PK01VR…N vacuum
PK010R…N pressure

Technical Data

Dimensions

Electrical Data

Response time <2.5 ms
Operating frequency 400 Hz
Supply voltage 10.8-30 V, keyed residual ripple 10% 
Power supply must be limited to 150 VA max
Input current during programming <55 mA
Input current in normal operation <35 mA
Switchable outputs 2x PNP 125-250 mA 
short-circuit protected
Display 3 digit 7 segment display
Ambient temperature effect: 3% of measured 
value of 0 to 50

°

C

Repeat accuracy: 0.2% of measured value
Hysteresis adjustable: 0 to 100%
Measuring range: 0 to -1 bar/0 to 10 bar
Max. over pressure: 5 bar/16 bar









Environmental Conditions

Protection: IP 65
Measuring medium: fi ltered compressed air, 
lubricated or unlubricated, inert gases
Emitted interference adheres to DIN EN 50081-1
Interference immunity adheres to DIN EN 50082-2
High voltage test 1000 VDC 1 min
Insulation resistance >100 M

Ω

 at 500 VDC

Operating temperature: 0 to +50°C
Storage temperature: -20 to +85°C
Permissible humidity: 10 to 90% RH
Shock resistance: 10G XYZ
Vibration resistance: 10 to 55 Hz, 1.5 mm,
XYZ 2 hours

Mechanical Data

Electrical connector: M8 4-pin
Process connector: male 1/8” NPT
Weight: approx. 40 g
Wetted parts: nickel plated brass














Circuits

Status LED
Out 2

Status LED
Out 1

Up

Down

Mode

Programming

Start-Up

 

Apply Voltage

 

Display

Segment

Check

Type

Pressure

Unit

Measure

Mode

Display

Output 1

Output 2

Special
Functions

Hysteresis
Mode

Hysteresis
Mode

Pressure
Unit Bar

Unlock

-0.46 bar

-0.79 bar

0.07 bar

NC Mode

0.07 bar

NC Mode

0 sec.

0 sec.

0 sec.

0 sec.

Output 1

Output 2

Special
Functions

Pressure
Unit

Unlock

Hysteresis
Mode

Switching
Threshold

Closing
Delay

Release
Delay

Normally
Closed

Hysteresis

Comparator
Mode

Upper

Switching

Threshold

Closing
Delay

Release
Delay

Normally
Open

Lower

Switching

Threshold

Factory
Settings

Rotate
Display 180°

1. Factory Settings

The Clear All special 
function loads the 
factory settings, and 
all previous settings 
are cleared.

2. Setting Options

- Menu items listed under OU1 are settings specifi c to output 1
- Menu items listed under OU2 are settings specifi c to output 2
- Menu items listed under SF OU2 are general settings which infl uence both outputs.

Output setting options

 Hysteresis mode

 - 

Switching 

threshold

 - 

Hysteresis

 

- Type of contact (normally open, normally closed)

 - 

Closing 

delay

 - 

Release 

delay

 Comparator mode

 

- Upper switching threshold

 

- Lower switching threshold

 

- Type of contact (normally open, normally closed)

 - 

Closing 

delay

 - 

Release 

delay

Special functions settings options

 

Vacuum unit for PK01VR => bar, mmHg, inHg, KPa

 

Pressure unit for PK01VR => bar, psi, MPa

 

Clear All => factory setting loaded

 

Key lock activated = BLC, inactive = UnL

 

Rotate display 180°

3. General Procedure for Adjusting Settings

 

By following the fl ow diagram, you can move to any menu item you wish

 

using the three buttons (Up, Down and Mode).

 

For example: output 2

 - 

Comparator 

mode

 

- Lower threshold -0.3 bar

 

- Upper threshold -0.5 bar

 

- Position of normally closed contact

 

- Closing delay 0 sec.

 

- Release delay 0 sec.

