ACM 400 S motor control unit
12 / 24
Function
Photoelect
ric Light
barrier
Menu “8“
Safety strips
Menu “1…4”
8K2 OSE
Sensor triggering
while opening
Sensor triggering
whole closing
gate at a standstill
-
-
-
No effect
No effect
Disable sensor
00
00
16
No effect
No effect
Stop
01
01
17
No effect
Stop
04
04
20
Stop
No effect
05
05
21
Stop
Stop
Release *)
02
02
18
No effect
Release *)
08
08
24
Release *)
No effect
10
10
26
Release *)
Release *)
Reversing
03
03
19
No effect
opens
12
12
28
closes
No effect
16
--
--
No effect
opens
17
--
No effect
opens
18
--
No effect
opens
--
--
--
No effect
opens
Automatic closing after
quitting LS
16
--
--
No effect
Closes 0.5s after
command
17
--
--
No effect
Closes 3s after
command
18
--
--
No effect
Closes 7s after
command
Combined functions
06
06
22
Stop
Release *)
07
07
23
Stop
opens
09
09
25
Release *)
Stop
11
11
27
Release *)
opens
13
13
29
closes
Stop
14
14
30
closes
Release *)
15
15
31
closes
opens
*) Release
= if an obstruction is detected the gate moves a short distance in the opposite direction (released)
Release time
(in 0.25s steps)
Menu “B“ value
00
….15
0.25s
4.00s
q) Light outputs
[X10]
Two lamps for signal and lighting purposes can be connected for
230V AC
, namely...
[X10.1] at
terminals 9 / 10
with a load of max.
200 W
,
[X10.2] at
terminals 10 / 11
with a load of max.
200 W
.
Gate status
Menu “7”value
Light output terminals 9 / 10
00
No light
Gate started
01
Lit time from 0 600s
in10s steps
…60
in limit position “Closed“
61
Light off
in limit position “Open“
Light on
Stopped along the path
Light flashes slowly (0.5Hz)
opens / closed
Light flashes quickly (4Hz)
When motor starts
62
Short pulse (1.5s)
Gate status
Menu
“6“ - value
Warning light output terminals 10 / 11
opens / closes
00
Only while motor running
01
4s before motor while motor
running
02
10s before motor while motor
running
Closes
03
4s before motor while motor
running
04
10s before motor while motor
running