Commissioning
Addressing the device
28
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
7.3
Addressing the device
7.3.1
Setting the F address at the device
Open the cover above the switches.
Set the F address via the three rotary coding switches under the cover at the device.
Execute a power cycle.
DANGER
Intrusion of liquids or foreign bodies through open cover
Danger to life due to failure of the safety function
Tightly close the cover above the switches.
BUS
ERR
PROFINET
ETH1
ETH2
F-Address
0
9
8 7
6
5
4
3
2
1
0
9
8 7
6
5
4
3
2
1
0
9
8 7
6
5
4
3
2
1
x 100
x 10
x 1
Memory
Fig. 18: Rotary coding switches at the device
In the delivery state, the rotary switches are set to 000 (0 - 0 - 0). The addresses 000 and ≥ 900
are no valid F addresses.
Switch position
Meaning
0
Delivery state, no valid F address
1…899
F address, accept setting by restarting the device
900
Factory Reset: resets the device to factory settings
901
Erase Memory: deletes the content of the memory chip.