12
Operating instructions
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
7.2.3
Address assignment
➤
➤
Set the F-address (PROFIsafe address) for the TBPN-L1-FDIO1-2IOL using the three rotary
coding switches under the cover at the device.
The module is delivered with the switch position 0. The address 0 and the addresses ≥ 900 are
no valid F-addresses.
Switch position
Meaning
0
State of delivery, no valid address
1…899
F-address, the setting is accepted after a device restart
900
Factory Reset: reset of the device to factory settings
901
Erase Memory Stick: deletes the content of the configuration memory
7.2.4
Configuring
The safety function of the safe channels can only be configured via the software Turck Safety
Configurator.
After the configuration, the device generates a CRC and a configuration protocol. This protocol
has to be checked and validated by the user. The CRC is stored as reference in the configuration
of the PROFIsafe control and guarantees the correct safety function.
Further information about the software can be found in the online help.
The configuration of the safe I/O channels set via the Turck Safety Configuratior is automatically
stored to a pluggable memory stick which is part of the scope of delivery. In case of a device ex-
change, the device configuration can be transferred to another device using the memory stick.