ambient Thermistor

If the thermistor fails the unit will operate normally.

Mode

ON

OFF

Beverage/Drinks

10

45

Market/Fresh

10

45

Root

5

90

Pantry

10

45

Deli

10

45

White Wine

5

60

Red Wine

5

60

Sparkling Wine

10

60

Polar

55

5

52

Summary of Contents for 2224RGL

Page 1: ...SER GUIDE SERVICE MANUAL SAFETY INSTALLATION INTEGRATION OPERATING INSTRUCTIONS MAINTENANCE SERVICE 2000 Series 2224RGL 24 Glass Door Refrigerator RIGHT PRODUCT RIGHT PLACE RIGHT TEMPERATURE SINCE 196...

Page 2: ...Dimensions Grille Plinth Installation Door Swing Door Stop Door Adjust Operating Instructions First Use Control Operation Sabbath Mode Airflow and Product Loading Interior Shelves Refrigerator Bins C...

Page 3: ...decades and is proud to have the opportunity to ship to you PRODUCT INFORMATION Looking for additional information on your product User Guides Spec Sheets CAD Drawings Compliance Documentation and Pro...

Page 4: ...ury or death WARNING Warning means that failure to follow this safety statement could result in serious personal injury or death CAUTION Caution means that failure to follow this safety statement may...

Page 5: ...reezer take off the doors and leave shelves in place so children may not easily climb inside If the unit is being removed from service for disposal check and obey all federal state and local regulatio...

Page 6: ...10 C and 100 F 38 C Higher ambient temperatures may reduce the unit s ability to reach low temperatures and or reduce ice production on applicable models For best performance keep the unit out of dir...

Page 7: ...to the unit Always keep your working area dry NOTICE Electrical installation must observe all state and local codes This unit requires connection to a grounded three prong polarized receptacle that ha...

Page 8: ...he front grille plinth strip base fascia must NOT be obstructed CAUTION Unit can NOT be installed behind a closed cabinet door U Line products are designed and manufactured to be installed in the spec...

Page 9: ...Dimensions 1 u line com SAFETY INSTALLATION INTEGRATION OPERATING INSTRUCTIONS MAINTENANCE SERVICE Product Dimensions 3 5 16 84 mm 33 11 16 to 34 11 16 856 to 881 mm 23 5 8 600 mm Not Including Handl...

Page 10: ...t Dimensions in each unit s Installation Guide Each door can be opened individually one at a time without interference However to ensure unobstructed door swing opening both doors at the same time 1 4...

Page 11: ...drill bit drill 3 pilot holes 5 8 16 mm deep into bottom of counter top Use the anti tip bracket as a template 4 Install 3 8x5 8 screws into the plate using a 2 Phillips head screwdriver SIDE MOUNT Si...

Page 12: ...total unit rear height of 1 8 3 mm less than the opening s rear height Shorten the unit height in the front by adjusting the front legs This allows the unit to be gently tipped into the opening Adjust...

Page 13: ...panel to match your surrounding furniture Finish front back and edges to prevent warping Carefully follow the manufacturer s recommendations for finish application and cure times 3 Apply double sided...

Page 14: ...fascia When using the unit the grille plinth strip base fascia must be installed WARNING DO NOT touch the condenser fins The condenser fins are SHARP and can be easily damaged Removing the grille pli...

Page 15: ...llow the door to open 90 Allow for additional space for any knobs or pulls installed on the integrated panel frame Stainless Steel models that are installed adjacent to a wall require 2 1 4 57 mm door...

Page 16: ...pproximately 90 2 Remove hinge cover by lifting top and bottom of hinge cover and sliding the cover inwards to remove from hinge 3 Once cover is removed slide hinge pin into hole as shown Pin should s...

Page 17: ...that it is firmly in contact with the cabinet Also make sure the door gasket is not pinched on the hinge side of the door CAUTION Do not attempt to use the door to raise or pivot your unit This would...

Page 18: ...ve caps from screw heads on opposite side 2 on top and 2 on bottom Using 2 Phillips bit remove the 4 underlying screws Reinstall the screws and caps on the opposite side 5 Partially install screw 1 in...

