7
2 Getting Started
2.1 About this document
The configuration guide provides information about configuration of the TBEN-LH-8IOL including:
Address switches
IP address assignment
Configuration options with Rockwell and Omron PLCs
NOTE
The device data sheet and technical information is available for download at
www.turck.us.
2.2 Factory default IP address
The TBEN-LH-8IOL device is shipped with address switches set to 600 (PGM-DHCP). It is factory default
position of the rotary switches which is associated with the IP address:
IP Address:
192.168.0.254
Subnet mask:
255.255.252.0
Gateway:
0.0.0.0
The device has limited functionality in this state:
DHCP client is active and running; use any service to assign IP address
Web server is active
Some other services are active
ARGEE PLC is running
The device responds to the PING command as follows:
Figure 2.1 - Ping
The first step in the device configuration is to assign an operational IP address.
The device DHCP client is running and waiting for an IP address assignment. When IP address is
acquired, the DHCP becomes disabled.