background image

Inductive sensor

NI5-EM12-Y1X-H1141

Edition

 • 

2015-02-13T13:35:06+01:00

1 / 5

Hans Turck GmbH & Co.KG 

ñ

 D-45472 Mülheim an der Ruhr 

ñ

 Witzlebenstraße 7 

ñ

 Tel. 0208 4952-0 

ñ

 Fax 0208 4952-264 

ñ

 [email protected] 

ñ

 www.turck.com

Type code

NI5-EM12-Y1X-H1141

Ident no.

4010301

Rated operating distance Sn

5 mm

Mounting condition

non-flush

Assured switching distance

ð

 (0,81 x Sn) mm

Repeatability

ð

 2 % of full scale

Temperature drift

ð

 ± 10 %

Hysteresis

1…10 %

Ambient temperature

-25…+70 °C

Output function

2-wire, NAMUR

Switching frequency

2  kHz

Voltage

Nom. 8.2  VDC

Non-actuated current consumption

ï

 2.1 mA

Actuated current consumption

ð

 1.2 mA

Approval acc. to

KEMA 02 ATEX 1090X

Internal capacitance (C

i

) / inductance (L

i

)

150 nF / 150 µH

Device designation

É

 II 1 G Ex ia IIC T6 Ga/II 1 D Ex ia IIIC T115 °C

Da
(max. U

i

 = 20 V, I

i

 = 20 mA, P

i

 = 200 mW)

Construction

threaded barrel, M12 x 1

Dimensions

52 mm

Housing material

stainless steel, V2A (1.4301)

Material active area

plastic, PA

Max. tightening torque housing nut

10 Nm

Connection

male, M12 x 1

Vibration resistance

55 Hz (1 mm)

Shock resistance

30 g (11 ms)

IP Rating

IP67

MTTF

6198 years acc. to SN 29500 (Ed. 99) 40 °C

Switching state

LED yellow

ATEX category II 1 G, Ex zone 0

ATEX category II 1 D, Ex zone 20

SIL2 as per IEC 61508

Threaded barrel, M12 x 1

Stainless steel, 1.4301

DC 2-wire, nom. 8.2 VDC

Output acc. to DIN EN 60947-5-6 (NA-

MUR)

M12 x 1 male connector

Wiring diagram

Functional principle

Inductive sensors detect metal objects con-
tactless and wear-free. For this, they use a
high-frequency electromagnetic AC field that
interacts with the target. Inductive sensors
generate this field via an RLC circuit with a
ferrite coil.
We offer special versions for temperatures of
-60 °C up to +250 °C.

Reviews: