Product Description
Functions and operating modes
18
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
Protocol Dependent Functions
The device Supported the following Ethernet protocol specific functions:
PROFINET
n
FSU - Fast Start-Up (prioritized startup)
n
Topology discovery
n
Address assignment via LLDP
n
MRP (Media Redundancy Protocol)
EtherNet/IP™
n
QC – QuickConnect
n
Device Level Ring (DLR)
5.4.2
IO-Link channels
The IO-Link master module TBEN-L…-8IOL has four Class A IO-Link ports (slots C0…C3) and
four Class B IO-Link ports (slots C4…C7).
The eight IO-Link channels can be parameterized independently of each other and operated
either in IO-Link mode or in SIO mode (DI).
Simple IO-Link Device Integration (SIDI)
Turck's Simple IO-Link Device Integration (SIDI) simplifies the handling of IO-Link devices in
PROFINET engineering systems. Since the devices are already integrated in the GSDML file of
the master, the user can select the devices from the device library (for example in the TIA
portal) and integrate them into his project via drop-down fields as if the devices were submod-
ules of a modular I/O system. The user benefits from plain text access to all device properties
and parameters. Measuring ranges, switching points and pulse rates can be set directly from
the engineering system - without programming or additional software.
5.4.3
Configurable digital channels – functions
The device is provided with four digital channels, which can be configured as inputs or outputs
according to the application requirements. In all, up to four 3-wire PNP sensors or four PNP DC
actuators with a maximum output current of 0.5 A can be connected per input or output.