33
4 Configure TBEN-LH-8IOL with Rockwell PLC
The configuration of the TBEN-LH with the Logix5000 controllers, using RSLogix5000 / Studio5000
programming environment may be done using:
EDS file
Generic device profile
4.1 TBEN-LH-8IOL Configuration using EDS files
4.1.1 Install EDS file
The EDS file is the Electronic Data Sheet or the device configuration file, described in the
“Volume 1, Common Industrial Protocol (CIP), Edition 3.22, by ODVA”.
The procedure:
Download
TBEN-LH-8IOL_R2.7.EDS
file from the TURCK web site
In the RSLogix5000 menu bar, expand the
Tools
drop down menu and click on the
EDS
hardware Installation Tool
Figure 4.1 – Tools menu
In the
Rockwell Automation’s EDS Wizard
dialog, click at the
Register and EDS file(s)
and
Next
Follow the dialog to complete device registration
Figure 4.2 – Register an EDS file(s)