Operation
Software diagnostic messages
202
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
9.6.3
Diagnostic messages – digital channels
Byte no.
Bit
7
6
5
4
3
2
1
0
0
VErrV1C1
VErrV1C0
3
ERR3
ERR2
ERR1
ERR0
Meaning of the diagnostic bits
Designation
Meaning
VErrV1C0Ch0Ch1
Overcurrent at power supply terminal VAUX1 at socket C0 (channels 0 and 1)
VErrV1C1Ch2Ch3
Overcurrent at power supply terminal VAUX1 at socket C1 (channels 2 and 3)
ERRx
Error message on channel x
9.6.4
Diagnostic messages – device status
Byte no.
Bit
7
6
5
4
3
2
1
0
0
DIAG
1
FCE
COM
V1oPoE
Meaning of the diagnostic bits
Designation
Meaning
DIAG
Module diagnostics present
FCE
Force mode in the DTM active
COM
Internal error
V1oPoE
Undervoltage detected at power supply terminal V1 or power sourcing equip-
ment (PSE) type 1