This installation guide provides the basic wiring, programming and troubleshooting information required to install the PowerSeries Neo alarm controller. 

Use this guide in conjunction 

with the 

PowerSeries Neo Reference Manual

 available online from the DSC website at www.dsc.com.

 Available models: HS2016, HS2032, HS2064, HS2128.

Quick Setup

Compatible Devices

Throughout this document, x in the model number represents the operating frequency of the device 

as follows: 9 (912-919 MHz), 8 (868MHz), 4 (433MHz).

NOTE: 

Only models operating in the band 912-919 MHz are UL/ULC listed where indicated. Only

UL

 approved devices are to be used with UL/ULC listed systems.

Table 1-1 Compatible Devices

Alarm Controller v1.0 Installation Guide

1

Plan

Plan the installation including all alarm detection 

devices, zone expanders, keypads and other 

required modules.

2

Mount

Decide on a location for the alarm panel and 

secure it to the wall using suitable mounting 

hardware.

3

Wire

Complete all wiring including modules, zones, 

bells/sirens, telephone line connections and ground 

connections. Record module serial numbers on 

page 13.

4

Power

Connect the battery and power up the system. The 

battery must be connected.

5

Enroll 
First Key-
pad

Hardwired: Wire the keypad to the Corbus, power 

up the alarm panel then press any button on the 

keypad.
Wireless: Wire the HSM2Host to the Corbus, then 

power up the alarm panel and a wireless keypad. 

Press any button on the keypad to enroll it. The 

HSM2Host is then enrolled on the alarm panel. 

Alternately, enroll an RF keypad.

6

Enroll 
modules

[*][8][Installer Code][902] subsection [000]. Press 

[*] to begin auto-enrollment. 
Module slots are automatically assigned. Use 

scroll keys to view slots. Change slot by typing a 

2-digit number.

7

Enroll 
wireless 
devices

[*][8][Installer Code][804] subsection [000].
Note: An HSM2HOST or RF keypad must be 
enrolled first.

8

Program

Basic programming:
[*][8][installer code]
[001]/[002]> Zone Type/Zone Attribute
[005]>[001] Partition 1 Timers:
– Entry Delay 1
– Entry Delay 2
– Exit Delay
[301]>[001] Phone #1
[310]>[000] System Account Code

9

Test

Test the panel completely to ensure that all 
features and functions operate as programmed.
– [901] Walk Test
– [904][000] Wireless Placement Test

Modules

Wireless keypads:

HS2LCDWFx

UL

 

HS2LCDWFPx

UL

 

HS2LCDWFPVx

UL

 

Hardwired keypads with 2-way wireless 

integration module:

HS2LCDRFx

UL

HS2LCDRFPx

UL

 

HS2ICNRFx 

UL

HS2ICNRFPx

UL

Hardwired keypads:

HS2LCD

UL

HS2LCDP

UL

HS2ICN

UL

HS2ICNP

UL

HS2LED

UL

2-way wireless integration module:

HSM2HOSTx 

UL

8-zone expander:

HSM2108

UL

8-output expander:

HSM2208

UL

Power supply:

HSM2300

UL

4 high current output expander:

HSM2204

UL

Alternate communicator:

3G2080

UL

              

3G2080R

UL

           

TL280

UL

              

TL280R

UL

            

TL2803G

UL

           

TL2803GR

UL

           

PCL-422

UL

Hardwired Devices

2-wire smoke detectors:

x= A, B, or C

A: ULC listed models

B: UL listed models

C: European and Australian models

FSA-210x

UL

FSA-210xT

UL

FSA-210xS

UL

FSA-210xST

UL

FSA-210xLST

UL

FSA-210xR

UL

FSA-210xRT

UL

FSA-210xRS

UL

FSA-210xRST

UL

FSA-210xLRST

UL

4-wire smoke detectors:

x= A, B, or C

A: ULC listed models

B: UL listed models

C: European and Australian models

FSA-410x

UL

FSA-410xT

UL

FSA-410xS

UL

FSA-410xST

UL

FSA-410xLST

UL

FSA-410xR

UL

FSA-410xRT

UL

FSA-410xRS

UL

FSA-410xRST

UL

FSA-410xLRST

UL

CO detectors:

CO-12/24

UL

12-24SIR

UL

FW-CO12

UL

FW-CO1224

UL

CO1224

UL

Wireless Devices

Wireless PG smoke detectors:

PGx926

UL

PGx916

UL

Wireless PG CO detector:

PGx913

Wireless PG PIR motion detectors:

PGx904(P)

UL

PGx934(P)

UL

PGx974(P)

UL

PGx924

UL

PGx984(P)
PGx994

UL

Wireless PG glass break detector:

