V01.00 | 2021/11
13
5
Installing
The sensor detects the surface of the medium nearest to the sensor and outputs the distance.
The sensors can be installed in any alignment according to application requirements. The
sound wave is propagated vertically to the sonic transducer at an opening angle of 15°
(LUS211-40…) and 16° (LUS211-130…). The display of the unit can be rotated by 180°
(see parameter DiSr). The maximum tightening torque for fastening the sensor is 40 Nm.
S
min
Fig. 5: Mounting the LUS211…
Install the sensor at the intended mounting location.
Install the sensor in such a way that no foreign objects are located in the detection range
or in the blind zone.
0
-15
-10
-5
5
10
15
0
10
20
30
40
cm
20x20 mm
ø 27 mm
0
-30
-20
-10
10
20
30
0
20
40
60
80
120
140
100
cm
100x100 mm
20x20 mm
ø 27 mm
Fig. 6: LUS211-40… wave pattern
Fig. 7: LUS211-130… wave pattern
When using more than one ultrasonic sensor in an application: Avoid the overlapping of
sonic cones. An overlap can occur if two sensors are mounted less than 200 mm
(LUS211-40…) or 450 mm (LUS211-130…) apart. If this minimum distance is not ensured,
synchronize the sensors via IO-Link.
Optional: Rotate the sensor head within the 340° range to align the connection to the I/O
level as well as to ensure optimum operability and readability.