Section 5 Programming Descriptions
13
6HFWLRQ>@6\VWHP7LPHV
After entering Section
[005]
, enter the 2-digit subsection number for the desired partition and program the
Entry Delay 1
,
Entry Delay 2
and
Exit Delay
for each active partition on the system. Valid entries are from
[001]
to
[255]
. Enter subsection
[09]
to program the
Bell Cut-Off
Time
. Valid entries are from
[001]
to
[255]
(in minutes).
6HFWLRQ>@,QVWDOOHU&RGH
The default Installer Code is
[5555]
or
[555555]
if 6-Digit Access Codes is enabled.
6HFWLRQ>@0DVWHU&RGH
The installer does not have access to this section. The master code can be restored to default in section [989] Default Master Code. The
default Master Code is [1234] or [123456] if 6-Digit Access Codes is enabled.
6HFWLRQ>@0DLQWHQDQFH&RGH
The default Maintenance Code is
[AAAA]
(not programmed).
6HFWLRQ>@WR>@3*02XWSXWV
The PC1616 and PC1832 have two on-board PGM outputs (PGM1 and PGM2). The PC1864 has four on-board PGM outputs (PGM1 to
PGM4). The panel has the capacity for up to 14 PGM outputs (8 additional low-current PGM outputs with PC5208 module, 4 additional
high-current PGM outputs with a PC5204 module).
3*02XWSXW2SWLRQV
[35]
24-Hour Bell/Buzzer:
Instant alarm when violated, system will activate bell output if armed, keypad buzzer if disarmed
[36]
24-hour Non-Latching Tamper Zone:
Instant tamper condition when violated. Active in both the armed and disarmed state
[37]
Night Zone:
Functions like Interior Stay/Away but will remain bypassed if the user presses
[
,
][1]
to re-activate Stay/Away zones
when armed in the Stay mode
[41]
24 Hr. Carbon Monoxide:
This zone type is used with a hardwired CO detector. This zone definition has a distinct bell cadence in
the event of an alarm. The cadence of this alarm is 4 cycles of 100ms on/off pulses, followed by a 5-second pause, and then
repeated. After 4 minutes, the 5-second pause is extended to 60 seconds in duration. The bell is silenced when an access code is
entered or the bell times out (see your CO detector instruction sheet for more details)
[81]
24 Hr. Carbon Monoxide (Wireless):
This zone type is used with a wireless CO detector. This zone definition has a distinct bell
cadence in the event of an alarm. The cadence of this alarm is 4 cycles of 100ms on/off pulses, followed by a 5-second pause, and
then repeated. After 4 minutes, the 5-second pause is extended to 60 seconds in duration. The bell is silenced when an access code
is entered or the bell times out
[87]
Delayed 24-Hour Fire (Wireless/Addressable):
Same as Delayed 24-Hour Fire (Hardwire) but must be used for wireless or
addressable smoke detectors
[88]
Standard 24-Hour Fire (Wireless/Addressable):
Same as Standard 24-Hour Fire (Hardwire) but must be used for wireless or
addressable smoke detectors
Option Description
[00]
For Future Use
[01]
Fire and Burglary:
Output will activate (steady for burglary, pulsing for fire) if an alarm occurs on the selected partition
[02]
For Future Use
[03]
Sensor Reset:
Output will normally be active and deactivate for 5 seconds when a
[
,
][7][2]
fire reset command is entered or when an
Auto-Verify Fire alarm is detected
[04]
2-Wire Smoke:
Configures PGM2 as 2-wire smoke detector input (PGM2 only)
[05]
Armed Status:
Output will activate when all of the selected partitions are armed
[06]
Ready Status:
Output will activate when all the selected partitions are in the Ready state (Ready light
ON
)
[07]
Keypad Buzzer Follow:
Output will activate and follow the keypad buzzer for the selected partition when the following events occur;
entry delay, door chime, audible exit delay, automatic arming pre-alert, 24-Hour Supervisory Buzzer zone alarm
[08]
Courtesy Pulse:
Output will activate during entry/exit delay if the selected partition is armed – will remain active for an additional 2
minutes after the entry or exit delay expires
[09]
System Trouble:
Output will activate when any selected trouble condition is present
[10]
Latched System Event (Strobe):
Output will activate when a selected condition occurs on any selected partition. Note output can be
programmed to follow timer
[11]
System Tamper:
Output will activate when any tamper condition is present
[12]
TLM and Alarm:
Output will activate if a telephone line trouble is present and then an alarm occurs
[13]
Kissoff:
Output will activate for 2 seconds when a valid kissoff is received from the central station
[14]
Ground Start:
Output will activate for 2 seconds when the panel attempts to seize the phone line (additional dial tone search must be
programmed in the central station phone number – HEX
[D]
)
[15]
Remote Operation:
Output can be activated/deactivated via the DLS software