TURTLE
TOUGH
®
23
WIDE ORP
Measurement
Wide ORP
Setup Parameter
Configuration
3
N/A
Sensor Type
3
P18
Default Node
3
P02
Default Baudrate
19,200
P03
Default Output Type
4-20mA
P04
Default Polarity
non-inverted
P05
Default Low Whole
0
P06
Default Low Decimal
0
P07
Default Hi Whole
100
P08
Default Hi Decimal
0
P09
Days to Recalibrate
30
P17
Integer Limits
Engineered ORP Limits
0
-2,000.0
20,000
2,000.0
% of Full Range
Engineered ORP Units
RTU Integer
0.00%
-2,000.0
0
5.00%
-1,800.0
1000
10.00%
-1,600.0
2000
15.00%
-1,400.0
3000
20.00%
-1,200.0
4000
25.00%
-1,000.0
5000
30.00%
-800.0
6000
35.00%
-600.0
7000
40.00%
-400.0
8000
45.00%
-200.0
9000
50.00%
0.0
10000
55.00%
200.0
11000
60.00%
400.0
12000
65.00%
600.0
13000
70.00%
800.0
14000
75.00%
1,000.0
15000
80.00%
1,200.0
16000
85.00%
1,400.0
17000
90.00%
1,600.0
18000
95.00%
1,800.0
19000
100.00%
2,000.0
20000
0.00%
-2,000.0
Default Low Setpoint P06/P07
100.00%
2,000.0
Default High Setpoint P08/P09
CHANGING ORP VALUES ABOVE GET % SCALING COMPUTED
Note 1:
Low and high analog setpoints should be at least 1,000 MODBUS RTU steps apart.