Properties of the IO-Link channels
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
20
2.8
Diagnostics and Status
2.8.1
LED Displays Channel LEDs (C4 to C5)
LED
LED
GREEN
LED
RED
Meaning
Remedy
IO-Link
C6, LED 12
and
C7, LED 14
Channel in IO-Link-mode
off
off
No IO-Link communication, diag-
nostics deactivated
–
connect an IO-Link device
–
Parameterize the channel as
DI if necessary.
–
wire break in IO-Link cable
possible
blink-
ing
off
IO-Link communication active,
valid process data
off blink-
ing
IO-Link communication active and
module error, invalid process data
–
No input data received from
the connected device (only
valid for devices with an input
data length > 0),
–
No reaction from the con-
nected device to the sending
of output data (only valid for
devices with an output data
length > 0),
–
connected device sends an
error: "process data invalid".
see also:
Start-up Problems – Fre-
quently Failure Causes (page
38)
off
on
No IO-Link communication
and/or module error,
invalid process data
Channel in DI-mode
off
off
Input active
on
off
Input signal active
DXP
C6, LED 13
and
C7, LED 15
off
off
-
on
off
In-/ output signal active
off
on
Short circuit at output of the
respective channel
Summary of Contents for TBIP-L...-FDIO1-2IOL Series TBIP-L4-FDIO1-2IOL
Page 1: ...Your Global Automation Partner TBIP L FDIO1 2IOL Safety Block I O Module Instructions for Use...
Page 2: ...2 Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com...
Page 118: ...Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com 2...