IO-Link – Functions for Acyclic Communication
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
30
4.1.2
Subindex 65: IO-Link Events
Structure of the read data:
Byte 0 contains 2 bit per IO-Link port which show, if the process data of the connected device are
valid or not.
Byte 0 is followed by 4 byte per Diagnostic Event which clearly assign and specify the diagnostic
message.
A maximum of 14 Events per IO-Link port are shown.
Byte
Bit
7
6
5
4
3
2
1
0
0
x
PD_Valid input port 1
x
PD_Valid output port 1
x
PD_Valid input port 2
x
PD_Valid output port 2
1
Qualifier
Defines the type of the Event
(Warning, Notification, Single
Shot Event, etc.) in accor-
dance with IO-Link specifica-
tion "IO-Link Interface and
System".
2
Port
Indication of the IO-Link port
which sends an Event.
3
Event Code high byte
High or respectively low byte
of the Event Code sent.
4
Event Code low byte
...
222
Qualifier
see byte 1 - 4
223
Port
224
Event Code high byte
225
Event Code low byte
Entity_
Port
IO-Link
subindex
Read
Write
Length
Description
0
65
r
255 byte
This object serves for reading the IO-Link
events.
NOTE
On "appears" (coming diagnostics) and "Single Shot Events" are shown, as long as they are
pending.
Summary of Contents for TBIP-L...-FDIO1-2IOL Series TBIP-L4-FDIO1-2IOL
Page 1: ...Your Global Automation Partner TBIP L FDIO1 2IOL Safety Block I O Module Instructions for Use...
Page 2: ...2 Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com...
Page 118: ...Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com 2...