RDU Mk2 Installation & Programming Manual
Document No: LT0499
Programming Part 1
Page 6-36
8 April 2015
Issue 1.02
7. Set 8 hr period in 6 minute units
A value from 0 to 255 can be set. A default value of 80 selects a time of 8 hours for the
buzzer re-activation period described above.
8. Buzzer operates in loud mode when door/keyswitch is open/enabled
This option allows selection of quiet or loud mode for the buzzer when the door is open.
This is particularly for slim-line RDUs where the door may be open (keypad enabled) all
of the time. The default setting is quiet mode.
6.4.4.13
New Zealand Mode
Selecting "New Zealand options
” from the global data menu produces the following menu.
1:NZ mode enabled 2:Display bd >
Pressing the right arrow key produces
1:External defect is fault
On the first menu, option 1 allows New Zealand mode to be enabled or disabled. Option 2
allows the NZ display extender board to be enabled or disabled. On the second menu, the
external defect input can be enabled or disabled.
When New Zealand mode is enabled or disabled, a number of other parameters are
changed automatically as shown in the table below.
PARAMETER
AUSTRALIAN DEFAULT
NEW ZEALAND DEFAULT
New Zealand mode enabled
External defect is fault
Zone alarm buzzer enabled
Zone fault buzzer enabled
System fault buzzer enabled
Fault sounder after 8 hrs fault
Fault sounder after 8 hrs isolate
Mains fail is fault after 8 hours
Battery low is fault
Battery connection test enabled
Hourly battery test enabled
Daily 40 minute battery test enabled
Charger high/low is fault
MCP is enabled
Daylight savings
N
N
Y
Y
Y
Y
Y
N
Y
Y if MAF bd
Y if MAF bd
Y if MAF bd
Y if MAF bd
Y
Defaults (disabled)
Y
Y
Y
N
N
N
N
N
Y
Y if MAF bd
Y if MAF bd
Y if MAF bd
Y if MAF bd
N
Defaults (disabled)
The default settings for Australian operation are required for AS4428.1 compliance.