PGx912

Wireless PG shock detector:

PGx935

UL

Wireless PG flood detector:

PGx985

UL

Wireless PG temperature detector (indoor use):

PGx905

UL

Outdoor temperature probe (requires PGx905)

PGTEMP-PROBE

Wireless PG keys:

PGx939

UL

PGx929

UL

PGx938

UL

PGx949

UL

Wireless PG sirens:

PGx901

UL

PGx911

UL

Wireless PG repeater:

PGx920

UL

Wireless PG door/window contacts:

PGx975

UL

PGx945

UL

Central Station Receivers

SG-System I, II, III, IV      

Enclosures

PC5003C, PC4050CR (ULC Fire Monitoring), PC4050CAR (UL Commercial Burg),

CMC-1(UL Commercial Burg)

Other enclosures are available to suit a variety of system configurations.

WARNING: This manual contains information on limitations regarding product use and function and information on the 

limitations as to liability of the manufacturer. The entire manual should be carefully read.

firealarmresources.com

Summary of Contents for DSC PowerSeries neo

Page 1: ...t Test the panel completely to ensure that all features and functions operate as programmed 901 Walk Test 904 000 Wireless Placement Test Modules Wireless keypads HS2LCDWFxUL HS2LCDWFPxUL HS2LCDWFPVxU...

Page 2: ...lephone connection e Do not route any wiring over circuit boards f The installer must ensure that a readily accessible disconnect device is incorporated into the building for permanently connected ins...

Page 3: ...sistors When double end of line DEOL resistors are installed at the end of a zone loop the sec ond resistor enables the panel to determine if the zone is in alarm tampered or faulted Diagram 1 4 DEOL...

Page 4: ...quired Programming Once basic installation of the alarm panel is complete the following general configuration options can be set 000 Language Selection LCD keypads only Use this section to set the lan...

Page 5: ...ication 9 Normally Closed EOL 10 Single EOL 11 Double EOL 12 Fast Normal Loop Response Trouble Detailed Trouble 01 Service Required 01 Bell circuit 02 RF jam detected 03 Aux supply trouble 04 Time and...

Page 6: ...on PGM2 being used as a 2 wire smoke detector input This trouble is generated by a short on hardwired zones when DEOL is used Ensure a 2 2K EOL resistor is connected red red red Remove wire leads from...

Page 7: ...led in the same enclosure and configured as primary or back up with AES 128 bit encryption Compliant with EN50136 1 1 EN50136 2 1 ATS2 requirements Trouble 10 Module Tamper Press 10 to determine speci...

Page 8: ...03 Maintenance Code AAAA00 PGM Programming 007 PGM Programming 000 Main Bell Partition Assignment 1 Partition 1 2 Partition 2 3 Partition 3 4 Partition 4 5 Partition 5 6 Partition 6 7 Partition 7 8 Pa...

Page 9: ...Thursday Friday Saturday 003 Auto Disarming Holiday Schedule Holiday 1 Holiday 2 Holiday 3 Holiday 4 004 Auto Arming Pre Alert 004 005 Auto Arming Postpone Timer 000 006 No Activity Arming Timer 000...

Page 10: ...g 4 Pulse Dial After 5th Attempt 5 Parallel Communications 6 Alternate Dial 7 Reduced Dialing Attempts 8 Activity Delinquency 381 Communicator Option 2 1 Keypad Ringback 2 Bell Ringback 4 Closing Conf...

Page 11: ...may not remove any proprietary notices marks or labels from the Software Product You shall institute reasonable measures to ensure compliance with the terms and conditions of this EULA b Separation of...

Page 12: ...80 017 081 018 082 019 083 020 084 021 085 022 086 023 087 024 088 025 089 026 090 027 091 028 092 029 093 030 094 031 095 032 096 033 097 034 098 035 099 036 100 037 101 038 102 039 103 040 104 041 1...

Page 13: ...Wireless Device Record Installer Defined Access Codes System Account Code Module Type Slot Serial Number Module Type Slot Serial Number Device Type Zone Serial Number Device Type Zone Serial Number 0...

Page 14: ...Fire Installations section 001 fire zone shall be programmed as type 025 The entry delay shall not exceed 45 seconds refer to section 005 The exit delay shall not exceed 60 seconds refer to section 00...

Page 15: ...s of time Also an intruder may cut the telephone line or defeat its operation by more sophisticated means which may be difficult to detect Insufficient Time There may be circumstances when the system...

Page 16: ...entry and exit delays and bell time out for the system Note Combined entry delay and communications delay abort window shall not exceed 60s Range 30 sec to 4 min Default 30 sec Required programmable A...

Reviews: