![turck TBIP-L...-FDIO1-2IOL Series
TBIP-L4-FDIO1-2IOL Instructions For Use Manual Download Page 26](http://html1.mh-extra.com/html/turck/tbip-l-fdio1-2iol-series-tbip-l4-fdio1-2iol/tbip-l-fdio1-2iol-series-tbip-l4-fdio1-2iol_instructions-for-use-manual_1181729026.webp)
Product description
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
18
3.4.3
Technical data – safety inputs
General
Safe status
0 V (de-energized)
Current sink
against 0 V
Inputs for potential free contacts/antivalent switches
Max. loop resistance
< 150
Max. cable length limited by
line capacity
max. 1
F at 150
Test pulses
typical
0.6 ms
maximum
0.8 ms
Interval between two test pulses
for static inputs
min. 900 ms
for dynamic inputs
min. 30 ms
No connection to external potential
Inputs for OSSDs
Max. OSSD supply per channel
2 A
Max. output current T1_A
0 A, must not be connected to external potential
Low level
EN 61131-2 type 1 (< 5 V; < 0,5 mA)
High level
EN 61131-2 type 1 (> 15 V; > 2 mA)
Max. tolerated test pulse width
1 ms
Min. interval between two test pulses
12 ms at 1 ms test pulse width
8.5 ms at 0.5 ms test pulse width
7.5 ms at 0.2 ms test pulse width
Times
Internal delay time
(for calculating the Watchdog time)
10 ms
Reaction times
see
Summary of Contents for TBIP-L...-FDIO1-2IOL Series TBIP-L4-FDIO1-2IOL
Page 1: ...Your Global Automation Partner TBIP L FDIO1 2IOL Safety Block I O Module Instructions for Use...
Page 2: ...2 Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com...
Page 118: ...Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com 2...