background image

Model EG-25 Sprinkler Guard 

For Model ESFR-25 Pendent Sprinkler

Page 1 of 2 

AUGUST 2018 

TFP784

IMPORTANT

Refer to Technical Data Sheet 

TFP2300 for warnings pertaining to 

regulatory and health information.
Always refer to Technical Data 

Sheet TFP700 for the “INSTALLER  

WARNING” that provides cautions 

with respect to handling and instal-

lation of sprinkler systems and com-

ponents. Improper handling and 

installation can permanently damage 

a sprinkler system or its compo-

nents and cause the sprinkler to fail  

to operate in a fire situation or cause  

it to operate prematurely.

Worldwide 

Contacts

www.tyco-fire.com

General 

Description

The TYCO Model EG-25 Sprin-

kler Guard is designed for use with 

the TYCO Model ESFR-25 Pendent 

Sprinkler and may be located in areas 

that make it susceptible to mechanical 

or physical damage.
The Model EG-25 Sprinkler Guard, 

as seen in Figure 2, provides protec-

tion from mechanical and/or physical 

damage, for example, rack storage 

sprinkler installations.
The Model EG-25 Sprinkler Guard 

is intended for use in fire sprinkler 

systems designed in accordance with 

the standard installation rules recog-

nized by the applicable Listing agency.

NOTICE

The Model EG-25 Sprinkler Guard 

described herein must be installed 

and maintained in compliance with 

this document and with the appli-

cable standards of the NATIONAL 

FIRE PROTECTION ASSOCIATION 

(NFPA), in addition to the standards 

of any Authorities Having Jurisdiction. 

Failure to do so may impair the perfor-

mance of these devices.
Owners are responsible for maintaining 

their fire protection system and devices 

in proper operating condition. The 

installing contractor or sprinkler man-

ufacturer should be contacted with any 

questions.

Technical 

Data

Approvals

FM Approved

Finishes

Red painted and zinc chromate

Physical Characteristics

Welded assembly fabricated from carbon 

steel

Design 

Criteria

In accordance with the requirements 

of the NFPA, sprinkler guards shall be 

Listed. Sprinkler guards are only Listed 

for use with specified sprinklers; there-

fore, the Model EG-25 Sprinkler Guard 

should only be used with the TYCO 

Model ESFR-25 

Pendent 

Sprinkler. 

Installation

The TYCO Model EG-25 Sprinkler 

Guard must be installed onto the TYCO 

Model ESFR-25 Sprinkler in accor-

dance with this section and with refer-

ence to Figures 1 and 2:

Note: The Model ESFR-25 Sprinkler 

must be installed in accordance with 

Technical Data Sheet TFP312 before 

installing the Model EG-25 Sprinkler 

Guard.

Step 1.

 With the clips loose, care-

fully spread the two halves of 

the sprinkler guard apart so 

the bars pass by the sprinkler 

deflector and the base plates pass by 

the sprinkler thread relief from the side. 

Step 2.

 Position the guard on center 

relative to the sprinkler, engaging the 

base plates evenly onto the sprinkler 

thread relief. Align the guard base plate 

gaps parallel with the sprinkler frame 

arms.

Step 3.

 Swivel the first clip to engage 

the open end onto the opposing bar 

and slide toward the base plates until 

fully seated against the base plates

Step 4.

 Swivel the second clip to 

engage the open end onto the oppos-

ing bar and slide toward the base 

plates until fully seated against the 

base plates.

Note: The Installation Tool shown in 

Figure 2 may be used as an aid when 

sliding and seating the clips. Pliers may 

be used in addition to the Installation 

Tool to facilitate seating the clips.

NOTICE

To complete the installation, the clips 

must seat against the base to be fully 

seated.

Care and 

Maintenance

The TYCO Model EG-25 Sprinkler 

Guard does not require any regularly 

scheduled maintenance; however, 

proper installation of the sprinkler guard 

should be verified during the annual 

visual inspection of the sprinkler. 

NOTICE

Before closing a fire protection system 

main control valve for maintenance 

work on the fire protection system 

that it controls, obtain permission to 

shut down the affected fire protec-

tion system from the proper authori-

ties and notify all personnel who may 

be affected by this action.
Responsibility lies with sprinkler 

owners for the inspection, testing, 

and maintenance of their fire protec-

tion system and devices in compliance 

with this document, as well as with 

the applicable standards of the NFPA  

(for example, NFPA 25), in addition to 

Reviews: