![turck TBIP-L...-FDIO1-2IOL Series
TBIP-L4-FDIO1-2IOL Instructions For Use Manual Download Page 158](http://html1.mh-extra.com/html/turck/tbip-l-fdio1-2iol-series-tbip-l4-fdio1-2iol/tbip-l-fdio1-2iol-series-tbip-l4-fdio1-2iol_instructions-for-use-manual_1181729158.webp)
IO-Link – Functions for Acyclic Communication
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
32
4.1.5
Subindex 68: Master Port Scan Configuration
28 byte are returned per IO-Link port
IO-Link
Port
Content
Length
Format
Description
Port 1
Vendor_ID
2 byte
UINT16
Vendor ID of the connected device
Device_ID
4 byte
UINT32
Device-ID of the connected device
Function_ID
2 byte
UINT16
reserved
Serial_Number
16 byte
String
Serial number of the connected device
COM_Revision
1 byte
UINT8
IO-Link version
Proc_In_Length
1 byte
UINT8
Process input data length of the con-
nected device
Proc_Out_Length
1 byte
UINT8
Process output data length of the con-
nected device
Cycle time
UINT8
Cycle time of the connected device
Port 2
Structure similar to port 1
Entity_
Port
IO-Link
subindex
Read
Write
Length
Description
0
68
r
max. 120 byte
This object serves for reading the
Configuration of the IO-Link devices con-
nected to the IO-Link master.
Summary of Contents for TBIP-L...-FDIO1-2IOL Series TBIP-L4-FDIO1-2IOL
Page 1: ...Your Global Automation Partner TBIP L FDIO1 2IOL Safety Block I O Module Instructions for Use...
Page 2: ...2 Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com...
Page 118: ...Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com 2...