V02.00 | 2020/08
127
7.10.3
Connecting Modbus master and Modbus slave online
Select the slave device.
Click
Online
Ò
Login
.
7.10.4
Reading out process data
The I/O image of the slave can be viewed in Online mode.
Double-click the Modbus TCP slave.
Click the
Modbus TCP Slave I/O Mapping
tab.
a
The process data is displayed. In this example, the “Tag present” bit is set if a tag is
present in the detection range of the read/write head connected to channel 1.
Fig. 124: Example: process data
Refer to the operating instructions of the connected slave for the mapping the channels (see
figure below).
Fig. 125: Example: extract from the Modbus TCP mapping for the connected TBEN-S2-2RFID-4DXP slave device