 

Procedure: Measure mode output

 a) 

Briefl y press Mode button 

 

=> OU1 display

 b) 

Briefl y press Up button 

 

=> OU2 display

 c) 

Briefl y press Mode button to enter Menu level 

=> HY2 display

 

d)  Proceed to desired menu item with Up or Down 

 

 

button and confi rm by pressing the Mode button.

 

e)  In this case: confi rm HY2 with Mode button. 

=> HY2 display fl ashes

 

f )  Go to the desired setting with the Up or Down button.

 

 

In this case: CP2.  Then confi rm setting with Mode button.

 

g)  To adjust further settings, follow the procedure in (d) above.  In this case, set U-2

 

 

(lower threshold) and confi rm with Mode button. 

=> U-2 display fl ashes

 

h)  Adjust the desired setting with the Up or Down button.  

 

 

In this case: set U-2 to 0.50 and then confi rm setting with Mode button.

 

i)  Proceed in the same way for all other settings.

 

j)  To enter another setting level, e.g. output 1 (OU1) or special functions (SF), you use 

 

 

the Up or Down button to go to the menu item rEt (Return). If this is confi rmed with 

 

 

the Mode button, you arrive at the previous level.  In this case you would arrive at 

 

 

the menu item OU2 and now you can switch between the menu items Output 1 or 

 

 

Special functions with the Up or Down button in order to adjust settings.

4. Activate Key Lock

 

The locking function ensures that the switch settings are safeguarded against 

 

unintentional changes or manipulation.  To activate the locking function, proceed

 as 

follows:

 

 

Starting state is Measure  

 

=> Display: Pressure activated

 

 Briefl y press Mode button (select level)    

=> Display OU1

 

 

Press Up or Down button until SF reached  

=> Display SF

 

 Briefl y press Mode button until menu entered 

=> Display PU

 

 

Press Up or Down button until UnL reached 

=> Display UnL

 

 Briefl y press Mode button until menu entered 

=> Display UnL fl ashes

 

 

Set BLC with Up or Down button 

 

=> Display BLC fl ashes

 

 Confi rm setting with Mode button 

 

=> Display Measure

5. Deactivate Key Lock

 

 Briefl y press Up, Down and Mode buttons simultaneously     => Display BLC

 

 Briefl y press Mode button once 

 

=> Display BLC fl ashes

 

 

Set UnL with Up or Down button 

 

=> Display UnL fl ashes

 

 Confi rm with Mode button 

 

=> Display UnL static

 

 

Return to Measure state via rEt (Return) menu item

6. Selectable Display Units

The following units of measurement are available

7. Setting Display To Zero

 

 

Operate switch in Measure mode

 

 

Depress Mode button for 3 sec.

 

 

Display is set to zero

8. Peak Values

 

 Briefl y press Down button, the lowest measured value will be displayed for 3 sec.

 

 Briefl y press Up button, the highest measured value will be displayed for 3 sec.

9. Error Messages

PK01VR Display

Procedure for adjusting settings

bar

KPa

mmHg

inHg

- Looking at the flow diagram, select the
menu item SF (special functions) and
briefly press Mode button.
- PU appears on the display (pressure unit).
- Select PU with Mode button. Now the
desired unit can be selected with the Up or
Down button.
- Confirm the selected unit with the Mode
button and exit the menu via the rEt
function (Return).

PK010R Display

bar

Psi

bar

MPA

Error Messages

Cause

Overcurrent
Out1

Overcurrent
Out2

Applied vacuum
> range

EEPROM
defective

Distance to
zero point >3%

Output 1 overloaded
(current > 125 mA)

EEPROM defective, data
memory defective

Vaccuum or pressure was
higher than +/- 3% of the
measuring range

Pressure instead of vacuum

Remedy

Pressure instead
of vacuum

Output 2 overloaded
(current > 125 mA)

Applied vacuum >
measuring range

Increase load impedance

Increase load impedance

Apply vacuum

Switch defective, replace

Put the vacuum within the
measure range

Reset zero point to
ambient pressure