TURTLE
TOUGH
®
15
Display Features
For Sensor Type 1 pH
- the “pH / ORP” LED will be continuous illuminated unless otherwise indicated below
•
-2.00 to -0.01 displayed as 2.00 to 0.01 flashing
•
0.00 to 9.99 displayed not flashing with two decimal points
•
10.0 to 16.0 display with one decimal point
If the ‘
Down
’ button is pressed, then the temperature of connected sensor is shown *
If
‘Down’
button is held for 3 to 5 seconds, then the absolute mV will be shown *
If the
‘Up’
button is pressed, then the mA for the current process value and scaling will be shown
For Sensor Type 2 ORP
- the “pH / ORP” LED will be continuous illuminated unless otherwise indicated below
•
-999 to -1 displayed as 999 to 1 flashing
•
0 to +999 displayed not flashing
If the
‘Down’
button is pressed, then the temperature of connected sensor is shown *
If
‘Down’
button is held for 3 to 5 seconds, then the absolute mV will be shown *
If the
‘Up’
button is pressed, then the mA for the current process value and scaling will be shown
For Sensor Type 3 Wide ORP
- the “pH / ORP” LED will be continuous illuminated unless otherwise indicated below
•
-2,000 to -1,000 display as 2.00 to 1.00 with LED flashing
(units are Volts)
•
-999 to -1 displayed as 999 to 1 flashing
•
0 to +999 displayed not flashing
•
+1,000 to +2,000 display as 1.00 to 2.00 with LED not flashing
(units are Volts)
If the
‘Down’
button is pressed, then the temperature of connected sensor is shown *
If
‘Down’
button is held for 3 to 5 seconds, then the absolute mV will be shown *
If the
‘Up’
button is pressed, then the mA for the current process value and scaling will be shown
For Sensor Type 4 Dissolved Oxygen (D.O.)
- the “D.O.” LED will be continuous illuminated unless otherwise
indicated below
•
If P10 is ‘ppm’ then 0.00 to 150.00 ppm units displayed not flashing as 0.00 to 9.99, 10.0-99.9 and 100-150 ppm
•
If P10 is ‘%Sat’ then 0.0-1,500.0 percent (%) saturation units displayed not flashing as 0.0-99.9%, 100-999%
with the special range of 1,000-1,500% displayed as 1.00-1.50 with LED flashing
(kilo % Saturation Units)
If the
‘Down’
button is pressed, then the temperature of connected sensor is shown *
If
‘Down’
button is held for 3 to 5 seconds, then the absolute mV will be shown *
If the
‘Up’
button is pressed, then the mA for the current process value and scaling will be shown
If
‘Up’
button held and P10 is ‘ppm’ (basis of 4-20mA output) then % Saturation units are displayed
If
‘Up’
button held and P10 is ‘%Sat’ (basis of 4-20mA output) then ppm units are displayed
For Sensor Type 5 Ion Selective (ISE)
- the
“ISE”
LED will be continuous illuminated unless otherwise indicated below
•
0.00-9.99, 10.0-99.9, 100-999 ppm units displayed same as per TT-MA-ISE transmitter
kilo-ppm units displayed with LED flashing to signify kilo-ppm scale is in use same as per TT-MA-ISE-kilo
• 1.00-9.99 (1,000-9,990 ppm), 10.0-99.9 (10,000-99,900 ppm) and 100-999 (100,000-999,000 ppm)
If the
‘Down’
button is pressed, then the temperature of connected sensor is shown *
If
‘Down’
button is held for 3 to 5 seconds, then the absolute mV will be shown *
If the
‘Up’
button is pressed, then the mA for the current process value and scaling will be shown
If
‘Up’
button held for 3 to 5 seconds, pION value is shown with same scheme used display the pH
For Sensor Type 6 or 7 Conductivity (EC)
- the
“Cond”
LED will be continuous illuminated unless otherwise indi
-
cated below
•
<1.00 mS shown as flashing from 1 to 999 uS/cm with 0.01-9.99, 10.0-99.9 and 100-999 floating decimal point
•
1.00 to 999 mS/cm shown displayed not flashing with 0.01-9.99, 10.0-99.9 and 100-999 floating decimal point