TBIP-L4-FDIO1-2IOL Instructions For Use Manual Download Page 95](http://html1.mh-extra.com/html/turck/tbip-l-fdio1-2iol-series-tbip-l4-fdio1-2iol/tbip-l-fdio1-2iol-series-tbip-l4-fdio1-2iol_instructions-for-use-manual_1181729095.webp)
87
2018/02
TBPN-L1
-FDIO1-2IOL- Saf
e
I/O
9.1.3
Error LED (ERR)
9.1.4
BUS LED
9.1.5
Channel-LEDs
LED
GREEN
LED
RED
Meaning
off
off
Input active
on
off
Input active, 24 V at input
blinking
off
Self-test input
off
blinking
Cross-circuit
off
on
Discrepancy
C0 and C1(FDI)
LED
GREEN
LED
RED
Meaning
Remedy
off
off Device
not
supplied,
device switches to the safe state
Check the voltage supply.
on
off
No diagnostic message available
off
on
Diagnostic message pending
Check the diagnostic message.
on
on
No valid state,
device switches to the safe state
off
Initialization, configuration trans-
fer from memory chip running
Wait until the procedure is finished.
LED
GREEN
LED
RED
Meaning
Remedy
off
off Device
not
supplied,
device switches to the safe state
Check the voltage supply.
on
off
Active connection to a master
blinking
off
Device is ready for operation
off
on
IP address conflict or restore mode
or timeout
–
Check the network for duplicate IP
addresses,
–
wait for the device to be ready for
operation
off
blinking
Blink-/wink-command active
blinking
blinking
Autonegotiation and/or waiting
for DHCP-/BootP-address assign-
ment.
–
wait for the device to be ready for
operation
–
Check the address setting per DHCP/
BootP.
Summary of Contents for TBIP-L...-FDIO1-2IOL Series TBIP-L4-FDIO1-2IOL
Page 1: ...Your Global Automation Partner TBIP L FDIO1 2IOL Safety Block I O Module Instructions for Use...
Page 2: ...2 Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com...
Page 118: ...Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com 2...