fully sprinklered in accordance with the
recomendations of NFPA 13, NFPA
13D, or NFPA 13R. In the event of this
condition, consult the authorities
having jurisdiction for guidance and
approval.
The owner is responsible for maintain-
ing their fire protection system and
devices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
relative to any questions.

Tyco Fire Products --- www.centralsprinkler.com
451 North Cannon Avenue, Lansdale, Pennsylvania 19446 --- USA
Customer Service/Sales: Tel: (215) 362-0700 / Fax: (215) 362-5385
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500

Model BVR

No. 4-4.0

5.4 K-factor -
Fast Response  Residential

Horizontal Sidewall & Recessed Horizontal Sidewall
Glass Bulb Automatic Sprinkler

General
Description

The Central Model BVR, 5.4 K-factor
Residential Horizontal Sidewall &
Recessed Horizontal Sidewall Sprinklers
are decorative glass bulb sprinklers
designed for use in residential occupan-
cies such as homes, apartments,
dormitories, and hotels.
They are to be used in wet pipe residential
sprinkler systems for one- and two-family
dwellings and mobile homes per NFPA
13D; wet pipe residential sprinkler
systems for residential occupancies up to
and including four stories in height per
NFPA 13R; or, wet pipe sprinkler systems
for the residential portions of any occu-
pancy per NFPA 13.
The recessed version of the Model BVR
Residential Horizontal Sidewall Sprinkler is
obtained by utilizing the Model BVR
Horizontal Sidewall Sprinkler in combina-
tion with the Model BV Res./QR Re-
cessed Escutcheon Assembly.  The
recessed version of the Central Model
BVR using a Model BV Res./QR Re-
cessed Escutcheon provides up to  3/8
inch (9,5 mm) of total adjustment from the
flush Horizontal Sidewall position.
Operation: The glass bulb contains a fluid
which expands when exposed to heat.
When the rated temperature is reached,
the fluid expands sufficiently to shatter the
glass bulb, which then allows the sprinkler
to activate and flow water.

WARNING

The BVR Residential Horizontal
Sidewall Sprinklers described herein
must be installed and maintained in
compliance with this document, as well
as with the applicable standards of the
National Fire Protection Association, in
addition to the standards of any other
authorities having jurisdiction. Failure
to do so may impair the integrity of
these devices.
Because of the above cited stipulations
and the varied nature of residential
type architecture, there will be some
compartment designs which cannot be

Technical
Data

CENTRAL

BVR Sidewall

7-02

Residential
Horiz. Sidewall
Sprinklers

Design
Criteria

The Model BVR Horizontal Sidewall and
Recessed Horizontal Sidewall Sprinklers
are UL, ULC Listed and MEA Approved
for use in accordance with current NFPA
standards for use on wet pipe sprinkler
systems.  These sprinklers have been
investigated for use under smooth flat
horizontal ceilings with slopes up to 2
inches per foot, at spacings up to 16 feet
by 20 feet, using the design requirements
found in Table 1. These sprinklers have
also been investigated for use under
smooth flat sloping ceilings with slopes up
to 8 inches per foot, at spacings up to 16
feet by 20 feet, using the design
requirements found in Table 2 & 3 as well
as the sloped ceiling "Specific Application
Design Criteria" found in Figure 1.

The Recessed Horizontal Sidewall
Sprinklers are only listed with the Series
BV Res./QR Recessed Escutcheon
Assembly.

The minimum required single and multiple
sprinkler flow rates for systems designed
to NFPA 13D or NFPA 13R occupancies
are given in Table 1, Table 2, and Table 3.
The single sprinkler flow rate is the
minimum required discharge from the
most hydraulically demanding single
sprinkler and, the multiple sprinkler flow
rate is the minimum required discharge
from each of the total number of "design
sprinklers" as specified in NFPA 13D or
NFPA 13R.

(Continued on page 2)

Sprinkler Identification Number
SIN - C3396
Approvals
UL & ULC Listed. MEA (323-98-E)
(Refer to the Design Criteria Section)
Maximum Working Pressure
175 psi (12,1 bar)
Pipe Thread Connection - 1/2 inch NPT
Discharge Coefficient
K = 5.4 GPM/psi

1/2

 (77,9 LPM/bar

1/2

)

Temperature Ratings - 155

°

F/68

°

C

Finishes
Sprinkler: White Polyester, Chrome
Plated, or Natural Brass
Recessed Escutcheon: White Coated,
Chrome Plated, or Brass Plated
Physical Characteristics
The Model BVR Residential Horizontal
Sidewall Sprinkler utilizes a dezincification
resistant (DZR) bronze frame and a 3 mm
bulb. The sprinkler frame orifice is sealed
with a  gasketed spring plate (Belleville
Seal) consisting of a beryllium nickel disc
spring that is sealed on both its inside and
outside edges with a Teflon

TM

 gasket. The

compression screw is bronze, and the
deflector is brass.

SPRINKLERS FOR REPLACEMENT USE ONLY IN EXISTING SPRINKLER SYSTEMS

OBSOLETE

Summary of Contents for central bvr

Page 1: ...ailure to do so may impair the integrity of these devices Because of the above cited stipulations and the varied nature of residential type architecture there will be some compartment designs which cannot be Technical Data CENTRAL BVR Sidewall 7 02 Residential Horiz Sidewall Sprinklers Design Criteria The Model BVR Horizontal Sidewall and Recessed Horizontal Sidewall Sprinklers are UL ULC Listed a...

Page 2: ...should be submitted to Central Sprinkler Include sketches and technical details as appropriate In some instances the requirements of this document may concern specifications which are more stringent and which take precedence over those specified in NFPA 13 NFPA 13D NFPA 13R or by the authority having jurisdiction tighten the sprinkler into the sprinkler fitting Step 3 Wrench tighten the sprinkler ...

Page 3: ... minimum beam or lintel is required at the peak a minimum 4 101 6 mm maximum one half the maximum calculated spacing 36 MAX a a b b 20 M AX M EASURED ALO NG SLO PE 48 MAX 8 0 MIN D MAXIMUM SLOPE 8 12 33 7O D D MAXIMUM 8 0 OPENING ALLOWED IN PERIMETER WALLS D MAXIMUM SLOPE 8 12 33 7O a b b MEASURED ALONG SLOPE 18 MAX 4 8 M A X MAXIMUM 8 0 OPENING ALLOWED IN PERIMETER WALLS a b a b M E A S U R E D A...

Page 4: ... Remove dust lint cobwebs cocoons insects and larvae by gently brushing with a feather duster or gently vacuuming with a soft bristle i e dusting brush attach ment Exercise suitable safety precautions in the use and storage of highly flammable materials The rapid rate of fire development and spread of which can be caused by such materials can reduce the ability of the sprinkler system to aid in th...

Reviews: