TEMPERATURE CORRECTION CHARTS (Continued)
300/400 ft
3
(8.49/11.32 m
3
) Cylinders
(Except for Cylinders on the AQUASONIC System)
Examples:
1. The nitrogen cylinder on an ANSUL fire suppression system
indicates a pressure of 1800 psi (124.1 bar) on the pressure
gauge. The temperature of the cylinder is 80 °F (27 °C).
Reference to the chart shows that this is above the ‘‘tempera-
ture correction line’’ and the cylinder does not need to be
replaced.
2. One of the nitrogen cylinders of an ANSUL fire suppression
system indicates a pressure of 1600 psi (110.3 bar) on the
pressure gauge. The temperature of the cylinder is 80 °F
(27 °C). Reference to the chart shows that this is below the
minimum recommended pressure for this temperature.
The cylinder should be replaced by a fully charged nitrogen
cylinder.
TEMPERATURE CORRECTION CHARTS
8-1-11 Page 7
REV. 2
CYLINDER
PRESSURE
(bar)
psi
(144.8)
2100
(137.9)
2000
(131.0)
1900
(124.1)
1800
(117.2)
1700
(110.3)
1600
(103.4)
1500
(96.5)
1400
(89.6)
1300
–65
–40
–20
0
20
40
60
80
100
120
150 °F
(–54)
(–40)
(–29)
(–18)
(7)
(4)
(16)
(27)
(38)
(49)
(66) (°C)
NITROGEN CYLINDER TEMPERATURE
RECOMMENDED
OPERA
TING
PRESSURE
TEMPERA
TURE CORRECTION LINE
Summary of Contents for ANSUL PS-1000
Page 1: ...ANSUL FIRE SUPPRESSION SYSTEM OPERATION AND MAINTENANCE MANUAL Part No 78661 03...
Page 2: ......
Page 6: ......
Page 18: ......
Page 24: ......
Page 30: ......
Page 39: ......
Page 41: ...INSTALLATION ANSUL OPERATION AND AUTOMAN II C MAINTENANCE RELEASING MANUAL DEVICE ANSUL 001799...
Page 42: ......
Page 44: ......
Page 52: ......
Page 53: ......
Page 56: ......
Page 58: ......
Page 64: ......
Page 65: ......
Page 68: ......
Page 70: ......
Page 72: ......
Page 74: ......
Page 76: ......
Page 78: ......
Page 79: ......
Page 80: ......