Issue D QUARTZOID – 5.6 and 8.0 K-factor 

High Temperature, Upright and Pendent Sprinkler 

Standard Response, Standard Coverage

Page 1 of 4 

AUGUST 2018 

TFP690

IMPORTANT

Refer to Technical Data Sheet 

TFP2300 for warnings pertaining to 

regulatory and health information.
Always refer to Technical Data 

Sheet TFP700 for the “INSTALLER  

WARNING” that provides cautions 

with respect to handling and instal-

lation of sprinkler systems and com-

ponents. Improper handling and 

installation can permanently damage 

a sprinkler system or its compo-

nents and cause the sprinkler to fail  

to operate in a fire situation or cause  

it to operate prematurely.

Worldwide 

Contacts

www.tyco-fire.com

General 

Description

TYCO Issue D QUARTZOID 5.6K and 

8.0K Upright and Pendent Sprinklers 

are standard response, standard cov-

erage, 11 mm glass bulb-type spray 

sprinklers designed for use in light, 

ordinary, or extra-hazard, commercial 

occupancies where high ambient tem-

peratures may be encountered.
Corrosion-resistant coatings, where 

applicable, are utilized to extend the life 

of copper alloy sprinklers beyond that 

which would otherwise be obtained 

when exposed to corrosive atmo-

spheres. Although corrosion-resistant 

coated sprinklers have passed the 

standard corrosion tests of the appli-

cable approval agencies, the testing is 

not representative of all possible cor-

rosive atmospheres. Consequently, 

it is recommended that the end user 

be consulted with respect to the suit-

ability of these coatings for any given 

corrosive environment. The effects of 

ambient temperature, concentration of 

chemicals, and gas/chemical velocity 

should be considered, as a minimum, 

along with the corrosive nature of the 

chemical to which the sprinklers will be 

exposed.

NOTICE

The Issue D QUARTZOID Sprinklers 

described herein must be installed 

and maintained in compliance with this 

document, as well as with the applica-

ble standards of the NATIONAL FIRE 

PROTECTION ASSOCIATION (NFPA), 

in addition to the standards of any other 

authorities having jurisdiction. Failure 

to do so may impair the performance 

of these devices.
The owner is responsible for main-

taining their fire protection system 

and devices in proper operating con-

dition. Contact the installing contrac-

tor or product manufacturer with any 

questions.

Sprinkler 

Identification 

Numbers (SINs)

TY3191        Upright 5 6K, 1/2 in  NPT
TY3296      Pendent 5 6K, 1/2in  NPT
TY4191        Upright 8 0K, 3/4 in  NPT
TY4292      Pendent 8 0K, 3/4 in  NPT

TY3191 is a re-designation for G1036
TY3296 is a re-designation for G1040
TY4191 is a re-designation for G1136
TY4292 is a re-designation for G1140

Technical 

Data

Approvals

UL and C-UL Listed 

FM and LPCB Approved 

(Refer to Table A for complete approval 

information, including corrosion-resistant 

status.)

Maximum Working Pressure

175 psi (12,1 bar)

Discharge Coefficients

K=5.6 gpm/psi

½

 (80,6 lpm/bar

½

K=8.0 gpm/psi

½

 (115,2 lpm/bar

½

)

Temperature Ratings

Refer to Table A

Finishes

Refer to Table A

Physical Characteristics

Frame  . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze

Deflector . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze

Bulb Seats . . . . . . . . . . . . . . . . . . . . . . . . .Bronze

Pin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze

Button . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze

Spacer . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze

Spring Plates . . . . . . . . . . . . . . . . . . . .  INCONEL

Gaskets . . . . . . . . . . . . . . . . . . . . . . . . . .  Copper

Bulb (11 mm dia.)  . . . . . . . . . . . . . . . . . . . . Glass

Design 

Criteria

TYCO Issue D QUARTZOID 5.6K and 

8.0K Upright and Pendent, Standard 

Response, Standard Coverage Sprin-

klers are intended for fire protection 

systems designed in accordance with 

the standard installation rules rec-

ognized by the applicable listing or 

approval agency (UL Listing is based 

on the requirements of NFPA 13, and 

FM Approval is based on the require-

ments of FM Approvals’ Loss Preven-

tion Data Sheets).

Operation

The glass bulb contains a fluid which 

expands when exposed to heat. When 

the rated temperature is reached, the 

fluid expands sufficiently to shatter the 

glass bulb, allowing the sprinkler to 

activate and water to flow.