Model QRS Electronic Accelerator  

(Quick Opening Device)  

For Dry Pipe or Preaction Systems

Page 1 of 16 

SEPTEMBER 2021 

TFP1100

Worldwide 

Contacts

www.tyco-fire.com

IMPORTANT

Refer to Technical Data Sheet 

TFP2300 for warnings pertaining to 

regulatory and health information.

General 

Description

The TYCO Model QRS Electronic 

Accelerator is a quick opening device 

intended to reduce the operating time 

of a dry pipe valve in a dry pipe system 

or an automatic control valve (deluge 

valve) in a double interlock electric/

electric preaction system.
The control panel for the QRS may be 

used with up to four QRS switches for 

one to four system risers using one of 

the following dry pipe valves:

•  TYCO 4 in. & 6 in. (DN100/150) 

Model DPV-1 Dry Pipe Valves

•  Central 3 in. (DN80) Model AF or 

Central 4 in. & 6 in. (DN100/150) 

Model AF/AG Dry Pipe Valves

•  Gem 4 in. & 6 in. (DN100/150) Model 

F302/F3021 Dry Pipe Valves

•  Star 4 in. & 6 in. (DN100/150) Models 

A or A-1 Dry Pipe Valves

The control panel for the QRS may 

be used with one QRS switch for one 

system riser using the following auto-

matic control valve (deluge valve) used 

in a double interlock electric/electric 

preaction system:

•  TYCO 1-1/2 in. through 8 in. (DN40 

through DN200) DV-5

A

 Deluge Valve

The Model QRS Electronic Accelerator 

(see Figure 1) utilizes a unique system 

air pressure monitoring device (UL and 

C-UL Listed, as well as FM Approved, 

Model QRS Extinguishing System 

Attachment) that continuously samples 

air pressure twice per sec ond. When 

the air pressure is deter mined to have 

a sustained drop ex ceeding a rate of 

0.1 psi (0,007 bar) per second as veri-

fied by three con secutive samplings, 

the QRS signals the Releasing Panel 

(Model PFC 4410-RC) via its “Panel 

Input” initiating zone circuit, which 

energizes the Sole noid Valve.

In the case of a dry pipe valve, the 

energized Solenoid Valve introduces 

system air pressure to the interme-

diate chamber of the dry pipe valve. 

This pressure neutralizes the differen-

tial pressure holding the dry pipe valve 

closed and permits it to open.
In the case of a double interlock elec-

tric/electric preaction system, the 

energized Solenoid Valve releases dia-

phragm pressure from the automatic 

control valve (deluge valve) to permit 

the automatic control valve (deluge 

valve) to open.
The Model QRS Electronic Accelera-

tor automatically adjusts to both small 

and slow changes in system pressure, 

but trips when there is a steady drop 

in pressure (as in the case of sprinkler 

operation).
The QRS Electronic Accelerator fea-

tures the following: 

•  Operation of a dry pipe or preaction 

valve within four seconds — inde-

pendent of various combinations of 

system initial air pressures, system 

volumes, or sprinkler K-factors 

•  One Releasing Panel can control 

up to four dry pipe systems or one 

double interlock preaction system

•  Built-in low pressure and high 

pressure alarm supervision

•  Proven electric release technology 

as used for electrically operated 

del uge and preaction systems

•  Battery back-up in the event of 

primary power failure

NOTICE

The Model QRS Electronic Accel-

erator described herein must be 

installed and maintained in compli-

ance with this document, as well as 

with the applicable standards of the 

NATIONAL FIRE PROTECTION ASSO-

CIATION (NFPA), in addition to the 

standards of any other authorities  

having jurisdiction. Failure to do so may 

impair the performance of this de vice.
The owner is responsible for main-

taining their fire protection system 

and devices in proper operating con-

dition. Contact the installing contrac-

tor or sprinkler manufacturer with any 

questions.
The QRS uses electronic compo-

nents to monitor the system air pres-

sure. Keep all radio transmitters or RF 

sources at least one foot from the QRS. 

Failure to do so could result in an unin-

tended operation of the dry pipe or pre-

action system.
For additional information please refer 

to the Potter Electric Signal Company 

Data Sheet #5471131 for the QRS 

Quick Release Switch and/or Manual 

#5403550 for the PFC-4410RC Releas-

ing Panel. 

Technical 

Data

Approvals

UL Listed:

The Model QRS Electronic 

Accelera tor is UL Listed per UL1486 

for a maximum system capacity of 

1690 gal (6397 L) for a single nom-

inal 5.6 K-factor sprinkler and a 

maximum working water pressure 

of 175 psi (12,1 bar).

FM Approved:

The Model QRS Electronic 

Accelera tor is FM Approved based 

on the sensitivity criteria provided 

in Graph A and a maximum working 

water pressure of 250 psi (17,2 bar). 

Listings and Approvals are under 

the name of Potter Electric Signal 

Com pany. 

Summary of Contents for QRS

Page 1: ...e from the automatic control valve deluge valve to permit the automatic control valve deluge valve to open The Model QRS Electronic Accelera tor automatically adjusts to both small and slow changes in...

Page 2: ...ion Step 1 The QRS Electronic Accelera tor Riser Components P N 52 312 2001 must be installed per Figure 2 or 8 as applicable The DV 5A Double Interlock Preaction Trim with Electric Electric Actuation...

Page 3: ...79 65 4 48 70 4 83 MODEL DPV 1 DRY PIPE VALVE WITH TRIM 4 INCH DN100 SOLENOID VALVE NORMALLY CLOSED UNTIL ENERGIZED 24 VDC P N 52 287 1 024 MODEL PFC 4410 RC RELEASING PANEL P N 20135 WITH MODEL BT 1...

Page 4: ...stem operation is based on the electric detec tion system operating before a first sprinkler operation 4 The minimum system air pressure must be the greater of that required for the dry pipe preaction...

Page 5: ...DN80 6 INCH DN150 4 INCH DN100 6 7 ACCELERATOR TRIM CONNECTION TO INTERMEDIATE CHAMBER 1 2 NPT 3 4 2 10 7 6 3 QUICK RELEASE SWITCH ACCELERATOR TRIM CONNECTION TO AIR SUPPLY PORT 1 2 NPT 9 5 8 5 1 6 7...

Page 6: ...3 922111003 922111003 16 1 DRIP FUNNEL 923431007 923431007 923431007 923431007 923431007 923431007 17 2 COMP FITTING 90 1 2 MNPT x 1 2 OD TUBE 1001253 01 1001253 01 1001253 01 1001253 01 1001253 01 10...

Page 7: ...000640 535000660 535000680 48 1 TUBING ASSY ALARM TEST INTERCONNECT 535000320 535000320 535000330 535000340 535000360 535000380 49 1 TUBING ASSY SYSTEM DRAIN 535000420 535000420 535000430 535000440 53...

Page 8: ...e System Gauge Item Description M N P Q R S T U V W X Manual Control Station Manual Reset Actuator Diaphragm Supply Valve Diaphragm Supply Strainer Water Supply Shut Off Air Supply Valve Air Pressure...

Page 9: ...NCH DN65 DN80 VALVES 4 INCH DN100 VALVE 6 INCH DN150 VALVE 7 5 16 185 7 mm 19 5 16 490 5 mm 6 3 8 161 9 mm 20 508 0 mm 5 7 16 138 1 mm 21 7 16 544 5 mm FIGURE 4A MODEL DPV 1 DRY PIPE VALVE INSTALLATIO...

Page 10: ...3 0 76 12 2 310 13 1 333 16 5 419 21 0 533 5 1 129 16 8 427 4 5 114 4 3 109 6 150 4 5 114 13 6 345 15 0 381 18 4 467 24 8 630 3 4 86 22 4 569 5 9 150 5 7 145 8 200 5 3 135 16 3 414 17 2 437 19 5 495...

Page 11: ...INSTALL AT PART 3005012 DIODE ASS Y END OF LINE RELEASING SOLENOID 5 1K LOCATION SOLENOID INSTALL AT PART 3005012 DIODE ASS Y END OF LINE RELEASING SOLENOID 5 1K LOCATION SOLENOID INSTALL AT PART 300...

Page 12: ...ZONE 1 SUPERVISORY ABORT BROWN BLUE YELLOW ORANGE VIOLET GREEN BLACK RED EOLR ALARM AIR LOW TAMPER 24VDC JUMPER JUMPER HIGH GREEN BROWN RED BLACK BLUE VIOLET RELEASING SOLENOID 5 1K LOCATION SOLENOID...

Page 13: ...drain valve The blow down proce dure that will assure complete drain ing of the system will be more easily ac complished with 10 psi air pressure in the system Step 6 When the system reaches the inten...

Page 14: ...elerator test procedure be per formed quarterly Step 1 When operation of the dry pipe preaction valve is not intended during the Accelerator trip test close the sys tem s Main Control Valve and open t...

Page 15: ...ded Field fabrication of additional materials will be Some items provided with the Model QRS Trim P N 52 312 2 001 are not used for the 2 Installation notes are typical of all Dry Pipe Valve models sh...

Page 16: ...ctric Actuation Trim When ordering Model QRS Quick Release Switch equipment for use with the DV 5a Valve Double Interlock Pre action Electric Electric Actuation Trim the QRS equipment and DV 5a Valve...