11
V01.0| 2017/04
TBPN-L1
-FDIO1-2IOL -
Standard IO-Link
2.5.2
Process Input Data – IO-Link Master Channels
Word
Bit 15
Bit 14
Bit 13
Bit 12
Bit 11 Bit 10 Bit
9
Bit
8
Bit
7
Bit
6
Bit
5
Bit
4
Bit
3
Bit
2
Bit
1
Bit
0
Ba
sic
n + +1
DXP15
C7P2
DI14
C7P4
DXP13
C6P2
DI12
C6P4
-
-
n + 2
-
DVS14
-
DVS12 -
...
IO-Link chan-
ne
ls
n + 11
…
n + 26
IOL1 – process input data (connector C6)
Structure depends on the channel parameterization
n + 27
…
n + 42
IOL2 – process input data (connector C7)
Structure depends on the channel parameterization
Diagnostics
Overcurrernt sensor supply (IOL1)
n + 43
-
VERRV1
K1213
-
Overcurrent output
n + 44
SCO15
-
SCO13
-
IO-Link port diagnostics
IOL1 (connector C6)
n + 45
GENR
OVL
VHIGH
VLOW ULVE
LLVU
OTMP PRM
ER
EVT2 EVT1
PD
INV
HW
ER
DS
ER
CFG
ER
PPE -
IOL2 (connector C7)
n + 46
Assignment similar to port IOL1
IO-Link
Events
n + 47
Port (1st Event)
Qualifier (1st Event)
n + 48
Event Code (1st Event)
…
n + 77
Port 16th Event)
Qualifier (16th Event)
n + 78
Event Code (16th Event)
Name
Value
Meaning
DXPx
CxPy
0
Input active
1
Input active
DVSx
Input value valid (Data Valid Signal)
0
The IO-Link data are valid.
Possible causes:
–
Sensor supply is below the admissible range,
–
IO-Link port is parameterized as simple digital input,
–
No device connected to the masters,
–
No input data received from the connected device (only valid for devices with an
input data length > 0),
–
No reaction from the connected device to the sending of output data (only valid
for devices with an output data length > 0),
–
The connected device sends an error "process input data invalid.
1
The IO-Link data are valid.
Summary of Contents for TBIP-L...-FDIO1-2IOL Series TBIP-L4-FDIO1-2IOL
Page 1: ...Your Global Automation Partner TBIP L FDIO1 2IOL Safety Block I O Module Instructions for Use...
Page 2: ...2 Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com...
Page 118: ...Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com 2...