Page 19: ...the factory Initial startup requires no adjustments NOTICE U Line recommends allowing the unit to run overnight before loading with product When plugged in the unit will begin operating under the fac...

Page 20: ...OL FUNCTION GUIDE FUNCTION COMMAND DISPLAY OPTIONS ON OFF Press and release Unit will immediately turn ON or OFF Toggle lights Press and release to leave interior light on for 3 hours Glass door wine...

Page 21: ...ain internal temperatures and set points View a full list of Star K certified U Line units at www star k org To enable Sabbath Mode 1 Press 4 and hold for ten seconds and release the F C symbol will f...

Page 22: ...eave space between the internal fans or vents and product loaded Anything blocking the required airflow circulation will result in uneven temperature distribution in the cabinet and can also freeze pr...

Page 23: ...f Height Shelf height may be adjusted to accommodate a broad range of product To alter your shelf spacing follow the instructions below 1 Remove the 4 Shelf clips from the shelf clip holes 2 Move shel...

Page 24: ...of the bin and raise the bin off the racks 3 Lift the rear of the bin off its seat on the rack 4 Pull the bin up and away from the racks To Reinstall 5 Fully extend the empty rack from within the cab...

Page 25: ...otchbrite will cause the graining in the stainless steel to become blurred Rust not cleaned up promptly can penetrate the surface of the stainless steel and complete removal of the rust may not be pos...

Page 26: ...drain pan and possibly damaging water sensitive flooring the unit must be removed from cabinetry To defrost 1 Disconnect power to the unit 2 Remove all products from the interior 3 Prop the door in a...

Page 27: ...n necessary Depending on environmental conditions more or less frequent cleaning may be necessary WARNING Disconnect electric current to the unit before cleaning the condenser NOTICE DO NOT use any ty...

Page 28: ...is returned to service 3 If ice is on the evaporator allow ice to thaw naturally 4 Clean and dry the interior of the unit Ensure all water has been removed from the unit 5 The door must remain open t...

Page 29: ...listed Compressor The compressor makes a hum or pulsing sound that may be heard when it operates Evaporator Refrigerant flowing through an evaporator may sound like boiling liquid Condenser Fan Air mo...

Page 30: ...openings and the time the door is open The time the internal light is illuminated This mainly affects product on the top rack or shelf Digital Display Shows 1 16 or 99 A factory test mode may be enabl...

Page 31: ...UG 220 240 VOLT PLUG OVERLOAD NEUTRAL WHITE 115v DARK BLUE 220 240v TO COMPRESSOR NEUTRAL WHITE 115v DARK BLUE 220 240v BLUE 115V LIGHT BLUE 220V 240V TO COMPRESSOR 1 10 CONTROL BOARD ZONE TEMP FUSE 1...

Page 32: ...nt of a part the servicer is authorized to replace the part in question The part that caused the damage must be returned to U Line in its entirety The part must be clearly labeled with the serial numb...

Page 33: ...shes 12 represents the production month In most cases warranty status can be verified by the production date information within the serial number Alternatively a Proof of Purchase or equivalent may su...

Page 34: ...p fan w cover and screws 80 54151 00 14 Evaporator 80 54057 00 15 Evaporator cover 80 54045 00 16 Glass shelf 1 w clips 80 54041 00 17 Grille w screws 80 54040 00 18 Hinge covers 2 pcs 80 54001 00 19...

Page 35: ...s will be shipped at no charge after U Line confirms warranty status Please provide the model serial number part number and part description Some parts will require color or voltage information If U L...

Page 36: ...federal state and local laws regarding refrigerants Gloves and Eye Protection must be used R 600a is considered non toxic but is flammable when mixed with air Keep a dry powder type fire extinguisher...

Page 37: ...equipment should be at least 10 feet from the work area It is recommended that a simple LPG gas detector is on site during service Ensure that all R 600a is removed from the system prior to brazing a...

Page 38: ...he system prior to repair simple venting is not sufficient Evacuate and charge with dry nitrogen for leak checks Repair leaks or replace system parts as required When re brazing the system must be pur...

Page 39: ...e access port on the compressor process stub Evacuate the system to 100 microns prior to charging Weigh in the R 600a charge using a refrigerant scale run compressor an extra two minutes to clear the...

Page 40: ...Lower than normal Warm near room temperature Hot Warm Warm Extremely cold near inlet Outlet below room temperature Lower than normal Partial Restriction Somewhat lower than normal vacuum Warm near ro...

Page 41: ...st strap that is grounded to an electrical ground or grounded water pipe Handle circuit boards carefully and avoid touching components To measure the start winding resistance measure across the C and...

Page 42: ...utputs located on the relay power board Included in this section are some diagnostic tips and of course if additional help is required please contact the U Line Corp Customer Care Facility at 1 800 77...

Page 43: ...efer to 14 Error Log in Service Mode Thermistor failure Check Error Log in Service Mode OHM thermistor Frost Buildup Inside Unit Door Ajar or Restricted from Closing Check door clearance to adjoining...

Page 44: ...into overload The compressor will automatically deactivate during an overload and will remain deactivated until the overload switch cools This could take some time It is important to allow the compres...

Page 45: ...d magnetic force pulls the reed to its contact and closes the circuit which turns the light and display off When the door is open the reed pulls away from the contact and opens the circuit If the door...

Page 46: ...gates through service menu LED activated with button activation 3 Down Button Decreases temperature Navigates through service menu LED activated with button activation 4 Light Button Activates light f...

Page 47: ...ter exit this mode hold the light key and the power key for 5 seconds The display will flash once and beep and the degree symbol will begin to flash When the degree symbol is flashing the unit will al...

Page 48: ...n the refrigerator section 13 ADJUST DEFROST DURATION 0 TO 99 MINUTES The length of the defrost can be adjusted 0 to 99 minutes long The other defrost parameters still apply Lengthening a defrost may...

Page 49: ...n will continue to run at the end of a cooling cycle Adjustable 0 99 minutes 19 INDIVIDUAL COMPONENT TOGGLE 20 MODEL NUMBER INDICATOR Displays the two digit model number of the specific unit See model...

Page 50: ...conds use the up and down arrow buttons to select the appropriate model number See Above Model List 5 Press the light bulb button once 6 The display will blink and then will appear as the programmed d...

Page 51: ...t Evaporator Fan Condenser Fan N A N A 2218WC N A N A N A N A N A Compressor Light Evaporator Fan Condenser Fan N A N A 2224BEV N A N A N A N A N A Compressor Light Evaporator Fan Condenser Fan N A N...

Page 52: ...e Control Operations Service section This unit has three thermistors Thermistor one Zone Located along the right hand side wall It is used to maintain the operating temperature within that zone Thermi...

Page 53: ...ta Temp F Temp C Nominal Resistance OHMS 40 40 169157 31 35 121795 22 30 88766 13 25 65333 4 20 48614 5 15 36503 14 10 27681 23 5 21166 32 0 16330 41 5 12696 50 10 9951 59 15 7855 68 20 6246 77 25 500...

Page 54: ...C 1224 RF 12 45 15 9 1215 1224 2218 2245 2224 2260 WC ZWC 12 45 45 7 1215 1224 2218 2245 2224 2260 R RSOD RDC BEV DC DWR RGL 12 45 42 6 CO29 F 12 18 n a CO1224 F 12 18 45 7 1224FZR Freezer Mode 6 45...

Page 55: ...losed the fan will either continue running with the cooling cycle or if not currently cooling the fan will run for 1 minute to circulate air and clear any condensation that may have appeared on glass...

Page 56: ...ole 13 Remove the 4 screws mounting the fan shroud to the evaporator plate 14 Remove and replace fan Take special care to properly route fan wire NOTICE Fan must be oriented to pull air in through low...

Page 57: ...nty arising by operation of law U Line will not be responsible for any consequential or incidental damages arising from the breach of these warranties or any other warranty whether express implied or...

Reviews: