D301171 - IO-Link master 1108
3-3
Technical data
3
Technical data
Figure 4:
SDPX-IOL4-
0001
Table 6:
Technical data
Power supply
U
B
nominal value (range)
24 V DC (21,6 to 28,4 VDC)
I
B
max. 200 mA
U
L
24 V DC (21,6 to 28,4 VDC)
Not required, only monitored for an eventual
transmission.
Physical interfaces
– FIeldbus
PROFIBUS-DP
9.6 kBit/s to 12 MBit/s
potential isolation between fieldbus and oper-
ating voltage
Addressing fieldbus
1 - 100 via dec. rotary coding switches
(00 = addr. 100)
Fieldbus connection technology
2 × M12
Fieldbus shield connection
via PROFIBUS-DP cable
– Inputs
Pin 4 in SIO-mode and Pin 2
Number of channels
4 (8) digital pnp inputs (EN 61131-2)
Input voltage
21.6 ... 28.4 VDC from operating voltage
Signal voltage low level
-3 to 5 VDC (EN 61131-2, type 2)
Singal voltage high level
11 to 30 VDC (EN 61131-2, type 2)
Max. input current
6 mA
– Inputs (IO-Link mode)
Pin 4
Parameterization:
support of IO-Link specification V1.0
GSD, function block and FDT/DTM
Synchronization
port spanning synchronization possible
Diagnostics
mapping of the IO-Link-diagnostics into the
DP-diagnostics
26,5
203
23
210
30
C0 C1
C2 C3
33
36,5
C4
C5
C7
C6
26,5
203
23
210
30
C0 C1
C2 C3
33
36,5
C4
C5
C7
C6