Connecting
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
36
5.4.1
Switching Examples
Safety Inputs
Safety Outputs
Safe equivalent input for potential free contacts (NC/NC)
Safe antivalent input for potential free contacts (NC/NO)
Safe electronic input (OSSD)
Fig. 12: Switching examples for safe inputs
Safe output PP-switching
For PP-switching outputs, connect the negative pole
of the load to the GND of the respective output (pin 3).
Another connection to the GND of the power supply
unit is not permitted!
The wiring has to allow an exclusion of faults regarding
cross connection.
Safe output PM-switching
For PM-switching outputs, connect the negative pole
of the load to the M-connector of the respective out-
put (pin 2).
Fig. 13: Switching examples for safe outputs
2 FDI (T2)
1 T1
3 n.c.
4 FDI (T1)
5 T2
TBPN-L1…
2 FDI (T2)
1 T1
3 n.c.
4 FDI (T1)
5 T2
TBPN-L1…
2 FDI (T2)
1 T1
3 n.c.
4 FDI (T1)
5 T2
TBPN-L1…
2 FDI (T2)
1 VAUX1
3 GND
4 FDI (T1)
5 n.c.
OSSD
+
–
TBPN-L1…
2 n.c.
1 n.c.
3 GND (V1)
4 FDO +
5 n.c.
TBPN-L1…
2 FDO –
1 n.c.
3 n.c.
4 FDO +
5 n.c.
TBPN-L1…